101-01 Rockaway Boulevard
Queens, NY 11417BBL 4-09540-0002Map
Owner of record: NYC Department Of Education
101-01 Rockaway Boulevard is a school building built in 1929 in Queens, 11417. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 49
- ECB violations
- 100
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 49
- Elevator elevatorrequired
Cease use
Oct 6, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 6, 2021
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 6, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 6, 2021
Dob violation - active - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2020
Jun 20, 2021
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 2, 2019
Dob violation - resolved
Show 39 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Aug 2, 2019
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 1, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 15, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 22, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 19, 2014
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 16, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 20, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 8, 2010
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 10, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 8, 2008
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 30, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 20, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 20, 2005
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 28, 1993
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed - Elevator elevatorrequired
(07) car door safety edge
Aug 8, 1989
Dob violation - resolved - Elevator elevatorrequired
(06) gate swtich, front gate
Aug 8, 1989
Dob violation - resolved - Elevator elevatorrequired
(15)secure exit cover from top of cover (33)provide dust cover 3rd floor (35)cover for interlock also at 3rd floor (51)provide aproved type communications all system as per code, in elevator
Jan 18, 1989
Dob violation - resolved
ECB violations · 100
- Class - 2
Reissue: 35691786y date of issue: 04/14/2025. failure to maintain building in code-compliant manner. at the time of inspection observed and noted at sub-cellar level water leaking from swimming pool above appro
Apr 22, 2026 · Penalty $3,125
Active - Class - 2
28-301.1. reissue: 35691783z date of issue: 04/14/2025. failure to provide ventilation to gas meter room per p115.6.(1968 code) fgc appendix(e4) 2014 code at the time of inspection observed and noted at cellar
Apr 22, 2026 · Penalty $3,125
Active - Class - 2
Exit door not self-closing properly. at the time of inspection observed and not at 3r door exit-9, 6, 1 all places one exit door and 2nd floor, exit-6 one exit door stairway "a" 2 exit doors, exit-7 one exit do
Apr 22, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. at the time of inspection observed and noted at stair way-8 between 1st and 2nd floorstair way at landing area at stair partition 4 panel missing at stair
Apr 22, 2026 · Penalty $1,250
Active - Class - 2
Reissue #35402456h. failure to maintain building wall(s) or appurtenances. noted at scattered locations of masonry facade vertical cracks inbrick and decorative stone. at roof level cracks in chimney and in bul
Apr 14, 2025 · Penalty $6,250
Resolve - Class - 2
Reissue #35677155r. failure to maintain building in code-compliant manner. noted at stair 3 and 4 bulkhead, spalling/missing plaster and cement finish on interior walls and ceilings. remedy: repair and/or repla
Apr 14, 2025 · Penalty $1,250
Resolve - Class - 2
28-301.1. reissue #35677157k. failure to provide ventilation to gas meter room per p115.6(1968 code), fgc appendix e(e4)(2014 code). noted at cellar gas meter room, no natural or mechanical fresh air ventilatio
Apr 14, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. noted at sub-cellar level, water leaking from swimming pool above. approx 1" of standing water at crawl space around the pool. remedy: repair and/or replac
Apr 14, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at 3 floor em. lights in library, stair d, 2fl. by room 236a auditorium
Apr 25, 2024 · Penalty $625
Resolve - Class - 2
27-misc. 28-misc, rc-misc. miscellaneous violations. reissue #35650872j. failure to provide natural or mechanical ventilation to gas meter room per p115.6(1968 code) fgc appendix e4(code 2014z0 at cellar ventil
Apr 25, 2024 · Penalty $3,125
Active
Show 40 more ↓
- Class - 2
Failure to maintain building in code-compliant manner. at bulkhead at stair 3 and 4 spalling concrete in auditorium ceiling leak water and at exit 15 railing is missing. remedy: repair and/or replace.
Apr 25, 2024 · Penalty $625
Resolve - Class - 2
Reissue#35650873l:exit door not self-closing at multiple level at various classrooms not close proerly does to defective hardware inches of door closer,missing or loose hinge and defective door check.rem:repair
May 26, 2023 · Penalty $1,562
Resolve - Class - 2
28-301.1 reissue#35650872j failure to provide natural or mechanical ventilation to gas meter room per p115.6(1968 code)fgc appendix e4 (2014code)at cellar gas meter room missing fresh an ventilations.rem:comply
May 26, 2023 · Penalty $3,125
Active - Class - 2
Exit door not self-closing.noted:observed at various locations each floor entire building numerous (fpsc) classroom doors not closing properly due to defective and/or missing door closers hardware.aprox 30 door
Apr 22, 2022 · Penalty $625
Resolve - Class - 2
28-301.1 failure to maintain building in code compliant manner.noted:observed at cellar electrical meter room has excessive amount of storage creating fire hazard.remedy:repair and/or replace,maintain electrica
Apr 22, 2022 · Penalty $625
Resolve - Class - 2
28-301.1 re-issued #5555759m failure to provide ventilation to gas meter room per p115.6(1968 code)fgc appendix e(e4)(2014 code)noted:observed at cellar both gas meter rooms missing fresh air ventilation.remedy
Apr 22, 2022 · Penalty $3,125
Active - Class - 1
3301.2 failure to safeguard all persons and property affected by construction operations.observed workers working on pipe scaffold along exp1 and 2 second deck from the roof without adequate illumination.observ
Sep 16, 2021 · Penalty $2,530
Resolve - Class - 2
Bc3307.6.59 inspection following an adjustment or repair.at time of re-inspection for complaint #54848277 and #4848058. observed vertical member for sidewalk shed had been removed from rain garden exp #1 to pre
Jun 19, 2021
Resolve - Class - 2
Bc 3307.10 failure to maintain sidewalk shed is obstructin construction of rain gurdens.note:at time of inspection observed sidewalk shed installed on pedestrian walkway at exp #4 101 street side not maintained
Jun 11, 2021
Resolve - Class - 2
3307.2 failure to provide dot permit as required.note:at time of inspection observed active job site.job site using occupancy (occupy) walkway entering the vehicle haney truck to the job site. upon request for
Jun 11, 2021
Resolve - Class - 1
Failure to provide occupancy contrary to that allowed by certificate of occupany or building dept record.note:at time of inspection observed active job site.exp$4 101 street side using construction materials st
Jun 11, 2021 · Penalty $2,500
Resolve - Class - 1
The only elevator in building(or section of building) out of service. upon inspection, the device is found to be out-of-service creating a hazardous condition as per 1rcny 11-02. remedy:restore to service immed
May 20, 2021 · Penalty $1,250
Active - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a
May 20, 2021 · Penalty $1,250
Resolve - Class - 2
Reissue: 35402459n failure to provide ventilation in gas meter room,per: 115.6(1968 code)fgc appendix e(e4)no fresh air. remedy: comply withcode.
Mar 23, 2021 · Penalty $3,125
Active - Class - 1
Upon inspection device was found out of service. restored to service immediately and contact nycdob at [email protected] for a complete inspection.
Sep 21, 2020 · Penalty $1,250
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor
Sep 21, 2020 · Penalty $1,250
Resolve - Class - 1
Upon inspection device was found out of service. restored to service immediately and contact nycdob at [email protected] for a complete inspection.
Sep 21, 2020 · Penalty $1,250
Active - Class - 1
Upon inspection device was found to be out of service. restore to service immediately and contact nycdob at [email protected] for a complete inspection.
Sep 21, 2020 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner no fire stopping stopping per bc 712.3 ;27-345 noted observed at cellars gas meter area above water meter (corner of fan room) have pipe penetrating through
Apr 29, 2020 · Penalty $1,250
Resolve - Class - 2
Reissue#35402461m failure to maintain buidlingin code compliant manner noted observed at second flor class room doors rm 207,290,240a are not closing properly due to defective hardware repair and or replace
Apr 29, 2020 · Penalty $1,562
Resolve - Class - 2
Re-issue #35402460k exit door not self closing noted observed exit doors at 3rd floor exit 4d 2nd floor exit 4,8h 10j and 6f 1st floor exit 6f cafeteria exit 4d exit 2 doors do not close properly due to execess
Apr 29, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue #35402459n miscellaneous violations failure to provide ventilation to gas meter room per p115.6(1968 code) f& c appendix e(e4) 2014 code) noted observed no fresh air ventilation at gas meter roomsby wat
Apr 29, 2020 · Penalty $3,125
Active - Class - 2
Reissue #35402455x failure to maintain building in code compliant manner:(interior) noted observed at pool area vertical cracks on bottom of masonry columsn horizontal cracks on cmu wall above pool psalling and
Apr 29, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination for exits ,exit discharges and publci corridors per bc 1006.1;27-381 noted observed existing emergency lighst at 2nd floor by door 2-134 ,11k,5
Apr 29, 2020 · Penalty $625
Resolve - Class - 2
Machine is leaking. seal machine. machine bearing worn. replace. generator bearing worn. replace. repair light in motor room. remove non elevator equipment from motor room. provide outside lighting to motor roo
Feb 14, 2020 · Penalty $625
Resolve - Class - 2
Emergency sign at elevator call stations missing. noted, emergency signs at elevator call stations missina at all floors. remedy: installsigns.
Apr 15, 2019
Resolve - Class - 2
28-301-1 failure to provide ventilation gas meter room per p 115.6 (1968 code),fgc appendix e (e4)(2014 code)noted:no fresh air ventillation provided to gas meter room . remedy: comploy with notice of violat
Apr 15, 2019
Active - Class - 2
Exit door not self closing. noted: the exit doors not self-closing: at 3rd floor exit 4 (d) 2nd floor missing vision panel at exit 4,exit 8 (h), exit 10(j) 1st floor exit 6(f), cafeteria exit 4 (d). remedy:
Apr 15, 2019
Resolve - Class - 2
Reissue # 35311790j. failure to maintain building wall(s) or appurtenaces. noted: coping area throughout coping stones,decorative cornice are cracked multiple locations. remedy: make necessary repairs.
Apr 15, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted: at secondfloor classroom 207, 209, 240a doors do not close properly due to defective hardware. remedy: repair/replace
Apr 15, 2019
Resolve - Class - 2
Reissue # 35311791l. failure to maintain wall (s) or appurtenances. noted: at pool area, far right side cmu column cracked. remedy: make necessary repairs.
Apr 15, 2019
Resolve - Class - 2
Reissue # 35311789m. failed to maintain building in code compliant manner. noted: pool area the beams above at ceiling area are cracking multiple places. remedy: make necessary repairs.
Apr 15, 2019
Resolve - Class - 2
B254,50a. found following violating condition for boiler #925603 50a-missing ladder and platform. rmdy: resolve violating condition and submit affidavit
Oct 5, 2018
Active - Class - 2
B254,50a, found following violating conditon for boiler #925602: 50-missing ladder and platform rmdy: resolve violating conditions and submit a affidavit.
Oct 5, 2018
Active - Class - 2
B254, 50a. found following violation in boiler #925601. 50a-missing ladder and platform. rmdy: resolve violations condition and submit affidavit.
Oct 5, 2018
Active - Class - 2
B254,50a. found following violating condition for boiler #925504 50a-missing ladder and platform. rmdy: resolve violating conditions and submit affidavit.
Oct 5, 2018
Active - Class - 2
Reissue #35094303p failure to maintain bldg in code-compliant manner note:@(swimming)pool area the beams above @ceiling area are cracked in multiple places.rem:repair &/or eplace.
Feb 13, 2018
Resolve - Class - 2
Reissue #35029013x failure to maintain bldg wall(s) or appurtences.note:@pool area the (collum)(cmu) @far right side is cracked.rem:maintain(collum) @pool area.
Feb 13, 2018
Resolve - Class - 2
Reissue #34918157z failure to maintain bldg wall(s) failure to maintain bldg wall(s) or appurtenances.note:@coping area throughout,coping stones,decorative cornice are cracked @multiple locn loose & missing.rem
Feb 13, 2018
Resolve - Class - 1
5m7,41b7,56y2. (5m)missing zone restrictor,must provide. (41b)motor room door must be self locking, must provide. (56y)motor leaking oil, clean & seal. (5m7 is cease use item).
Jul 11, 2017
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1929
- Floors
- 4
- Residential units
- —
- Building area
- 552,216 ft²
- Lot area
- 410,000 ft²
- Zoning
- R4
- Community board
- 410
- Council district
- 28
- Block / lot
- 9540 / 2
- Assessed value
- $30,343,950
- Landmark / historic district
- No
Questions about 101-01 Rockaway Boulevard
Who owns 101-01 Rockaway Boulevard?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 101-01 Rockaway Boulevard have violations?
NYC HPD has no housing violations on record for this property.
Is 101-01 Rockaway Boulevard rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 101-01 Rockaway Boulevard built?
City records list 1929 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.