roofy

131-10 97 Avenue

Queens, NY 11419BBL 4-09477-0001Map

Owner of record: NYC Department Of Education

131-10 97 Avenue is a school building built in 1939 in Queens, 11419. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
11
ECB violations
68
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 11

  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
Show 1 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations · 68

  • Class - 2

    Failure to maintain building in code-compliant manner.noted:classroom doors do not self-close properly at 3rd-332,327,325,323,319,317,315,313,309.2nd flr-213,215,217,219,221,223,225,229,232.rem:repair and/or re

    Mar 4, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner:no firestopping per bc 712.3;27-345.noted:in electric meter room above the door there is a mesh wire opening & firestopping cannot be applied.rem:provide/ma

    Mar 4, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35678941z failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted emergency lights not working when tested at 3rd fl

    Mar 20, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Found hb smith 28a 5 gas boiler, gas vent needs to be hard piped correct violating condition and submit a certificate of correction

    Jul 22, 2024 · Penalty $625

    Active
  • Class - 2

    Found hb smith 28a 5 gas boiler, gas vent needs to be hard piped correct violating condition and submit a certificate of correction

    Jul 22, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc1006.1; 27-381. noted emergency lights not operative when tested. at 3rd fl. stair f, at

    Apr 11, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits,exit discharges and public corridors per bc 1006.1:27-381 noted observed emegrnecy exit lights near room 328 an and near exit 6f not

    Feb 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Hb smith boiler mdl# 28a-5. pilot tubing before pilot valve must be hard piped. correct violating conditions and submit a certificate of correction.

    Aug 7, 2019

    Active
  • Class - 2

    Hb smith boiler mdl# 28a-5. control corroded. pilot tubing before pilot valve must be hard piped. correct violating conditions and submit a certificate of correction.

    Aug 7, 2019

    Active
  • Class - 2

    Exit door not self closing. noted: @ 1st fl gym self closer/door checkin disrepair/non operational. remedy: repair/replace door.

    Mar 22, 2019

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ 1st fl cafeteria exit 5e door in disrepair racked. remedy: repair &/or replace.

    Mar 22, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. illumination for exits, exit discharges & public corridor bc 1006.1; 27-381. noted: @ 1stfl gym & auditorium emergency lights are non operational throughout in

    Mar 22, 2019

    Resolve
  • Class - 2

    28.301.1. reissue ecb #35317325l. failure to provide ventilation to gas meter room for p 115.6 (1968 code) f6c appendix 'e' (eh) 2014 code noted: @ bsmt gas meter room with no venting system installed. remedy:

    Mar 22, 2019

    Resolve
  • Class - 2

    Sec. 28-301.1 reissue#35228856x failure to provide ventilation to gas meter room per p 115.6(1968 code). fgc appendix'e'(eh)2014 code. noted: at gas room missing venting system in gas meter room,need to provide

    Feb 13, 2018

    Resolve
  • Class - 2

    Reissue#35228857h exit door not self closing. noted: at both inner exit door at expit#4 are racked not properly closing & requires extra force to open,need to be repair replace. remedy: comply w/code repair/or

    Feb 13, 2018

    Resolve
  • Class - 2

    Reissue#35194931y exit door not self closing. noted: both inner exit door at exit#4 are racked(cnot)properly closing & requires extra force to open &/or close doors also at exit#9 have the same condition,make

    Feb 27, 2017

    Resolve
  • Class - 2

    Sec. 28-301.1 reissue#35194934j failure to provide ventilation to gas meter room per p115.6 l1968 codes. fcc appendix e(e4)(2014 code)noted: at gas room missing venting system,provide venting system in gas room

    Feb 27, 2017

    Resolve
  • Class - 2

    Failure to maintain building code-compliant manner.noted:all emergencylighting packages in cafeteria are non operational.

    Jun 1, 2016

    Resolve
  • Class - 2

    Failure to maintain building code-compliant manner.noted: in boiler room foundation wall missing sections of concrete exposing rebars. rmdy: repair defective wall.

    Jun 1, 2016

    Resolve
  • Class - 2

    27-766 fresh air in gas meter room rs16/p115.4 and 6/tppn1 of 1994.noted: missing venting system in gas meter room. rmdy: provide venting system.

    Jun 1, 2016

    Resolve
  • Class - 2

    Exit door not self-closing. noted: both inner and outer exit doors located at exit #2 are racked (not properly closing and requires extra force to open/and/or close doors. exit door at exit9 also has similar

    Jun 1, 2016

    Resolve
  • Class - 2

    Exit door not self-closing. note:doors racked @stair f, 1st & 2nd floors & door @exit 6 sticks. rem:repair or replace doors.

    Jun 13, 2013

    Resolve
  • Class - 2

    Wooden ramp for portable unit t-1 has rotting wood & ramp sagging wooden deals a stair for portable t-3 has rotting wood.rem:repair or replace deck & ramp.

    May 2, 2012

    Resolve
  • Class - 2

    Sec. 27-371(b). plexi vision panels installed on doors at various locations throughout bldg. remedy: provide required glass panels.

    May 2, 2012

    Resolve
  • Class - 3

    Reissue 34791882x. area way grates pm south & west sides of bldg are corroded and pitting. remedy: repair/replace grates.

    May 2, 2012

    Resolve
  • Class - 2

    Doors not self closing at 2nd stairway f & 3fl stwy c fire proof self closing doors do not self close rem: replace door checks to make doors properly self close

    Jun 17, 2011

    Resolve
  • Class - 2

    Reissue : 34791887p interior exit doors at stair "d" & "e" do not close properly noted: door closer is defective by the 3rd fl level. remedy: repair and / or replace exit doors

    Apr 9, 2010

    Resolve
  • Class - 2

    Reissue : 34791889z interior space at the cellar has erected partitionwalls creating 3 rooms next to the electrical room w/o any permits. remedy: obtain permit/s or restore premises to prior legal condition

    Apr 9, 2010

    Resolve
  • Class - 2

    Reissue : 34791888r the electrical room is lacking fire stopping at the cellar level. remedy: provide / maintain fire-stopping

    Apr 9, 2010

    Resolve
  • Class - 2

    Reissue 34482166x failure to provide protection of structural members in boiler room on 1st fl lvl in the mini school noted no fire proofingapplied rem; provide maintain required fire proofing as required

    Feb 4, 2010

    Resolve
  • Class - 3

    Overhead stop room t3 bathroom broken - bar hanging from door slighty.remedy:repair / replace hardware as needed.

    Jun 15, 2009

    Resolve
  • Class - 3

    Room 135 - bowed, buckled ceiling tile right rear of room. remedy:replace ceiling tile.

    Jun 15, 2009

    Resolve
  • Class - 2

    Mechanical room used for storage of maintenance equipment.remedy:remove equipment - keep room clear.

    Jun 15, 2009

    Resolve
  • Class - 2

    Work no permit. at cellar level outside electric room - erected 8' higg drywall partitions w/entry doors,lighting & convenience outlets to create 3 rooms.rooms presently vacant work 100% complete. remedy:obtai

    Jun 15, 2009

    Resolve
  • Class - 2

    At cellar electric room - wire(lath ) transom above door not fire stopped. remedy:fire stop electric room transom.

    Jun 15, 2009

    Resolve
  • Class - 2

    On third fl stair d & e doors racked, will not properly close. remedy:repair doors.

    Jun 15, 2009

    Resolve
  • Class - 2

    Sec.bc1017.1 & 27-369. outside room 201 required corridor width reduced by fish tank, book case & chairs in hallway.remedy:remove obstruction.

    Jun 15, 2009

    Resolve
  • Class - 2

    Reissue 34711909y. vertical wall crack app 20' long in library (225) across window tops. also spalling plastic corridor outside room 323. remedy:repair walls & ceilings.

    Jun 15, 2009

    Resolve
  • Class - 2

    Installed door closers on existing auditorium doors w/double swing hinges and exit lights on both sides of wall reducing egress by 50% in either direction. remedy: remove closers - maintain clear egress for

    Jun 15, 2009

    Resolve
  • Class - 3

    Perimeter fence corner 97 ave & 132 st leaning,one section bowed - detached on bottom right from post. remedy:repair - replace fence.

    Jun 15, 2009

    Resolve
  • Class - 3

    Exterior windows grates rusted pitted perimeter of school,especially on 97 ave & 131 st sides of school. remedy:maintain / repair window grates.

    Jun 15, 2009

    Resolve
  • Class - 2

    Exterior wall has 20' long vertical crack at rear yard adjacent to transportables @ top corner. remedy:repair crack.

    Oct 21, 2008

    Resolve
  • Class - 2

    Large stress cracks in room 225(library) running across rear wall through lintels. remedy:repair walls.

    Oct 21, 2008

    Resolve
  • Class - 2

    Reissue 34607662p. corridor with decreased by obstructions noted on 3 floor in front of room 329 folding tables, chairs, chalkboard.remedy: remove obstructions.

    Oct 21, 2008

    Resolve
  • Non-hazardous

    Re-issue #34505141z.1fl playroom place of assembly (319 capacity) northwest corner exit doors swing against the flow of egress onto main entrance corridor.remedy:repair/replace door to swing in proper direction

    Jun 21, 2007

    Resolve
  • Non-hazardous

    3fl exit corridor required width decreased by mini class room set up w/desk,chairs & stored items-obstructions outside classroom 329.remedy:remove obstructions maintain exit corridors free of obstructions.

    Jun 21, 2007

    Resolve
  • Non-hazardous

    3fl exit 6, exit sign lamp defective-not light.remedy:repair/replace sign.

    Jun 21, 2007

    Resolve
  • Non-hazardous

    Re-issue #34505144y boiler room ventilation stacks 2 missing hood covers allowing water entry into boiler room.remedy:provide/install missing hood covers.

    Jun 21, 2007

    Resolve
  • Non-hazardous

    Reissue 34482167h boiler room @ 1st flr mini school has missing hood covers on vent stacks causing rain water to enter.remedy:install the missing covers

    Apr 4, 2006

    Resolve
  • Non-hazardous

    Exit passageway or corridor required width decreased by obstructions. observed a black board desks & chairs within corridor outside room# 309 & blocking exit#5 @ the 3rd flr.remedy:remove obstructions

    Apr 4, 2006

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1939
Floors
3
Residential units
—
Building area
53,746 ft²
Lot area
60,388 ft²
Zoning
R4A
Community board
409
Council district
29
Block / lot
9477 / 1
Assessed value
$6,343,200
Landmark / historic district
No

Questions about 131-10 97 Avenue

Who owns 131-10 97 Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 131-10 97 Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 131-10 97 Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 131-10 97 Avenue built?

City records list 1939 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.