252-72 Little Neck Parkway

Queens, NY 11426BBL 4-08401-0375Map

Owner of record: NYC Department Of Parks And Recreation

252-72 Little Neck Parkway is a school building built in 1958 in Queens, 11426. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
32
ECB violations
76
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 32

  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 27, 2017

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 25, 2016

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 6, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 26, 2012

    Dob violation - resolved
Show 22 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 5, 2010

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 2, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 26, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 26, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 23, 2006

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 13, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 1, 2004

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 28, 1993

    Dob violation - dismissed
  • Elevator elevatorrequired

    (15)secure and repair 1 fl outside door hinge (28)repair guide shoes and restore sw 160 to full service so a complete inspection of same can be made by a inspection from this dept (03)repair hole in cab waqll rusted out (15)adjust bsmt hoistway door (boiler room)

    Sep 26, 1989

    Dob violation - resolved

ECB violations · 76

  • Class - 2

    Failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. noted: upon inspection broken lense on an emergency light

    Feb 17, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. no fire stopping perr bc 712.3; 27-345. noted upon inspection fire stopping missing in various locations throughout basement boiler room. remedy: provide/m

    Feb 17, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: upon inspection fire rated smoke doors not self-closing on classrooms 101, 103, 113, 122, 137, 134, 201, 203, 205, 236, 237, 234, 235, 323, 322a, 32

    Feb 17, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner:use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:at bulkhead stair d,f,and g door handles are not functioning properly.rem:provide leg

    Feb 24, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted at 3 floorroom 317,(smoke)stair e,2 fl 203,218,1 floor stage left doors are not closing properly.rem:repair and/or replace.

    Feb 24, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    28-301.1. unlawful display or artwork in corridors greater than 20% per fdny 2008 code; fc803.3.2. noted: artwoork displayed in corridors throughout the building in greater them 20% allowed per fdny 2008 code.

    Mar 19, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35644483p(3/28/2022)failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridor per bc 1006.1,27-381 c 1st floor auditorium in basement room c-26 1 e

    Feb 27, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35546596m failure to maintain building in code compliant manner:illumination for exits,exit discharges and public corridor per bc 1006.1,27-381.noted:at 1st floor auditorium(near main entrance)exit sig

    Mar 28, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35526732j exit door not self-closing noted:at 2nd floor stairg(exit door)and at 1st floor gym(near reception)exit door bath are notself closing properly due to defective hardware.rem:repair/replace doo

    Mar 28, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35490809k date of issue 8-28-2020 exit door not self closing properly. 2nd fl at stair'a'at 1st fl gym(near reception)one exit(each)& main entrance 2 doors(one left side one right side)at 1st fl auditor

    Feb 16, 2021 · Penalty $1,562

    Resolve
Show 40 more ↓
  • Class - 2

    Reisse#35475988x date of issue#35475988x failure to maintain bldg in code compliant manner. at main entrance 2 doors do not open properly due to defective hardware. remedy: repair or replace doors.

    Feb 16, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35490808p date of issue 8-28-2020 failure to maintain bldg in code compliant manner. illumination for exits,exit discharges & publiccorridors per bc 1006.1;27-381. in basement near room no c-26 1 exit

    Feb 16, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner;illumination forexits,exit discharges and public corridors per bc 1006.1;27-381 basement near room no c-26 1 exit sign existing exit sign is not operational

    Aug 28, 2020 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing 2nd floor at stair "g" at 1st floor gym(near reciption)one exit(each) and main entrance two doors(one left & one right)at total 4 doors.rem:repair/replace door.

    Aug 28, 2020 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing. noted: at 1st fl at exit 2 at stair b,bothexit doors require excessive force to open due to rusted frame. remedyrepair/replace door.

    Feb 11, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35381570l failure to maintain bldg walls or appurtenances. noted: at boiler room,the foundation wall has become porous allowing the rain water to enter into the cellar. at the time of inspection,1"puddl

    Feb 11, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Sec. 28-301.1 unlawful display of artwork in corridors greater than 20% per fdny 2018 code;fc803.3.2. noted: artwork displaced in corridors throughout the bldg is greater than 20% allowed. remedy: comply w/noti

    Feb 11, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35381571n failure to maintain bldg in code compliant manner. noted: at main entrance 2 doors do not operate properly due to deffective hardware. remedy: repair or replace doors.

    Feb 11, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    B254,21a,32a,48b,50a,50b found fitzgibbons boiler mdl dm182 blr#41802-02 with the following violations: 21a,32a,48b,50a: missing boiler in sulation and 50b-missing ladder and platform. rmdy: resolve violating

    Feb 27, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at main entrance 2 doors do not work properly due to defective hardware.repair and/or replace

    Feb 26, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.use of probihited door and/or hardware per bc 1008.1.8;27-37(j) noted:kickdown door holders are installed at the doors throughout the building.remove illega

    Feb 26, 2019

    Resolve
  • Class - 2

    28-301.1;unlawful display of artwork in corridors greater than 20% per fdny 2008 code :fc 803.3.2.noted:artwork displayed in corridors throughout the builing is greater than 20% allowed..comply with notice of v

    Feb 26, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code complaint manner.noted:at 1st fl at exit c illegal storage of chairs boxes and supplies in front of the exit door.comply with notice of violation

    Feb 26, 2019

    Resolve
  • Class - 2

    Reissue#35311201m.failure to maintain building wall(s) or appurtencnes.noted:at boiler room the foundation wall has become porous allowing the water to entry in to the cellar.maintain exterior wall.

    Feb 26, 2019

    Resolve
  • Class - 2

    Reissure#35311202y.failure to maintain building in code compliant manner.provide required corridor width per bc 1016.2;27-369.noted:at cellar level 50% of the corridor obstructed by charis tables,electronic car

    Feb 26, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.no fire stopping per bc 712.3;27-345.noted:@electrical room 3 condition 4" each w/no fire stopping.rem:provide/maintain fire stopping.

    Feb 14, 2018

    Resolve
  • Class - 2

    Reissue #35234605m failure to maintain bldg wall(s) or appurtenances.noted:@boiler rm the foundation wall has become (porous) allowing the rain water to enter into the cellar.rem:maintain exterior wall.

    Feb 14, 2018

    Resolve
  • Class - 2

    Reissue #35234607x failure to maintain bldg in code-compliant manner.noted:smoke door @stair f,one door @exit 8 & one door @vestibule @main entrance do not operate properly due to defective door closers.rem:rep

    Feb 14, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.provide required corridor width per bc 1016.2;27-369.noted:@cellar level 50% of the corridor obstructed by (chours),tab;es,electronic,card boards displays etc.r

    Feb 14, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: smoke door at stair f and one door at exit 8 do not operate properly due to defective door closers. rmdy: repair/replc door.

    Mar 7, 2017

    Resolve
  • Class - 2

    Reissue #35177501j failure to maintain building in code compliant manner. no fire stopping per bc 712.3; 27-345. noted: at cellar electrical room no fire stopping with 5 holes 2"-4". rmdy: provide/maintain

    Mar 7, 2017

    Resolve
  • Class - 2

    Reissue #35177500h failure to maintain building walls or appurtenances.noted: at boiler room, the foundation wall has become porous allowing the rain water to enter. rmdy: maintain exterior wall.

    Mar 7, 2017

    Resolve
  • Class - 2

    Unlawful display of artwork in corridors greater than 20% per fdny 2008 code; rc 803.3.2. noted: artwork displayed in corridor throughout the bldg more than 20% allowed. rmdy: comply w/nov.

    Mar 7, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. failure to provide wired glass vision panels per 27-371(b) noted: following doors do nto have 1/4"wired glass vision panels. at 3rd floor room 317, at second

    Mar 28, 2016

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner, no fire stopping per bc 712.3; 27-345. noted: at cellar at electrical room no fire stopping with 5 holes 2"-4". rmdy: provide/maintain fire stopping.

    Mar 28, 2016

    Resolve
  • Class - 2

    Reissue #35129233x failure to maintain building wall(s) or appurtenances. noted: at cellar boiler room, the foundation wall has become porous allowing rain water to enter. rmdy: main exterior wall (bldg)

    Mar 28, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg exterior walls. noted: at cellar boiler room,the foundation wall has become porous allowing rain water to enter. remedy: comply w/code.

    Jun 5, 2015

    Resolve
  • Class - 2

    Sec. bcq102 failure to provide approved sprinkler main value per bcq102 section 8.15. noted: at cellar,sprinkler main has installed gate value that is not a cork screw,outside indicater or os & y,can not determ

    Jun 5, 2015

    Resolve
  • Class - 2

    Reissue #35094742j failure to maintain bldg code compliant. noted: at cellar boiler room,broken-in operative fresh air dampers. remedy: comply w/code,repair or replace.

    Jun 5, 2015

    Resolve
  • Class - 2

    Failure to maintain corridors free of combustible storage. noted: at 2nd & 3rd fl,combustible boxes stacked w/carts,tables & chairs. remedy:comply w/code,remove all items.

    Jun 5, 2015

    Resolve
  • Class - 2

    Reissue #35027740n. fail to maintain fresh air dampers in boiler room not auto-opeining/not operating. remedy: maintain & repair defect.

    Jul 14, 2014

    Resolve
  • Class - 2

    Reissue 34941726p water penetrating into room 236 at windows causing plaster damage. rmdy: make necessary repairs.

    Aug 5, 2013

    Resolve
  • Class - 2

    Reissue 34941727r fire dampers at boiler room not operational. rmdy: make necessary repairs.

    Aug 5, 2013

    Resolve
  • Class - 2

    Exit vestibule at stair c obstructed by storage of boxes of light fixtures celalr corridor obstructed by storage of file cabinet tablesdesk and boxes, stair e at cellar obstructed by storage of boxes of

    Aug 5, 2013

    Resolve
  • Class - 2

    27-765 reissue 349417282. rooms 228,228a,228b,223,223a,221a being occupied by teachers and students w/o ventilation. rmdy: provide ventilation or discontinue use.

    Aug 5, 2013

    Resolve
  • Class - 2

    Exit door at stair g is racked. rmdy: repair or replace door.

    Aug 5, 2013

    Resolve
  • Class - 2

    Water penetrating through foundation wall into electrical room leavingstanding water on floor. rmdy: make necessary repairs.

    Aug 5, 2013

    Resolve
  • Class - 3

    Water penetration into 2 flr corridor & room 236.water enetrating bldg notible damage to ceiling.rem:seal penetration.

    May 25, 2012

    Resolve
  • Class - 2

    Defective fire dampers in boiler room not in operation.rem:repair dampers.

    May 25, 2012

    Resolve
  • Class - 2

    27-765)no ventilation in rooms 228,228a,228b,223,223a,221a.no ventilation in occupied rooms as per code.noted:teacher & students occupying rooms.rem:provide ventilation or discontinue use!

    May 25, 2012

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1958
Floors
3
Residential units
—
Building area
161,500 ft²
Lot area
150,000 ft²
Zoning
R3-2
Community board
413
Council district
23
Block / lot
8401 / 375
Assessed value
$16,069,500
Landmark / historic district
No

Questions about 252-72 Little Neck Parkway

Who owns 252-72 Little Neck Parkway?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.

Does 252-72 Little Neck Parkway have violations?

NYC HPD has no housing violations on record for this property.

Is 252-72 Little Neck Parkway rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 252-72 Little Neck Parkway built?

City records list 1958 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.