75-38 Parsons Boulevard

Queens, NY 11366BBL 4-06809-0056Map

Owner of record: The Solomon Schechter School Of Queens

75-38 Parsons Boulevard is a school building built in 1972 in Queens, 11366. The owner of record is The Solomon Schechter School Of Queens. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
19
ECB violations
55
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 19

  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2012 inspection report

    May 15, 2014

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2012 inspection report

    May 15, 2014

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
Show 9 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 7, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 7, 1994

    Dob violation - dismissed
  • Public assembly none

    B.k

    Aug 12, 1980

    Dob violation - dismissed

ECB violations · 55

  • Class - 2

    Reissue:35719677r date of issue:05.08.2025 failure to maintain building in code compliant manner.at the time of inspection observed and noted at kitchen stove no fire suppression system ansul in place.rem:repai

    Apr 28, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35719676 date of issue:05.08.2025 failure to maintain buildingin code compliant manner.at the time of inspection observed and noted at 2nd floor hallway ceiling by room 205,221,and 1st floor gym ceiling

    Apr 28, 2026 · Penalty $3,125

    Active
  • Class - 2

    Exit door not self closing properly at the time of inspection when tested.at the time of inspection observed and noted at basement level main entrance two part doors,1st floor stairway a main entrance 2 exit do

    Apr 28, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted at kitchenstove no fire suppression system ansul in place.rem:fire suppression system.

    May 8, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35682707m failure to maintain building in code-compliant manner.illumination for exit,exit discharges and public corridors per bc 1006.1;27-381.noted at gym and cafeteria emergency lights not working pr

    May 8, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted at 2nd floor hallway ceiling by room 205,1st floor gym ceilings water penetration.rem:repair and/or replace.

    May 8, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.at rooms 207,219105 doors are not functioning properly.rem:repair and/or replace.

    May 13, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at thegym and cafeteria the emergency lighting is not work properly.rem:repa

    May 13, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue35473598l failure to maintain bldg in codecompliant manner:lack of emergency lighting for exit,exit discharges&public corridors per1006.1;27-592.repair &/or replace lighting.

    Mar 19, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain in codecompliant manner.fan not working in gym unit1&cr3 which are rm105,109,205,207 roof units not working.repair &/or replace.

    Mar 19, 2021 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Reissue#35454686h failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. note: at cellar level gym emergency exit lights not working.

    Apr 24, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. note: at roof levelroof leaks in various areas causing damage to ceiling below. remedy: repair & or replace.

    Apr 24, 2020 · Penalty $625

    Resolve
  • Class - 1

    Failure to maintain building in code compliant manner noted at the roof top at driveway side exp #2 2 inch at the time of my inspection photo taken make necessary repairs

    Mar 1, 2020

    Resolve
  • Class - 1

    Failure to maintain bldg in code compliant manner. noted: at the roof top at driveway side,exp#2 crushed stone,gravels are too close to the edge & are falling down in the driveway,observed at the time of inspec

    Dec 21, 2019 · Penalty $6,250

    Resolve
  • Class - 1

    Failure to maintain building in code compliant manner noted at the roof top at parosn blvd side gravels are too high to the edge in danger of falling down to the pedestrians and students atciev area photo taken

    Nov 12, 2019 · Penalty $1,280

    Resolve
  • Class - 2

    Reissue#35321935k failure to maintain bldg in code compliant manner. no fire stopping per bc1006.1;27-542 in electrical meter room & mechanical room,fire stop missing or inadequate. remedy: provide/maintain fir

    Oct 7, 2019 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances.note:observed water damage at ceiling in rooms 307,317 due to roof in disrepair.at roof level observed holes and cracks in roof membrane at edges and at var

    Oct 7, 2019 · Penalty $620

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. note: at gymnasium emergency exit lighting was not functional when tested.

    Oct 7, 2019 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue# 35228789p date of issue 3/2/2017, failure to maintain bldg in code compliant manner @ time of insp exit door 3 @ staircase b on 1st flr. the glass on each was replaced w/ masonite & plastic vision pane

    Mar 2, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner no fire stopping per bc 1006.1, 27-542 in electrical room 3 places & mechanical room flue place, fire stopping missing. rem: provide/maintain fire stopping.

    Mar 2, 2018

    Resolve
  • Class - 2

    Exit door not self closing. @ 1st flr near stair 'b' outside 2 doors. in zim area door# 024, 2 doors & in zim area outside exit 1 door not self closing @ time of insp. rem: repair/replace door.

    Mar 2, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: mechanical room (014) has a crack on the wall, cmu wall, its a vertical open crack. rem: repair &/or replace.

    Mar 2, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ time of insp exits doors 3 @ staircase b on the 1st flr, the glass on each was replaced w/ masonite & plastic vision pannel. also in the middle corrid

    Mar 2, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: 2nd flr stair b exit lights not working, also staircase b the lights are not working, the lights in the gym are not working,also room 15 the exit lights

    Mar 2, 2017

    Resolve
  • Class - 2

    @ stair 'a'from fls 1+2,missing one stair tred anti-slid convering and tred nosing in several locations.rem:maintain bldg

    Jan 28, 2015

    Resolve
  • Class - 2

    Defective emergency lighting throughout building. remedy: maintain lighting.

    Apr 17, 2014

    Resolve
  • Class - 3

    Re-issue # 35023730l. occupancy contrary to dept records. noted at side yard cars jumping curb & parking along side of building. remedy: discontinue illegal use.

    Apr 17, 2014

    Resolve
  • Class - 2

    Re-issue # 35023731n. illegal extension at front of stage basement level. remedy: restore to legal condition.

    Apr 17, 2014

    Resolve
  • Class - 2

    Illegal storage inside gas meter, electrical panel room. remedy: remove storage.

    Apr 17, 2014

    Resolve
  • Class - 2

    Reissue 34942524l illegal extension of stage at front in basement,multipurpose room. remedy: legalize/remove stage.

    Jul 10, 2013

    Resolve
  • Class - 2

    Failure to maintain bldg,noted at sideyard metal grating bowed,pullingaway from facade,also adjacent to grating concrete around drain missing causing trip hazard through passageway.rmdy: repair/replace affected

    Jul 10, 2013

    Resolve
  • Class - 3

    Reissue 34942522h occupancy contrary to dept records. noted at side yard cars jumping crosswalk to park,approx 7 cars at time of inspection. remedy: discontinue use.

    Jul 10, 2013

    Resolve
  • Class - 2

    School staff are using their vehicles entering/exit a non-parking lot by using a pedestrian crosswalk as a means of egress on parsons blvd. remedy: discontinue use of a pedestrian crosswalk & parking lot.

    May 3, 2012

    Resolve
  • Class - 2

    Exit door on the 2nd flr are being held open by door stoppers. remedy:remove doorr stoppers.

    May 3, 2012

    Resolve
  • Class - 2

    Work w/o a permit. noted: auditorium stage in the basement level has been enlarged approx 5' extension. w/o proper permit. remedy: obtain permit or restore premises to prior legal condition.

    May 3, 2012

    Resolve
  • Class - 2

    Reissue: 34809836h the gas meter room is lacking fresh air ventilationat the basement level. remedy: provide/maintain fresh air ventilation.

    Apr 6, 2011

    Resolve
  • Class - 2

    Exterior concrete floor around the drain is sinking approx 6" inches causing a tripping hazard located at the rear of school by gym exit. remedy: repair and/or replace concrete.

    Apr 6, 2011

    Resolve
  • Class - 2

    Exterior window air conditions does not have any extra support located in rm 202 , 204 & 206 on the 2nd fl lvl rem: provide maintain air condition window support

    Jan 15, 2010

    Resolve
  • Class - 2

    Reissue 347609735j failure to provide fresh air ventilation in the gasmeter rm at cellar lvl rem: provide maintain fresh air ventilation in the gas meter rm

    Jan 15, 2010

    Resolve
  • Class - 3

    Failure to maintain bldg walls or appurt. noted: separation cracks w/mortar missing in brick facade. location: rear wall (ext) adjacent to gym rear exit door. remedy: maintain ext bldg wall.

    Jan 30, 2009

    Resolve
  • Class - 3

    Failure to maintain bldg in code compliant manner. noted: failure to provide fresh air vent in gas meter room. remedy: correct noted defect provide fresh air vent.

    Jan 30, 2009

    Resolve
  • Non-hazardous

    Operation of a pa without a current permit.(nb 792-71).location:basement room #015 arranged for occuapncy by approx 96 persons.(class room) remedy:obtaion pa permit.

    Apr 1, 2005

    Resolve
  • Non-hazardous

    Failure to maintain exterior builaing wall. defect spalling, loose mortar joints front facade and cracked bricks- north east corner.

    Mar 27, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building exterior wall defects are crack at exterior wall over main entry,at parsons blvd.remedy:make safe,do all repairs required obtain all permit and install required sidewalk shed.

    Jan 26, 2001

    Resolve
  • Non-hazardous

    Failure to maintain building interior;defect are cracked walls in rm 213,200,201 and gym.remedy:do all repairs.

    Jan 26, 2001

    Resolve
  • Non-hazardous

    Work without a permit: work noted: demolished 1 1/2 story frame building at front of lot(7) concrete block garage & 1 story shed at rear. remedy: obtain a permit

    Oct 1, 1999 · Penalty $2,500

    Active
  • Non-hazardous

    Work withou ta permit work noted a demolition of concrete block garge of lot demolition of conrete block garage and story framed shed at rear o fpremise remedy obtain all necessary permits and approvals for wok

    Aug 4, 1999 · Penalty $2,500

    Active
  • Non-hazardous

    Failure to maintain bldg. noted: some school windows inoperable. rawsewage back up during rainfall. emergency lighting inadequate. remedy:maintain bldg interior. remedy: maintain bldg interior.

    Mar 2, 1999

    Resolve
  • Non-hazardous

    Work without a permit work noted: demolished 11/2 story frame building at front of lot, (2) concrete block garage & 1 story frame shed at rear. remedy: obtain a permit.

    Dec 11, 1997 · Penalty $2,500

    Active
  • Hazardous

    Work without a permit. work noted: demolished 1 1/2 story building at front of property and a shed at rear of property. remedy:obtain approvals and permits.

    Oct 10, 1995 · Penalty $1,000

    Active

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1972
Floors
2
Residential units
—
Building area
43,952 ft²
Lot area
32,900 ft²
Zoning
R4
Community board
408
Council district
24
Block / lot
6809 / 56
Assessed value
$5,847,300
Landmark / historic district
No

Questions about 75-38 Parsons Boulevard

Who owns 75-38 Parsons Boulevard?

The owner of record in NYC Department of City Planning PLUTO data is The Solomon Schechter School Of Queens.

Does 75-38 Parsons Boulevard have violations?

NYC HPD has no housing violations on record for this property.

Is 75-38 Parsons Boulevard rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 75-38 Parsons Boulevard built?

City records list 1972 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.