221-21 Corbett Road
Queens, NY 11361BBL 4-06185-0001Map
Owner of record: The Gordovia Living Trust
221-21 Corbett Road is a school building built in 1981 in Queens, 11361. The owner of record is The Gordovia Living Trust. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 38
- ECB violations
- 73
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 38
- Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2013 inspection report
Mar 3, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2013 inspection report
Mar 3, 2015
Dob violation - dismissed
Show 28 more ↓
- Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2010 inspection report
Dec 13, 2011
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2010 inspection report
Dec 13, 2011
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 10, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 10, 1997
Dob violation - dismissed
ECB violations · 73
- Class - 2
Reissued ecb#35720063k failure to maintain building in code-compliant manner.noted at ceiling and wall inside electrical room water penetration leak.rem:repair and/or replace.
May 8, 2026 · Penalty $3,125
Active - Class - 2
Reissued ecb#35655406p failure to provide ventilation to gas meter room per p115.6,fgc appendix e.noted:at gas meter room and electrical room no fresh air or mechanical ventilation system installed.
May 8, 2026 · Penalty $3,125
Active - Class - 2
Found hydrotherm gas fired boiler missing rating tag, relief valves in wrong position correct violating condition and submit a certificate of correction
Sep 12, 2025 · Penalty $6,250
Active - Class - 2
Found hydrotherm gas fired boiler missing rating tag relief valves in wrong position needs spill switches correct violating conditions and submit a certificate of correction
Sep 11, 2025 · Penalty $6,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at ceiling inside electrical room water penetration(leak). remedy: repair and/or replace.
Jun 12, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner: no fire stopping per bc 713.3; 27-345. cellar level in electrical room open holes around room. fire stop not done. remedy: provide/maintain fire stopping.
Jul 11, 2024 · Penalty $3,125
Resolve - Class - 2
28-301.1 reissue35561471y(8/4/21) failure to provide ventilation to gas meter rm per p115.6(1968code),fgc appexe(e4)(2014)@bsmt gas meter rm,no proper ventilation systems atoi.comply w/notice of vio.
Jun 15, 2022 · Penalty $3,125
Active - Class - 2
Missing rating plate on boiler,relief valve not vertical,spill switches missing,remote switch for boiler not at arms length,correct violation & send in certificate of correction
Mar 15, 2022 · Penalty $3,125
Active - Class - 2
Missing rating plate,on boiler,no switch at door to boiler room,no clean out at base of chimney,relief valve to be vertical,illegal valves on weil mc.moduel correct violation and send in certificate of correcti
Mar 15, 2022 · Penalty $3,125
Active - Class - 2
28-301.1 reissue35498491m noted:@bsmt level gas&electrical meter rm,doesnt have any fresh air or mechanical ventilation system installed.comply w/notice of violation.
Aug 4, 2021 · Penalty $3,125
Active
Show 40 more ↓
- Class - 2
Reissue35498493x failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc100.1;27-381.noted:@bsmt level by entrance to multipurpose rm&rm itself,emergency
Aug 4, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue35498492y failure to maintain bldg in codecompliant manner:no firestopping per bc712.3;27-345.noted:@bsmt level gas&electrical meter rm;have holes in various areas thruout.provide/maintain firestopping.
Aug 4, 2021 · Penalty $3,125
Resolve - Class - 2
Sec. 28-301.1 reissue#35452173n failure to provide ventilation to gas meter room per p115.6(1968 code),fgc appendix e(e4)(2019 code). noted:at basement level,no ventilation provided to gas meter room.
Jun 17, 2020 · Penalty $3,125
Active - Class - 2
Failure to maintain building wall(s)or appurtenances.noted:at the time of inspection,observed at first floor at various class rooms and at basement at multipurpose room,stained/missing ceiling files due to defe
Jun 17, 2020 · Penalty $1,250
Resolve - Class - 2
Reissue#35452171j failure to maintain bldg in code compliant mannar illumination for exits,exit discharges & public corridors per 1006.1;27-381. noted: at basement,multi purpose room,emergency exit lighting inf
Jun 17, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35452172l failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3;27-345. noted: at basement,at gas meter,meter electrival meter room,missing fire stopping w/holes in the walls.
Jun 17, 2020 · Penalty $3,125
Resolve - Class - 2
Reissue#35452170h failure to maintain bldg in code compliant manner. noted: at basement,water penetration at gas meter room & electrical meter room. remedy: make necessary repairs.
Jun 17, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35452169k failure to maintain bldg in code compliant manner. noted: at basement,at gas meter room & electrical room,illegal storage of misc items/materials. remedy: remove illegal storage.
Jun 17, 2020 · Penalty $1,562
Resolve - Class - 1
License master plumber#0909 pulled emergency work notification (ewn)#q-00280433 on 12-12-2019 to restore heat to the building by replacing several feet of gas piping. but failure to comply with the rules of ewn
Feb 1, 2020 · Penalty $2,500
Active - Class - 2
Failure to maintain building in code complaint manner illumination for exits exit discharges and public corrdiros per 1006.1/27-381 noted at basement multi purpose room emergency lights are non operationsl thro
Sep 9, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner no fire stopping per bc 712.3/27-345 noted at basement gas and electric meter rooms fire stopping misiing /none throughout in various locations provide/main
Sep 9, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner noted at basement gas and electri meter rooms storage of various items and materials comply with code
Sep 9, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner noted at basement gas and electric meter rooms water penetration damage with staing to walls & floors repair and or replace
Sep 9, 2019
Resolve - Class - 2
28=301.1:failure o provide ventilation to gas meter room per p 115.6(1968 code) foc appenxis e(e4) (2014 code0 noted at basement gas meter room with having no ventilation system installed comply with notice of
Sep 9, 2019
Active - Class - 2
Failure to maintain adequate fire stopping observed:@ boiler room,missing drywall @ interior of room adjacent entry door & around pipe penetration to left as you enter room.rem:maintain adequate firestopping.
Mar 13, 2015
Resolve - Class - 2
Failure to maintain.observed:water penetration into electrical & boiler rooms through foundation wall &/or electric conduit from street.rem:maintain bldg.
Mar 13, 2015
Resolve - Class - 2
Failure to maintain.observed:@ rear bldg(#2)water penetration into class rooms from roof @ rooms e,g,h.noticeable deterioration of roof deckaround areas of penetrations.rem:maintain bldg.
Mar 13, 2015
Resolve - Class - 3
Failure to maintain.observed:main entry door is racked,diffict to close,door hanging causing improper alignment.rem:maintain bldg.
Mar 13, 2015
Resolve - Class - 2
Failure to maintain.observed:@ main bldg fl 102 lower window operator broken on app 30 windows,making windows difficult to crew & close.rem:repair windows.
Mar 13, 2015
Resolve - Class - 2
Failure to maintain bldg.noted evident signs of water penetration into multiple classrooms of rear bldg(b)room y,71,72,76,78 also stair 'a' alsp spalling concrete ceiling in swimming pool exposing rebar,ceiling
May 22, 2014
Resolve - Class - 2
Doors not closing at basement main bldg,entry & rear exit doors are not closing w/no closers on basement entry fire proof doors. remedy: provide door closers/maintain doors self closing.
Jul 29, 2013
Resolve - Class - 2
Sec. 712.3;27-345 missing fire stopping. at electric meter room in main bldg,holes & penetrations in sheet rock fire walls to concealed spaces. remedy: provide/maintain fire stopping.
Jul 29, 2013
Resolve - Class - 2
Sec. 712.3;27-345 missing fire stopping at electric meter room in poolbldg,openings & penetrations in cmu block fire wall. remedy: provide/maintain fire stopping.
Jul 29, 2013
Resolve - Class - 2
Spalling concrete at pool area rear,spalling & cracking in concrete ceiling w/pieces missing exposing rebars which are begining to decay,rust & spall. remedy: repair concrete masonry.
Jul 29, 2013
Resolve - Class - 2
Reissue: 34922577r stairs leading to the pool level is missing guard railing from the 1st floor level. noted: guard railing is in a locked closet in building #2 pool area. remedy: provide a railing leading to
Jul 10, 2012
Resolve - Class - 2
Reissue: 34922576p rear concrete step are being under mined & sloping towards 1 side located behind the pool area at building #2. remedy: repair &/or replace rear sidewalk.
Jul 10, 2012
Resolve - Class - 2
Reissue: 34922578z the electrical room is lacking fire - stopping at the building #1 adjacent to the multi - purpose room at cellar level. remedy: provide/maintain fire stopping at the electrical room.
Jul 10, 2012
Resolve - Class - 2
Reissue #34830786p fl opening on 1st fl lvl inside closet is missing guard rails leading to bsmt lvl rem: provide maintain guard rail at opening in floor
Jun 24, 2011
Resolve - Class - 2
Reissue 334830787r exterior rear concrete steps are being under minded on the 1st fl lvl rem: fill in open gaps under concrete steps
Jun 24, 2011
Resolve - Class - 2
Reissue #34830789k drop ceiling tiles in the cafeteria is loose & missing at the bsmt lvl rem: repair &/or replace drop ceiling tiles
Jun 24, 2011
Resolve - Class - 2
Reissue 34830784l the electrical room is lacking fire stopping locatedat the bsmt lvl rem: provide maintain fire stopping in the electrical room
Jun 4, 2011
Resolve - Class - 3
Reissue: 34793272h. interior cafeteria ceiling tiles are loose & missing at the lower level. remedy: repair/replace missing/loose ceiling.
Mar 8, 2010
Resolve - Class - 2
Reissue: 34793273j. interior flr tiles around drain area is sinking atpool room at basement level causing a tripping hazard. remedy: repair/replace sinking flr tiles.
Mar 8, 2010
Resolve - Class - 2
Reissue: 34793274l. exterior concrete sidewalk/steps at rear of schoolis being under mined on 1st flr level. remedy: repair/replace concretesidewalk & steps.
Mar 8, 2010
Resolve - Class - 2
Reissue: 34780075x. the opening leading downstair (step ladder) to thebasement does not have guard rail to prevent someone from falling down. remedy: provide railing.
Mar 8, 2010
Resolve - Class - 2
Reissue: 34780078l exterior roof has become porous and leaking rain water into classrooms e,h,g, at 1st flr level causing interior damages &cafeteria & electrical room. remedy: repair/replace water-proofing.
Mar 8, 2010
Resolve - Class - 2
Reissue: the electrical room is lacking fire stopping at the basement level. remedy: provide/maintain fire-stopping.
Mar 8, 2010
Resolve - Class - 2
The concrete sidewalk at the rear of the premises is being order mine on the 1st fl lvl rem: repair replace sidewalk
Jun 29, 2009
Resolve - Class - 2
Reissue: 34698833n the fl tiles in the pool room is sinking missing located in the bsmt lvl causing a tripping hazard rem: replace repair sinking missing floor tiles
Jun 29, 2009
Resolve - Class - 2
Reissue: 34698832l the ceiling tiles in the cafeteria are loose and missing located in the cafeteria bsmt lvl rem: repair replace ceiling tiles
Jun 29, 2009
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W8)
- Year built
- 1981
- Floors
- 1
- Residential units
- —
- Building area
- 10,084 ft²
- Lot area
- 26,000 ft²
- Zoning
- R1-2
- Community board
- 411
- Council district
- 19
- Block / lot
- 6185 / 1
- Assessed value
- $1,645,200
- Landmark / historic district
- No
Questions about 221-21 Corbett Road
Who owns 221-21 Corbett Road?
The owner of record in NYC Department of City Planning PLUTO data is The Gordovia Living Trust.
Does 221-21 Corbett Road have violations?
NYC HPD has no housing violations on record for this property.
Is 221-21 Corbett Road rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 221-21 Corbett Road built?
City records list 1981 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.