74-10 88 Street
Queens, NY 11385BBL 4-03810-0093Map
Owner of record: Congregation Ygs
74-10 88 Street is a religious facility built in 1930 in Queens, 11385. The owner of record is Congregation Ygs. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 37
- ECB violations
- 22
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 37
- Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 16, 2016
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 16, 2016
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 16, 2016
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 16, 2016
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 27, 2016
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 27, 2016
Dob violation - dismissed
Show 27 more ↓
- Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 27, 2016
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 27, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 17, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 17, 2014
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2011 inspection/test
Oct 1, 2012
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 3, 2012
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 30, 2012
Dob violation - resolved - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jan 1, 2012
Dob violation - active - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2010 inspection report
Dec 13, 2011
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2010 inspection/test
Dec 13, 2011
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2010 inspection report
Dec 13, 2011
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 12, 2010
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 20, 2010
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 19, 2008
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Construction other optional
C-construction other optional
Jun 14, 2006
Dob violation - dismissed - Construction other optional
C-construction other optional
Dec 15, 2005
Dob violation - dismissed - Construction other optional
C-construction other optional
Sep 8, 2005
Dob violation - dismissed - Construction other optional
C-construction other optional
Jun 10, 2004
Dob violation - dismissed - Construction other optional
C-construction other optional
Jun 10, 2004
Dob violation - dismissed
ECB violations · 22
- Class - 2
Failure to maintain bldg in code compliant manner. noted: observed @ mezzanine roof level @ 2 large skylights no protection railings installed around the skylights. @ mezzanine flr the fire proof self closing d
Aug 5, 2016 · Penalty $250
Resolve - Class - 2
Unapproved/unsafe/unsuitable electrical equipment, apparatus, materials, devices, appliances or wiring in use. observed @ time of insp (10:00am) @ roof level: a)flexible cord use as a permanent wiring. b) elect
Aug 5, 2016 · Penalty $400
Resolve - Class - 1
Failure to maintain bldg in a code compliant manner; gas piping to rooftop hvac units on 8-5-16, i observed on rooftop at 20 hvac units. all units has severely rotted and pitted black gas pipe. bare black ga
Aug 5, 2016 · Penalty $1,000
Active - Class - 1
Failure to maintain bldg in a code compliant manner: defective gas locktop. inspection time: 10am. on 8/5/16 i observed in kitchen of above cited premises a six burner gas cooktop,there was a strong odor
Aug 5, 2016 · Penalty $250
Resolve - Class - 1
Work does not conform to approved construction documents and/or approved amendments; exceeding scope of work inspection time: 10:30am.on 06/02/16, i observed at above cited premises appp 8' on 1"black pipe goin
Jun 2, 2016 · Penalty $500
Resolve - Class - 1
Fail to perform hydrostatic pressure test-sprinkler.inspection time:10:30am. on 6/2/16, i observed new sprinkler heads and piping on second floor.the replacement of 25 spirnkler heads was covered under applicat
Jun 2, 2016 · Penalty $2,400
Resolve - Class - 2
Failure to maintain bldg in a code compliant manner re:installation/maintenance of plumbing materials per bc 102.3,27-902 inspection time: 10:30am. on 6/2/16, i observed at above cited property pvc piping on
Jun 2, 2016 · Penalty $500
Resolve - Class - 2
Work no permit. replaced sprinkler heads on 2nd flr. remove 2 sprinkler heads in itchen hood. disapproved laa 421122494 at time of inspect rmdy: obtain a permit or restore to prior legal condition.
Dec 7, 2015 · Penalty $500
Resolve - Class - 1
Failure to maintain building in code compliant manner.lack of a systemor automatic sprinklers where required.observed 11/16/15 laundry room equipment enclosed 100% with plywood,with no inside sprinkler protecti
Nov 16, 2015 · Penalty $1,000
Resolve - Class - 1
Electrical work w/out a permit an app for cert of electrical insp is not on file.for electrical feeders from bldg to t.c.4.trailers.no app file for elecrical connection for(compoctor).rem:obtain electrical perm
Nov 2, 2015 · Penalty $1,600
Resolve
Show 12 more ↓
- Class - 1
Work w/out permit.work noted:@the front side of the lot premises installed 8 trailers 1 story & use as a classrms & a 2 story trialers w/4 rms use as classrms & storage trailers/classrms arw supported on the to
Nov 2, 2015 · Penalty $1,600
Resolve - Class - 1
Occupancy contrary to that allowed by the bldg dept records.noted:observed @time of insp @1st fl all the classrms converted to dorms(rms)w/tota; 212 beds.@mezzanine level(5) classrms converted dorms(rms) w/180
Nov 2, 2015 · Penalty $2,400
Resolve - Class - 2
Illegal use in a manufacturing district.observed @time of insp the 1stfl classrms to be use as dorms (rms) w/total 392 beds.drms (rms) are premitted on c-1 to c-6 zoning under ug-3.premises is on m1-1 zoning di
Nov 2, 2015
Resolve - Class - 1
Failure to maintain bldg in code-compliant manner.1)water damage observed w/mold @the ceilings of dorms rms & public hallway.2)@several rms observed the fire alarm not supported @properly @the ceiling & be hang
Nov 2, 2015 · Penalty $1,000
Resolve - Class - 1
Failure to maintain bldg in code-compliant manner.no guardrails installed @the accessible roof around the large skylight.roof is accessible by a door & missing guardrails creating a fall hazards for any person
Nov 2, 2015
Resolve - Class - 1
Failure to provide a system of automatic sprinklers where required perbc 903.2; 27-954 failure to maintain inspection time: 9am on 11-2-15, i inspected above cited premises, a religious campus.throughout bldg
Nov 2, 2015 · Penalty $1,000
Resolve - Class - 1
Work w/o a permit: installation of hood over cooking equipment.inspection time: 9am on 11-2-15 i observed in above cited premises a large exhaust hood covering cooking equipment, with ansul type protection miss
Nov 2, 2015
Resolve - Class - 1
Occupancy contrary to that allowed by certificate of occupancy.noted dob cofo #401634148 and approved plan #a-105 indicates that 30 rooms @east part of bldg to be occupied as transient hotel (ug5).as per table
Oct 14, 2015 · Penalty $2,400
Resolve - Hazardous
Failure to comply wtih stop work order the prior violation was issued on 06/14/06.violation #061406c0501st noted:working on installation of floor tiles,painting wall.concrete work on floors,stucco work.
Jun 28, 2006 · Penalty $2,500
Resolve - Hazardous
Failure to safely & properly remove constr. debris from site appl. #401634148 defects noted: accumulation of masonry lumber, organic debris strewn thruout of the premises lumber has stiking out nails, masonry
Dec 23, 2005 · Penalty $5,000
Resolve - Non-hazardous
Work does not conform to approved plan. alteration work with permit no401634148 - al. non-conforming work noted: 1) rooms #148, #149 door, windows not as per plan, 2) rooms #169, #170 wall location not as per
Nov 23, 2004 · Penalty $2,500
Resolve - Non-hazardous
Work does not conform to approved plans job#401634148 + structural demo#401722971 200lf of exterior wall at 1st floor removed contrary to plan at north and south side of bldg.remedy:conform to approved plans
Jun 10, 2004 · Penalty $250
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- Religious facility (M9)
- Year built
- 1930
- Floors
- 1
- Residential units
- —
- Building area
- 60,484 ft²
- Lot area
- 129,900 ft²
- Zoning
- M1-1
- Community board
- 405
- Council district
- 32
- Block / lot
- 3810 / 93
- Assessed value
- $4,952,250
- Landmark / historic district
- No
Questions about 74-10 88 Street
Who owns 74-10 88 Street?
The owner of record in NYC Department of City Planning PLUTO data is Congregation Ygs.
Does 74-10 88 Street have violations?
NYC HPD has no housing violations on record for this property.