82-37 Kew Gardens Road
Queens, NY 11415BBL 4-03360-0001Map
Owner of record: NYC Educational Construction Fund
82-37 Kew Gardens Road is a school building built in 1924 in Queens, 11415. The owner of record is NYC Educational Construction Fund. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 43
- ECB violations
- 55
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 43
- Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - active - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - active - No report and / or late filing (facade) facade required
Failed to file fisp cycle 7b technical report by 08/21/2012
Aug 30, 2013
Dob violation - dismissed
Show 33 more ↓
- Emergency power none
Ll2604e-emergency power none
Mar 31, 2008
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 21, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 21, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 21, 2007
Dob violation - resolved - Facade facade required
L1198-local law 11/98 - facade facade required
Jun 25, 2007
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 19, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 19, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 2, 2005
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 18, 2002
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Elevator elevatorrequired
4p4987
Oct 19, 2000
Dob violation - resolved - Elevator elevatorrequired
4p4988
Oct 19, 2000
Dob violation - resolved - Elevator elevatorrequired
4p4986
Oct 14, 2000
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Elevator elevatorrequired
4p4986
Jun 25, 1999
Dob violation - resolved - Elevator elevatorrequired
4p4987
Jun 25, 1999
Dob violation - resolved - Elevator elevatorrequired
4p4988
Jun 25, 1999
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 4, 1991
Vpw*-violation unserved ecb-work without permit-dismissed - Elevator elevatorrequired
(73)restore to service
Jan 30, 1990
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 30, 1990
Dob violation - resolved - Elevator elevatorrequired
(33)replace 1fl missing dust cover(35)secure 1fl interlock cover (43)remove vibration to car as it runs through shaft (51)provide missi ng electric box covers & secure wires in same on car top
Mar 21, 1989
Dob violation - resolved - Elevator elevatorrequired
(05)remove cable slippage to same(47)replace broken glass to mr door (51)clean car top (52)replace all electric box cover missing on t top of car (53)repair motor room lighting or renew as necessary
Mar 21, 1989
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 12, 1988
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 12, 1988
Dob violation - resolved - Elevator elevatorrequired
(51)remove exposed wiring from exhaust fan in motor room (47)remove non related equipment from motor room
Oct 12, 1988
Dob violation - resolved
ECB violations · 55
- Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at thetime of inspection observed and noted at 1st floor near room no 124 on
Feb 27, 2026 · Penalty $1,250
Active - Class - 2
Reissue#35678612h failure to maintain building in code-compliant manner.rooms 310,306,303,204,201 exit 14 interior doors not self closing.rem:repair and/or replace.
Mar 18, 2025 · Penalty $3,125
Resolve - Class - 2
Reissue#35678610y fail to maintain building in code-compliant manner.miss mortar above exit 7,5,3 exit 2,3 walkway crack in walkway by exit 1.rem:repair and/or replace.
Mar 18, 2025 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code-compliant manner.at parapet missing mortar above exit 7,5 3 fl missing mortar exit 1,3 lentils cracked above doorways,exit 1 walkway broken concrete in disrepair.rem:repair
Apr 15, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381 em.at 2 floor stair g,auditorium entrance 3 fl across 306 exit sign 1 floor
Apr 12, 2024 · Penalty $625
Resolve - Class - 2
Exit door not self-closing.at exit door 10 smoke exit 15,8,7,h,lunchroom 16,11 doors are not functioning properly.rem:repair/replace door.
Apr 12, 2024 · Penalty $625
Resolve - Class - 2
Fail to maintain building in code-compliant manner.at 3 floor room 310,306,303,2 fl 207,204,201 and auditorium left and right entrance doors1 fl exit 14 interior building doors are not functioning properly.rem:
Apr 12, 2024 · Penalty $625
Resolve - Class - 1
Work after hours without a variance permit contrary to 28-105.2 note at the time of inspection it was observed multiple workers dissmebling a sidewlak shed on all side of the above address job #421105333 descr
Feb 14, 2020
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at time ofinspection observed at exp#1 along the size of 83rd avenue the facade have a steep crack in various location also at left size of facade at
Jan 23, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant:lack of emergency lighting for exits, exit discharges & public corridors per bc1006.1; 27-542. noted: emergency lights by auditorium, stairs e, stairs g, exit from mai
Feb 22, 2017
Resolve
Show 40 more ↓
- Class - 2
Exit door not self closing. noted: exit 8a & exit 7 doors were removed exit by auditorium stage on right side is not self closing. rem: comply w/ summons. repair &/or replace door.
Feb 22, 2017
Resolve - Class - 2
Construction
Sep 25, 2015
Resolve - Class - 2
Re-issue # 35023138m. water penetration from play yard entering room 120,124, cafeteria storage room, gym closet. remedy: seal penetration.
May 15, 2014
Resolve - Class - 2
Re-issue # 35023137k. illegal hardware at classroom doors throughout with door stops. remedy: remove hardware.
May 15, 2014
Resolve - Class - 2
Exit door not self-closing.note:kick down door stops installed on doors to rooms 112,304,305,auditorium,corridor doors at room 120,and various other doors to rooms w/no numbers.rem:remove door stops.
Jun 12, 2013
Resolve - Class - 2
Fail to maintain.note:water penetrating from playyard,cause damage to ceilings of auditorium, gym, & rooms 120 (120). remedy:make all necessary repairs.
Jun 12, 2013
Resolve - Class - 2
Reissue#34918505x.water pentrating through foundation wall into electrical room.rem:provide water proofing to foundation.
May 16, 2012
Resolve - Class - 3
Water penetrating through roof in rooms 120 & 124 leaks are located @ pipe penetrations for roof drains.rem:repair roof.
May 16, 2012
Resolve - Class - 2
Water penetrating from playground above cafeteria into cafeteria & storage room.rem:water proof affected areas.
May 16, 2012
Resolve - Class - 2
Ceilings of rooms 120,124,cafeteria storage room & gym damaged from exterior water penetrating.rem:repair damaged areas.
May 16, 2012
Resolve - Class - 2
Reissue #34830751p. water penetration. water penetrating into cafeteria storage room and teacher's lunch room. remedy: water proof affected areas.
Jun 9, 2011
Resolve - Class - 2
Water penetration. at electric room, the foundation at electric pull box conduit has become porous allowing water to enter w/water running through electric box. w/a pail under electric box full of water @ time
Jun 9, 2011
Resolve - Class - 2
Water penetration. at tank room, the foundation and slab has become porous allowing water to enter w/2" of standing water at time of inspection. remedy: water proof foundation & slab, remove water.
Jun 9, 2011
Resolve - Class - 2
Excessive combustibles. at 1st flr corridor between exits 1 & 5, excessive combustible art work and decorations hanging from and across ceiling. remedy: remove all items.
Jun 9, 2011
Resolve - Class - 2
Reissue: #34830752r. defective plaster. spalling plaster at cafeteria storage room and teachers lunch room & missing ceiling tiles in teachers lunch room. remedy: repair/replace plaster surfaces & ceiling tile.
Jun 9, 2011
Resolve - Class - 2
Reissue 34711118h,34791655x-water penetration through exterior playground into cafeteria,teachers cafe.rem-seal penetration.
Jan 29, 2010
Resolve - Class - 2
Reissue 34791656h,57j plaster damage in cafeteria storage room,also missing ceiling file in teachers cafe.rem-make repairs.
Jan 29, 2010
Resolve - Class - 3
Reissue: 3471118h playground flr leaking into cafeteria & gym beneath cafeteria & storeroom. remedy: waterproof playground flr.
Jun 10, 2009
Resolve - Class - 3
Wet,missing ceiling tile cafeteria hall exit 11,teachers cafeteria & cafeteria ceiling in front of kitchen. remedy: repair replace tile.
Jun 10, 2009
Resolve - Class - 3
Cafeteria storeroom rear wall spalling(wet plaster). remedy: repair wall.
Jun 10, 2009
Resolve - Class - 2
Corridor door stair e 1 flr,front & rear exit doors to gym out of alignment wont properly close. right rear auditorium door missing(closer) remedy: repair/replace doors & hardware.
Jun 10, 2009
Resolve - Class - 3
Water penetrating play ground flooring. water leading into gym/kitchen storage room below playground. remedy: seal all penetrations.
Nov 5, 2008
Resolve - Non-hazardous
Floor numbering signs missing at stairs throughout within stairwells & corridor(s) shoes,also stair identifications missing.remedy:install signs
Jun 19, 2007
Resolve - Non-hazardous
Failure to maintain. defect is curb attached to west side retaining wall approx. 15' in to 83 ave garage entry/exit is crumbling cracked & broken. upper retaining wall is also cracked. remedy:make area safe mak
Jun 6, 2005
Resolve - Non-hazardous
51k11, 51-change hoist cables
May 20, 2004 · Penalty $2,500
Active - Non-hazardous
83x10 83-x-10 restore elevator to service so a complete inspection canbe made by this dept
May 13, 2004
Resolve - Non-hazardous
59q03/39o02/10m07 10/m second ave
Feb 20, 2004
Resolve - Non-hazardous
50o02/43o02/24l07 24/l car indicators
Feb 20, 2004
Resolve - Non-hazardous
10m7/43h08/49q3/39o02 10/m second gib
Feb 20, 2004
Resolve - Hazardous
Failure to maintain exterior balcony.defect noted stucco lifting and cracking on outside wall of balcony 123-33 apt 504 and other balcony'es.remedy:repair defects maintain exterior bldg wall.
Sep 24, 2003 · Penalty $800
Active - Non-hazardous
43h08,17m11,71m07,31h11,21m07,66o02. (17) sc-worn 9 fl missing rear (71) toe guard (31) roller guides (21) door lock covers.
Aug 6, 2003 · Penalty $180
Resolve - Non-hazardous
31h11,25d06,66o02. (31) counterweight roller guide
Aug 6, 2003 · Penalty $180
Resolve - Non-hazardous
41d06,31h11,53m11,71m07,44m07. (41)cx relay on controller (31)counterweight roller (71) toe guard (44)cover
Aug 6, 2003 · Penalty $180
Resolve - Non-hazardous
Failure to provide adequate emergency exit lights on all floors,corridors and all stairs.failure to provide emergency power to exit lights on all floors,corridors and all stairs.failure to provide emergency po
Apr 3, 2001
Resolve - Non-hazardous
Failure to maintain building:defects are damaged & cracked ceilings rm 302,303,304,306,311,308,352 cracked on walls in rm 305,306,308,309 3rd fl teacher bathroo,208& 352.remedy:do all repairs immediately.
Feb 9, 2001
Resolve - Non-hazardous
Failure to carry out permitted work in accordance with applicable laws& regulations in that construction activities are being performed oth-er than on weekdays between the hours of 7am & 6pm w/o variance as req
Dec 1, 1999 · Penalty $2,500
Active - Non-hazardous
Failure to maintain. defect: numerous leaks at windows causing spall- ing plaster & peeling paint. roof leaking numerous locations. remedy: replace all windows, make all repairs.
Apr 5, 1999
Resolve - Non-hazardous
Failure to maintain. defect: no emergency (in stairwells) lighting or other locations thru-out building. remedy: install emergency lighting as per n.y.c. building code.
Apr 5, 1999
Resolve - Non-hazardous
Failure to maitin. defect exterior facades including perapets. loose mortar and bricks and coping stones. minor verticle wall north side. obtain all necessary repairs.
Feb 22, 1999
Resolve - Non-hazardous
73o22d (73-all 3 cars).
Jan 31, 1998 · Penalty $180
Active
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1924
- Floors
- 3
- Residential units
- —
- Building area
- 40,997 ft²
- Lot area
- 77,300 ft²
- Zoning
- C4-4
- Community board
- 409
- Council district
- 29
- Block / lot
- 3360 / 1
- Assessed value
- $7,099,200
- Landmark / historic district
- No
Questions about 82-37 Kew Gardens Road
Who owns 82-37 Kew Gardens Road?
The owner of record in NYC Department of City Planning PLUTO data is NYC Educational Construction Fund.
Does 82-37 Kew Gardens Road have violations?
NYC HPD has no housing violations on record for this property.
Is 82-37 Kew Gardens Road rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 82-37 Kew Gardens Road built?
City records list 1924 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.