68-17 68 Avenue
Queens, NY 11375BBL 4-03172-0002Map
Owner of record: NYC Department Of Parks And Recreation
68-17 68 Avenue is a school building built in 1955 in Queens, 11375. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 31
- ECB violations
- 73
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 31
- Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 10, 2015
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2010 inspection/test
Dec 13, 2011
Dob violation - dismissed
Show 21 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Oct 4, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 24, 2010
Vw*-violation - work w/o permit dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 21, 2004
Vw*-violation - work w/o permit dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 28, 1995
Vp*-violation unserved ecb- dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 28, 1993
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed - Elevator elevatoroptional
1
Oct 12, 1989
Dob violation - dismissed - Elevator elevatorrequired
(51)restore elevator to service so that a complete inspection can be made by this department or file to have same classified as out of use or dismantled
Jul 6, 1988
Dob violation - resolved
ECB violations · 73
- Class - 2
Reissue#35725430x failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.noted:in basement,electric meterroom main entrance door has wire mesh above door preventing fire-stopp
Jul 28, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35725429z failure to maintain building in code-compliant manner.noted:interior fpsc doors do not self-close properly when tested at 3rd flr-staircase c,g.basement-cafeteria door.classroom doors do not s
Jul 28, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: interiorsmoke doors not self-closing properly. classroom doors do not self-close properly, 3rd flr-320, 318, 317, 315, 307, 311, 304, 302, 301, 323,
Sep 18, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. noted: electric meter room is missing fire stopping in multiple places and door has mesh wiring on the top of it. re
Sep 18, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. at 2 floor corridor by room 234 and 1fl. corridor by 119 doors are not closing properly. remedy: repair and/or replace.
Jul 30, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at stage left, 1-4, 1-15 and gym emergency lights are not lighting prop
Jul 30, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner. at bulkheads b-c, e-f, g-h stairwells roof leaks at ceiling, stair i and o 3 floor ceiling crack and wall, stair b-c between 2 and 3 fl. crack in wall. rem
Jul 30, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner:lack of emergency lighting for exits,exit discharges and public corridors per bc1006.1;27-542.observed on 2nd and 3rd floor corridors exits(staircase)no eme
Jun 17, 2022 · Penalty $1,250
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor
May 26, 2021 · Penalty $1,250
Resolve - Class - 2
28-301.1 reissue: #35147196p-27-misc-no ventilation for rms:#331,245 &331b. occupied.remedy: repair and/or replace.
Jun 17, 2020 · Penalty $3,125
Resolve
Show 40 more ↓
- Class - 2
Sec. 28-301.1 reissue#35290649k failure to provide natual or mechanical ventilation to occupied spaces per mc 401.2. room#331b & room#245 are used as teachers rooms. remedy: comply w/notice of violation.
Aug 14, 2019 · Penalty $3,125
Resolve - Class - 2
24b,50. found 1- fitzgibbons boiler; 50-missing ladder and work plat form; 24b-missing emergency shutoff switch at 2nd boiler room door correct all violating conditions and submit a certificate of correctio
Sep 26, 2018
Resolve - Class - 2
24b, 50. found 1 fitzgibbons boiler; 50-missing ladder and work plat form; 24b-missing emergency shut off switch at 2nd boiler room door. correct all violating conditions and submit a certificte of correction
Sep 26, 2018
Resolve - Class - 2
24b,50. found 1- fitzgibbons boiler; 50-missing ladder and work plat form; 24b-missing emergency shutoff switch at 2nd boiler room door correct all violating conditions and submit a certificate of correctio
Sep 26, 2018
Resolve - Class - 2
Reissue #35272481r- failure to maintain bldg in code-compliant manner:use of prohibited door &/or hardware per bc 1008.1.8;27-371(j) illegalhardware includes kick stops in auditorium on right side,main entrance
Jul 3, 2018
Resolve - Class - 2
28-301.1 reissue:(35084862m)-no ventilation in rooms that be occupied w/students.rooms 331,245,225,331b.rem:comply w/summons.
Jul 3, 2018
Resolve - Class - 2
Reissue:35272480p-failure to maintain bldg in code-compliant manner:illumination for exits exit discharges & public corriodors per bc 1006.1;27-381 emergency lights @auditorium are not wworking properly when te
Jul 3, 2018
Resolve - Class - 2
Sec: 28-301.1. reissue# 35147196p. failure to provide natural or machanical ventilation to occupied spaces per mc 401.2 room# 245 use as teachers room, inadequate ventilation. rem: comply w/ nov.
Jul 21, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: illumination for exits, exit discharges & public corridors per bc 1006.1, 27-381. existing emergency light are not operational when tested. in auditorium 4 set
Jul 21, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8; 27-371(j) illegal hardware includesuse of kick stops. in auditorium right side main entrance door use ill
Jul 21, 2017
Resolve - Class - 2
Reissue#35747197r,failure to maintain bldg in code compliant manner. at austin st ramp railing loose unsecured at base outside exit door. remedy: comply w/notice of violation.
Nov 30, 2016
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner:illumination for extist,exit discharges & public corridors per bs 1006.1;27-381 note:@the time of insp @1st fl level in auditorium exit signs not illuminated.re
Aug 19, 2015
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.re-issue #35084861k issued on 2/6/14 austin street ramp railing is loose/unsecured concrete @base dislodged.rem:comply w/the notice of vio.
Aug 19, 2015
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtenances.note:@the time of insp @bsmt level in electrical rm a water run off system w/water standing in a bucket as well a moterized water pump w/hose leading out of the
Aug 19, 2015
Resolve - Class - 2
27-misc misc. vio re-issue #35084862m issued on 2/6/14 no centilation provided for rms 331,245,225 & 331b.rms occupied w/teachers,students.rem:comply w/the notice of vio.
Aug 19, 2015
Resolve - Class - 2
Re-issue # 35015672m. defective doors on 3rd flr stairway e & h; 2nd flr e & h & corridor door adjacent to room 231; 1st flr stairwell c, e & f; basement stairwell e, f & h. doors dragging, split doors & broke
Feb 6, 2014
Resolve - Class - 2
Re-issue # 35015671k. work without permit. sub-dividing rm 331 w/ full height partitions. remedy: obtain permit.
Feb 6, 2014
Active - Class - 2
Re-issue # 35015674x. austin street ramp railing is loose/unsecured. concrete at base dislodged. remedy: secure railing.
Feb 6, 2014
Resolve - Class - 2
27-765. re-issue # 35015673y. no ventilation provided for rooms 331, 245, 225 & 331b. rooms occupied w/teachers/students. remedy: provide proper/adequate ventilation.
Feb 6, 2014
Resolve - Class - 2
Defective doors at 3rd flr stair c,h and 2nd flr stair f,h, corridor door near 231. remedy: repair/replace doors.
Jun 27, 2013
Resolve - Class - 2
Reissue 34981827k, 34893462r. no ventilation provided for rooms 331,245,225 rooms occupied w/teacher/students. remedy: discontinue illegal use/provide ventilation. sec.27-765. remedy: discontinue illegal use/
Jun 27, 2013
Resolve - Class - 2
Austin street ramp railing is loose/unsecured. concrete at base dislodged. remedy: secure railing.
Jun 27, 2013
Resolve - Class - 2
Work w/o permit sub-dividing rm 331 full height partitions remedy: obtain permit.
Jun 27, 2013
Resolve - Class - 2
Reissue #34893462r inadequate ventilation at rooms 245 and 331b rooms used as offices and one on one for student instruction w/ inadequate ventilation and no windows rem; provide adequate ventilation to occupie
May 30, 2012
Resolve - Class - 2
Reissue #34893461p defective doors at bsmt girls btrm stairway e & f w/ broken hinges broken door closers rem: repair doors to properly open and self close
May 30, 2012
Resolve - Class - 2
Missing fire stop at gas meter room steel entry door w/ holes in it rem: seal all holes provide maintain fire stopping
May 30, 2012
Resolve - Class - 2
Work w/o permit at room 331 room dived w/ full height partition lighting fixtures pass through partition w/ no fire protection btwn room 331 and 331b also room 331b divided creating telecom room and small offic
May 30, 2012
Resolve - Class - 2
Inadequate ventilation in rooms 245,331 rooms converted into offices w/evident signs of child occupancy.no natural or mechanical ventilationnoted in rooms.rem:must provide ventilation to occupied rooms
May 20, 2011
Resolve - Class - 3
Defective door @ bsmt girl bathroom not closing.rem:replair/replace door
May 20, 2011
Resolve - Class - 3
Defective flooring @ room 240.multiple tiles loose/missing.rem:mantain flooring
May 20, 2011
Resolve - Class - 2
Reissue34855025l,34761541k,34692755j.electrical panel room missing fire stopping open pipe penetration & metal opening above door.rem:provide fire stopping
May 20, 2011
Resolve - Class - 3
Reissue34855027p.missing mortar on cmu wall boiler room between boys shower.also concrete spalling exposing rebar @ boiler room chase tunnelrem:maintain bldg
May 20, 2011
Resolve - Class - 2
Failure to maintain observed:defective handicap door operators @ 1st flr lobby outside gym & rm 154 handicap access pads fail to open doors when pressed.rem:maintain bldg per code
Jun 3, 2010
Resolve - Class - 2
Reissue34692754h observed:missing mortar/open joists on cmu wall boiler room demising wall between boys shower & boiler room.also concrete,exposed rebar boiler room chase tunnel.rem:maintain bldg
Jun 3, 2010
Resolve - Class - 2
Reissue 34761543y observed:racked f.p.s.c doors @ 2flr stair b&c, 1fl stair d & 1a. doors hard to open or won't properly close.rem:maintain bldg
Jun 3, 2010
Resolve - Class - 2
Reissue34761541k failure to maintain.observed @ electric room, open diamond lathe transform over doors,also open holes around several electrical conduits.@ gas meter room.open rows of circular holes in fire doo
Jun 3, 2010
Resolve - Class - 2
Tripping hazard in cafeteria multiple areas of possible acm tiles bulging cracks throughout bsmt lvl rem: repair floor
Feb 27, 2009
Resolve - Class - 3
Re 34692755j electrical panel room missing fire rating at cellar lvl on top of door opening metal wire grill in place rem: fire rate at top of door
Feb 27, 2009
Resolve - Class - 3
Electrical room door at basement level was not sealed. metal open wirelath. on top of door opening. remedy: replace wire lath with solid fire rated material.
Jul 9, 2008
Resolve - Class - 3
Cement block wall erected in boiler room and boys shower now has vertical cracks and open mortar joints with water damage.. remedy: repair cement block wall.
Jul 9, 2008
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1955
- Floors
- 3
- Residential units
- —
- Building area
- 134,102 ft²
- Lot area
- 137,530 ft²
- Zoning
- R7-1
- Community board
- 406
- Council district
- 29
- Block / lot
- 3172 / 2
- Assessed value
- $24,183,450
- Landmark / historic district
- No
Questions about 68-17 68 Avenue
Who owns 68-17 68 Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.
Does 68-17 68 Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 68-17 68 Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 68-17 68 Avenue built?
City records list 1955 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.