roofy

61-21 97 Place

Queens, NY 11374BBL 4-02083-0123Map

Owner of record: NYC Department Of Education

61-21 97 Place is a school building built in 1956 in Queens, 11374. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
9
ECB violations
75
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 9

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations · 75

  • Class - 2

    Reissue#35725347p date of issue:09.11.2025 exit door not self-closing properly outside main exit door.at the time of inspection observed andnoted 1st flat exit-8 3 outside exit doors and at 1st fl exit-12 one e

    Jul 15, 2026 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35725348r date of issue:09.11.25 failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at the time of inspection observed

    Jul 15, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.fpsc doors,exit doors or classroom doors are not self closing properly for difective hardware,door closure or hinges at the time of inspection observed and

    Jul 15, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35684601n. exit door not self-closing. noted exterior doors at exit #8 and 5 not closing or opening properly without excessive force. also 1st fl stair a and old cafeteria entry doors were rached. clas

    Sep 11, 2025 · Penalty $625

    Active
  • Class - 2

    Reissue #35684600l. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted emergency lights not working when tested: (3)

    Sep 11, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted at old building cellar electrical room,water penetration through hole for conduit with garbage pail stayed to collect water.additionally water penetra

    Jul 23, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted existing emegency lights not working when tested at old building cafet

    Jul 23, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted roof in disrepair at several locations with waterproof membrane pulling away along with insulation & vegetation growing allowing water to infiltrate i

    Jul 23, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue35584594x failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.observed:@transportable,existing emergency light arent op when teste

    Jun 21, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:lack of emergency lighting for exits,exit discharges&public ocrridors per bc1006.1;27-542.observed:@3&2fls,corridors emergency lighting required to illuminate&id

    Jun 21, 2022 · Penalty $1,250

    Resolve
Show 40 more ↓
  • Class - 2

    Reissued35495624n failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors for bc 1006.1;27-381.observed:existing emergency lights@1fl auditorium.corridors,arent

    Jun 21, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Work w/out permit.note:at the time of inspection observed sidewalk shed installed at exp.#1,2,& 3 w/out a valid permit in bis &/or dob now as of 11/04/2021.remedy:obtain permit.

    Nov 4, 2021

    Resolve
  • Class - 1

    Failure to institute/maintain safety equipment measures or temp const-no handrails.note:atoi i observed handrails isnt in place on stairwellb/w 1,2fl level create unsafe condition for 1st responder personnel/ot

    Oct 6, 2021

    Resolve
  • Class - 1

    Bc3307.4.7 failure to maintain work or storage zones.note:atoi of 3styschool bldg@roof level const work in progress i observed work&storage zone@exp3 adj to sws wasnt provided w/4' barrier&screen as required fa

    Oct 6, 2021

    Resolve
  • Class - 2

    Work doesnt conform to approved const docs note:atoi i observed that barriers in place for storage was aprx 60 linear ft&not 40' as requiredby approved dot permits stop all use of roadway&conform to approved do

    Oct 6, 2021 · Penalty $1,250

    Resolve
  • Class - 1

    Work does not conform to approved construction documents and or approved amendments note at the time of my inspection proposed 3 story new building i observed that existing s.o.e. drawing a supposed

    Aug 9, 2021 · Penalty $2,500

    Resolve
  • Class - 1

    Bc 3301.2 inadequate means of egress.at the time of inspection of proposed 3 story new building at foundation observed single ladder in place as a single means of egress from excavation not extending the requir

    Aug 9, 2021 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to safeguard all persons and property affected by construction operations.at time of inspection observed numerous violation conditions.all violating conditions are hazardous to construction workers.firs

    Aug 3, 2021 · Penalty $5,030

    Resolve
  • Class - 2

    Reissue#35495623l(06/10/2020)failure to maintain building in code-compliant manner.@ electrical room water infiltrated through conduits fromwater wall(97 place)side.remedy:repair and/or replace

    Jul 26, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35495624(06/10/2020)failure to maitnain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381 @ transportable operation to poorly deteriorate

    Jul 26, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35341664x noted: failure to maintain bldg in code compliant manner. electrical room on 97 place side. has water comiing through electrical feeders. remedy: repair &/or replace.

    Jun 10, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35442929p failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1 observed damaged emergency/exit lights. remedy: repair &/or replace.

    Jun 10, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue 35341664x-failure to maintain bldg in code-compliant manner.inelectrical meter room water leaks from ext through electrical feeder holes &pvc conduit.water comes in from well on 97 place.rem:repair &/or

    Aug 8, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner:use of prohibited door &/or hardware per bc1008.1.observed illegal kick stops on several fpsc doors thru-out bldg.rem:provide legal hardware & remove kick stop

    Aug 8, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.illumination for exits,exit discharges & public corridors per bc1006.1.observed in transportables damaged exit light & one operational when tested.also exit lig

    Aug 8, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.in electrical room wall on 97 pl water pouring in through electrical feeder holes.rem:repair or replace

    Jul 2, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. transportables 1 and 2 ceiling is leaking in various locations. rmdy: repair and/or replace.

    Jul 2, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381.noemergency lights throughout the building. rmdy: repair and/or replace

    Jul 2, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in a code-compliant manner.vision panels not as per code,27-371(b).14" thick wired glass.noted:on the 1st,2nd, & 3rd fls;classrooms & office doors in the corridors are missing wired gla

    Aug 17, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:lack of emergency lighting for exists,exit discharges & public corridors per bc 1006.1;27-592 noted emergency exit lights (2) @cafeteria are inoperative,3 emerg

    Aug 17, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:lack of emergency lighting for exits,exit discharges & public corridors.noted:emergency exit lights inoperative above the exit doors in transportables #t1,t2 &

    Aug 17, 2015

    Resolve
  • Class - 2

    Re-issue # 35023335l. water penetration into auditorium & rooms above gym on mezz. remedy: seal penetration.

    Feb 14, 2014

    Resolve
  • Class - 2

    Water penetration into bulkheads and auditorium, evident signs of roofflashing damage. remedy: seal penetrations.

    Jun 26, 2013

    Resolve
  • Class - 2

    Occupancy contrary @ north schoolyard,5 cars parked via jumping curb-no curb cut w/ side area way gate locked.c/o does not indicate off st parking.rem:discontinue illegal use or obtain permit & amend c/o.

    May 16, 2012

    Resolve
  • Class - 2

    Reissue#34847981l.defective play area rubber matting.@ north play yard,all rubber matting has seperated w/ gaps throughout creating a trip condition.rem:repair,replace,reset all rubber matting.

    May 16, 2012

    Resolve
  • Class - 2

    Reissue#34919077n.defective exterior wood entry.@ transportable units,unsecured planking & loose guard/handrails @ various location.t1,t2,& t3,t4.rem:repair & or replace as required.

    May 16, 2012

    Resolve
  • Class - 2

    Defective door.@ transportable unit t3-t4 the interior door is racked to frame & not properly self closing.rem:repair door to properly open & self close.

    May 16, 2012

    Resolve
  • Class - 2

    T2 &t3 interior walls in bathrooms broken in.rem:repair/replace walls

    Jun 3, 2011

    Resolve
  • Class - 2

    T4 entrance platform w/multiple wooden planks not screwed down.rem:repairs/replace planks

    Jun 3, 2011

    Resolve
  • Class - 2

    Failure to maintain observed: exterior door jambs rotted at base stairs a & b on 97 pl. remedy: maintain building.

    May 10, 2010

    Resolve
  • Class - 2

    Failure to maintain observed: water penetration into ceiling of rooftop mechanical room,hallway by rooms 305,207 & bulkhead wall stair b. remedy: maintain building.

    May 10, 2010

    Resolve
  • Class - 2

    Failure to maintain observed: at play yard on north side,separation ofrubber floor panels with gaps up to 3" wide. remedy: maintain building.

    May 10, 2010

    Resolve
  • Class - 2

    Reissue 34761951n failure to maintain. observed - around perimeter of school,sinking sidewalk,pavers & retaining walls,sinkholes in dirt yard on east side. remedy: maintain building.

    May 10, 2010

    Resolve
  • Class - 3

    50. 50- referenced boiler structure has an elevation in excess of 8' with no provision for safe access by personnel to the top of the unit. install a fixed steel ladder & associated platform to facilitate safe

    Mar 30, 2010

    Resolve
  • Class - 3

    50. 50- referenced boiler structure has an elevation in excess of 8' with no provision for safe access by personnel to the top of the unit.install a fixed steel ladder & associated platform to facilitate safe

    Mar 30, 2010

    Resolve
  • Class - 2

    Re 34692766p. exterior concrete and pavers at south side (rear) of bldg w/ severe setting erosion of soil around bldg causing shifting of concrete slabs pavers and small retaining walls. remedy: make safe remov

    Mar 4, 2009

    Resolve
  • Class - 3

    No solid cover to cover wire (mech) over electric room door that is open. remedy: provide solid cover over electrical room in cellar.

    Jul 11, 2008

    Resolve
  • Class - 3

    Cellar gas meter ( ) has no ventilation as required. re-issue 34525234r. remedy: provide ventilation.

    Jul 11, 2008

    Resolve
  • Class - 3

    Re-issue: 34586804l. on inspection exterior concrete & pavers in rear of auditorium & gymnasium pavement has sank at approx 6" around all exits. remedy: replace/repair concrete pavement.

    Jul 11, 2008

    Resolve
  • Hazardous

    Reissue:34523228k.roof has become porous & allowing rain water to enter the bldg causing interior damages in the auditorium rear on the 1st level.remedy:water-proof roof.

    Jul 24, 2007

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Jan 8, 2022 · Apt 6L

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1956
Floors
3
Residential units
—
Building area
95,995 ft²
Lot area
82,000 ft²
Zoning
R7-1
Community board
406
Council district
24
Block / lot
2083 / 123
Assessed value
$13,215,600
Landmark / historic district
No

Questions about 61-21 97 Place

Who owns 61-21 97 Place?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 61-21 97 Place have violations?

NYC HPD has no housing violations on record for this property.

Is 61-21 97 Place rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 61-21 97 Place built?

City records list 1956 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.