85-28 Britton Avenue
Queens, NY 11373BBL 4-01514-0001Map
Owner of record: NYC Department Of Education
85-28 Britton Avenue is a school building built in 1930 in Queens, 11373. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 43
- ECB violations
- 107
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 43
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed
Show 33 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 20, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 20, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 20, 2012
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2010 inspection/test
Dec 13, 2011
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 3, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 3, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 3, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 30, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 3, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 24, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 24, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 24, 2009
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 7, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 7, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 7, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 13, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 13, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 13, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 11, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 11, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 11, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 19, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 19, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 19, 2005
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations · 107
- Class - 2
Reissued ecb#35719881y emergency signs at elevator call staions missing defective or non-compliant with section requirements.noted missing emergency signs at cellar elevator#1 and #2.rem:install and/or repair s
Apr 20, 2026 · Penalty $1,562
Active - Class - 2
Reissued ecb#35719879p failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.noted no firestopping at cellar gas meter room an approx 8"x8" penetration in cmu wall at floor l
Apr 20, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.noted smoke doors not closing property at 3rd floor stair g an 1st floor stair i.rem:repair and/or replace.
Apr 20, 2026 · Penalty $1,250
Active - Class - 2
Emergency signs at elevator call stations missing defective or non-compliant with section requirements. cellar level elevators "c" were missing emergency signs and pictorial floor plan for evactuation in the ev
May 9, 2025 · Penalty $625
Active - Class - 1
Failure to maintain building in code-compliant manner. (4)gas powered show blower being stored at cellar level mechanical room next to generator. gas inside the tanks. remove from building immediately. remedy:
May 9, 2025 · Penalty $2,500
Resolve - Class - 2
Reissue #35654846y. failure to maintain building in code-compliant manner. at cellar level gas and electric meter rooms, foundation walls have deteriorating bricks and mortar and corroding declining on ceilings
May 9, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35682399x. failure to maintain building in code-compliant manner: no fire stopping per bc 718.3; 27-345. at cellar meter room an approx. 8"x8" penetration in cmu wall at floor level for new gas pipe, n
May 9, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35682898y. failure to maintain building walls or appurtenances. noted diagnal step crack with seperation at hampton street side 3rdterrace next to exp #3 and 4 corner. remedy: maintain exterior buildin
May 9, 2025 · Penalty $6,250
Active - Class - 2
Reissue #35682896k. failure to maintain building in code-compliant manner: use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted illegal kick stops mounted on rm 106, auditorium exits and 1st
May 9, 2025 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code-compliant manner. throughout school corridors magnetic door holders are defective due to fire alarm being out of service. all cross corridor smoke doors are kept open using
May 9, 2025 · Penalty $1,250
Resolve
Show 40 more ↓
- Class - 2
Exit door not self closing.noted:exterior exit doors t exits#10 & #3 not self closing properly.also boiler room exit door gets stude extremely difficult to open & will not self close.additionally corridor smoke
Jul 1, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.noted at cellar level gas meter room or approx.8"x8" penetration in cmu wall at floor level with no firestopping in pla
Jul 1, 2024 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.noted at cellar level electrical & gas meter rooms,ceilings with corroded metal decking and brick walls having washed out mortar joints.evidence of extensiv
Jul 1, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building wall(s)or appurtenances.noted a vertical step crack with brick separation at the hampton st side 3rd fl terraceexp#3 & 4 corner.rem:maintain exterior building walls.
Jul 1, 2024 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:auditorium stairwell e fireproof self closing doors are equipped with kickdown door s
Jul 1, 2024 · Penalty $625
Resolve - Class - 2
Found laars pncvo500 gas fired water boiler not registered, maintain boiler; register the boiler and submit a certificate of correction
Sep 26, 2023 · Penalty $625
Active - Class - 2
28-301.1 reissue#35561023k-failure to maintain in code-compliant manner.at roof level machine room vertical cracks.rem:comply with code.
Apr 27, 2023 · Penalty $1,250
Resolve - Class - 2
Re-issued #35561024m failure to maintain bldg in code-compliant mannerat time of inspection(4th fl)hallway dors near rm#423 is not working properly & also 1st fl stairs h & g door's not working.remedy:repair &
May 16, 2022 · Penalty $1,562
Resolve - Class - 2
28-301.1 re-issued #35561127p failure to provide ventilation to gas meter rm per 115-6(1968 code).fgc appendix b(b4)2014 code.noted:at cellar gas meter rm w/out ventilation system.provide ventilation as require
May 16, 2022 · Penalty $3,125
Resolve - Class - 2
28-301.1 failure to maintain bldg in code-compliant manner:at time of inspection observed at roof level machine rm vertical cracks/separation of block walls at cellar gas & electric meter rooms,w/cracked brick
May 16, 2022 · Penalty $3,125
Active - Class - 2
Boiler doors open,#1 boiler has cracked chamber,2 low water cut offs on 1-tapping,close open ducts no wood,missing valve on suction line on oil tnk b/4 anti syphon
Jun 2, 2021 · Penalty $625
Active - Class - 2
2-low water cut offs on 1-tapping,boilers doors are open,missing rating plate,valve leaking on boiler
Jun 2, 2021 · Penalty $625
Active - Class - 2
Boiler doors open,missing rating plate,missing insulation on boiler,wiska switch missing on louver #2 blr,cover missing on control
Jun 2, 2021 · Penalty $625
Active - Class - 2
Failure to maintain bldg in code compliant manner.noted:at(roof level)machine room & bulkhead stair d(4th fl) rooms 413 & 423(cellar)gas & electric meter rooms w/having water penetration/damage to walls,ceilin
May 4, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner noted:at(roof level)machine room vertical cracks/separation of block walls at(cellar)gas/ electric meter rooms w/cracked bricks missing mortar ceiling decking
May 4, 2021 · Penalty $625
Active - Class - 2
Failure to maintain bldg in code compliant manner.noted:at(4th fl) hallway doors near rm423(3rd fl)stair f (1st fl)stair h&g doors are in disrepair/racked.remedy:repair &/or replace
May 4, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner use of prohibited door &/or hardware per bc1008.1.8/27-371(j) noted:throughout entire at all levels installed kick door stoppers in various locations.remedy:pr
May 4, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.noted:at(cellar) electric meter room fire stopping missing/none w/holes & openings throughout in various locations.remedy:provide maintain fire stopping
May 4, 2021 · Penalty $1,250
Resolve - Class - 2
28-301.1 failure to provide ventilation to gas meter room per p 115.6 (1968 code),fgc appendix e(e4)2014 code noted:at cellar gas meter roomw/having no ventilation system provided as required.remedy:comply w/no
May 4, 2021 · Penalty $1,250
Resolve - Class - 2
Exit door not self closing. noted:on the 4th fl on gleane st side two of the corridor doors are not closing properly,also on the 1st fl two of the corridor doors are not closing properly. remedy:repair and/or r
May 2, 2019
Resolve - Class - 2
Occupancy contrary to that allowed by the certificate of occupancy or to bldg dept records. reissue nov #35085627r.noted:storage room 410,310,210,127,117,and 110 have been converted and are being used as office
Oct 18, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner:provide required corridor width per bc1016.2;27-369(partial obstruction).reissue violation#35147089j.noted:@various locations throughout each flr 1,2,3,4th flr
Oct 18, 2016
Resolve - Class - 2
Re-issue nov#35085629k.failure to maintain bldg in code-complaint manner:no fire stopping as per bc 712.3,27-345.rem:
Sep 2, 2015
Resolve - Class - 2
Reissue nov#35085626p.failure to maintain bldg in code compliant manner:provide required corridor width per bc 1016.2;27-369.@ various location throughout public corridors all levels storage of classrm & office
Sep 2, 2015
Resolve - Class - 2
Reissue nov#35085625n.failure to maintain bldg wall(s)or appurtenances.water penetrating bldg envelope.peneration(water damage)observed @ expansion joint in bsmt corridor adjoing auditorium exit door,@ 4th sty
Sep 2, 2015
Resolve - Class - 2
Reissue nov#35085630h.failure to maintain bldg in code-compliant manner.@ cellar generator rm foundation wall spalling w/ loose displaced mortar joints.rem:comply w/ notice of violation.
Sep 2, 2015
Resolve - Class - 2
Reissue nov#35085627r.occupancy contrary to that allowed by the cert of occupancy or bldg dept records.@ rms designated 110,117,127,210,310,410 occupied as offices/classrms w/o adeqaute natural light or ventila
Sep 2, 2015
Resolve - Class - 2
Re-issue # 35023777z. storage of combustable tables, chairs, carts, books in corridors and accessive combustable art work on walls. remedy: remove all obstructions and combustables from corridors.
Feb 18, 2014
Resolve - Class - 2
Re-issue # 35023776r. occupancy contrary storage rooms at 110,117,127,210,310,410 being used as office classes. remedy: discontinue illegal use.
Feb 18, 2014
Resolve - Class - 2
Doors racked at 1st floor stair i, 2nd floor stair b & rooms 118 & 203. remedy: repair or replace doors.
Feb 18, 2014
Resolve - Class - 2
Approx 1'x 1' opening in wall of gas meter room at vent duct with no fire stopping. remedy: provide fire stopping.
Feb 18, 2014
Resolve - Class - 2
Interior side of foundation wall in cellar generator room is spalling with missing mortar. remedy: make necessary repairs.
Feb 18, 2014
Resolve - Class - 2
Re-issue # 35023778k. water penetrating at auditorium (basement level) causing plaster damage to ceiling. remedy: make necessary repairs.
Feb 18, 2014
Resolve - Class - 2
Reissue 34949634y water penetrating building envelope at basement auditorium intersection of new and old school area. rmdy: repair defect noted maintain weatherproof integrity of building envelope.
Jul 15, 2013
Resolve - Class - 2
Area way drain clogged w/standing (pooling) water present. at area wayadjacent to boiler room fresh air intake louvers. rmdy: repair defect noted.
Jul 15, 2013
Resolve - Class - 2
Reissue 34949636h storage rooms occupied as offices/classrooms without adequate natural light or ventilation. at 1st story rooms 110,117 & 127; at 2nd story-room 210; at 3rd story-room 310; at 4th story-room 4
Jul 15, 2013
Resolve - Class - 2
Reissue vio #34949635x combustible items obstructing public corridors at 1st,2nd,34d,4th stories various locations throughout. rmdy: remove items from public corridors maintain full corridor width in a code-com
Jul 15, 2013
Resolve - Class - 1
Sec. 3314.9 supported scaffold does not meet code specifications. noted: at time of inspection observed loose netting on supported scaffold at all exposure's on job site. make safe. remedy: conform to code spec
Oct 29, 2012
Resolve - Class - 2
Water penetration at auditorium over stage left exit rain water penetration at new and old school joint area rem: water proof exterior
Mar 30, 2012
Resolve - Class - 2
Occupancy contrary at 3fl storage room converted to and used as office w/ inadequate fresh air rem: discontinue illegal use
Mar 30, 2012
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1930
- Floors
- 5
- Residential units
- —
- Building area
- 163,000 ft²
- Lot area
- 40,000 ft²
- Zoning
- R4
- Community board
- 404
- Council district
- 25
- Block / lot
- 1514 / 1
- Assessed value
- $14,233,500
- Landmark / historic district
- No
Questions about 85-28 Britton Avenue
Who owns 85-28 Britton Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 85-28 Britton Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 85-28 Britton Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 85-28 Britton Avenue built?
City records list 1930 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.