34-25 82 Street
Queens, NY 11372BBL 4-01443-0019Map
Owner of record: NYC Department Of Education
34-25 82 Street is a school building built in 1998 in Queens, 11372. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 42
- ECB violations
- 41
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 42
- Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 21, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 21, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed
Show 32 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Jun 8, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 8, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 13, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 13, 2015
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 26, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 26, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 4, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 4, 2008
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 17, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 13, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 9, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 1, 2004
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 1, 2004
Dob violation - resolved - Elevator elevatorrequired
4p10310
Sep 12, 2002
Dob violation - resolved - Elevator elevatorrequired
4p10311
Sep 12, 2002
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Construction other optional
Rm
Jul 10, 1990
Vw*-violation - work w/o permit dismissed - Public assembly none
Pa-public assembly none
Jun 27, 1990
Dob violation - dismissed - Public assembly none
Pa-public assembly none
Jun 27, 1990
Dob violation - dismissed
ECB violations · 41
- Class - 2
Exit door not self-closing properly. at the time of inspection at cellar level stairway b" one exit door, at first floor one exit door near rm-108, one exit door main entrance inside, one corridor exit door nea
Mar 26, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted at main entrance exit 1 exterior soffit over doorway loose sheetrock. remedy: repair and/or replace soffit.
Apr 28, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner:provide required corridor width per bc1016.2:27-369 noted:hallway to electrical rm,secondary water rm,&emergency generator rm partially obstructed by excessive s
Apr 27, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code-compliant manner:note: in elc-closet on cl storage of combustible materials.rem:repat and/or replace.
Apr 3, 2019
Resolve - Class - 2
Fail to maintain bldg in code-compliant manner: use prohibited door and/or harware per bc1008.1.8; 27-371(j).note:@sub-cellar rooms sc-4,sc-9 and book storage closet have kick stop.rem:provide legal harware.
Apr 3, 2019
Resolve - Class - 2
28-301.1. unlawful display of artwork in corridor greater than 20% perfdny 2008 code; fc 803.3.2. note: on all floors artwork approx. 65% ofcorridor walls. remedy: comply with notice of violation.
Apr 3, 2019
Resolve - Class - 2
Re-issued 35329036n. exit door not self closing @ 1st fl exit #2, 2nd fl exit #2, corridor door outside of lunch & cafeteria (front) door self closing. remedy: repair/replace.
Apr 3, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. no fire stopping per bc 712.3, 27-345. observed several room no fire stopping. 4th flelectrical and telecom room, 3rd floor electricl room, at 2nd floor bi
Apr 13, 2018
Resolve - Class - 2
Exit door not self closing. observed at 1st floor exit 2 rmdy: repair or replace door.
Apr 13, 2018
Resolve - Class - 2
Bc 3009.1 3-m-07-otis elevator 056001 failed to provide caution tape accross entrance of elevator while device is (being) servied on 10/12/17.
Oct 13, 2017
Resolve
Show 31 more ↓
- Class - 1
05l11)zone lock restrictor.
Oct 13, 2017
Resolve - Class - 1
97-b-07 otis elevator license #056001 failed to properly safe guard device 4p10311 while working on the device on 10-12-2017 this caused a teached @the location to fail into the cab & break her arm during the c
Oct 13, 2017 · Penalty $25,000
Active - Class - 2
Failure to maintain bldg in code compliant manner. storage of furniture & objects inside gas meter room @ cellar. rem: remove/no storage in gas meter room.
May 2, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner provide required corridor width per bc 1016.2. 4th,3rd,2nd,1st flr c level corridors there are plastic bins,desks,chairs,computer equipment,objects reducing cor
May 2, 2017
Resolve - Class - 2
Reissue #35085378p.failure to maintain corridor width.note:excessive storage of desks storage lockers chairs + misc(terms)+use of corridors for class instruction.on floor all reducing corridor width.rem:remove
Feb 12, 2015
Resolve - Class - 2
Corridors at cellar,2nd,3rd & 4th floors are obstructed by storage of tables,chairs & carts, also excessive combustable art works on corridor walls. remedy: remove all storage & excessive combustables from fir
Feb 11, 2014
Resolve - Class - 2
Kick down door stops installed on fire doors to gym, cafeteria and various other doors. remedy: remove kick stops.
Feb 11, 2014
Resolve - Class - 2
Reissue 34949616k unauthorized storage at cellar: 1-gas meter room; 2-water pump room. rmdy: remove all stored items from mechanical rooms.
Jul 15, 2013
Resolve - Class - 2
Sub cellar boiler room above elec panel embp missing fire stopping. rmdy: provide and maintain fire stopping.
Jul 15, 2013
Resolve - Class - 2
Unauthorized storage at cellar gas meter room storage of various maintenance equipment supplies rem: remove all items maintain gas meter service room storage free
Mar 27, 2012
Resolve - Class - 2
Reissue #34906552k partial corridor obstruction at cellar 2nd 3rd & 4th w/ tables desk chairs rolling carts rem: remove all items maintain fire corridors width clear
Mar 27, 2012
Resolve - Class - 2
67x10. 67-x-10-in car emergency phone.
Jan 3, 2012
Resolve - Class - 2
Re- 34848002m. the corrior hallway is partially obstructed by tables &chairs which are being used as a one to one teaching session located on the 2nd,3rd,4th flr level. remedy: remove obstruction.
Apr 11, 2011
Resolve - Class - 2
Failure to maintain observed: at floors 3 & 2,corridor smoke doors held open by floor chocks due to defective magnetic hold opens tied into fire alarm system. smoke doors at 1fl held open w/chocks.
May 12, 2010
Resolve - Class - 2
Sec. 28-301.1 failure to maintain egress clear & unobstructed observed: at corridors on fls 4 & 3,storage of desks,chairs,tables & rolling carts. remedy: remove obstruction,provide clear egress.
May 12, 2010
Resolve - Non-hazardous
Failure to maintain building defects noted roof leaks at fan room b fan room a chiller room leaks also noted first floor corridor near office 125 has a roof leak from play area above.remedy:maintain roof all ne
Mar 30, 2005
Resolve - Non-hazardous
Failure to maintain building defects noted plaster wall cracks at third floor corridor boys & girls bathroom on rear wall horizontal cracks near ceiling remedy:maintain wall make all necessary repairs
Mar 30, 2005
Resolve - Non-hazardous
Failure to maintain building defects noted cracked masonary walls at:roof fan room a near stairwell cellar electrical service room has a 5 foot vertical crack above entry door sub cellar gymnasium has a 10 foot
Mar 30, 2005
Resolve - Non-hazardous
Failure to maintain exterior building wall defects noted main entry exterior soffit above doors has 2 cracks also noted 83 street side entryyard brick pillac on left side near entry doors has a vertical crack
Mar 30, 2005
Resolve - Non-hazardous
Failure to maintain building defect noted:stairwell a landing between 4 floor & fan room window has water penetration remedy:maintain buildijng make all necessary repairs
Mar 30, 2005
Resolve - Non-hazardous
Failure to maintain building defect noted second floor classroom 216 double hung window next to column lower sash is inoperable screwed shotsash too small for window frame.remedy:replace window sash
Mar 30, 2005
Resolve - Non-hazardous
Failure to maintain exterior building wall. defect: loose (4 of 8 total) decorative cast stone globes sitting on parapet wall coping over 4 floor (82 sheet facade). remedy: repair defect.
Jan 10, 2003
Resolve - Non-hazardous
Failure to provide 3 inch minimum high alphabetic letter of identification (not number) for elevator bank on floor 1 to 5. remedy: provide identification as per local law 16/84.
Apr 16, 2002
Resolve - Non-hazardous
Failure to maintain. upon inspection of the above address. gym nasium boy's bathroom ceiling has broken & cracked plaster. (approx 3'-5' long) remedy: make all repails.
Apr 10, 2001
Resolve - Non-hazardous
Work without a permit. expired sidewalk shed. permit number 400954035 expired 12-31-98. obtain a current permit.
Oct 25, 1999 · Penalty $500
Resolve - Hazardous
Failure to remove glass from bldg before commencement of demoliton work. stop order. remedy: stop all work. remove all glass before starting demolition work.
Mar 12, 1998 · Penalty $500
Resolve - Hazardous
Failure to provide 24 hr notice before commencement of demolition workremedy: notify the dept of bldgs 24 hours prior to the commencement ofdemolition work as required by dept of bldgs requirements.
Mar 12, 1998
Resolve - Hazardous
Failure to carry out demolition operations in a safe & proper manner. in that demolition debris has been accumulating outside the bldg. thedebris was from the parapet walls at the 2nd & 4th fl.
Mar 12, 1998 · Penalty $2,000
Resolve - Non-hazardous
74u.
Sep 29, 1993
Resolve - Non-hazardous
Catering&bonquet hall with in occupant load 718 person from c/o and permit require a system of automatic sprinkler system installed remedy:intall sprinkler system or discontinue illegal use forthwith
Apr 29, 1991 · Penalty $115
Resolve - Non-hazardous
Established a catering&banquet hall with an occupant load of 318 persons from c/o and persut requiring a systems of auto-matic sprinkler systems installed remedy:install sprinkler system or discontinue illegal
Apr 25, 1991 · Penalty $115
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1998
- Floors
- 4
- Residential units
- —
- Building area
- 93,899 ft²
- Lot area
- 22,000 ft²
- Zoning
- R7-1
- Community board
- 403
- Council district
- 25
- Block / lot
- 1443 / 19
- Assessed value
- $19,163,700
- Landmark / historic district
- Jackson Heights Historic District
Questions about 34-25 82 Street
Who owns 34-25 82 Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 34-25 82 Street have violations?
NYC HPD has no housing violations on record for this property.