38-43 12 Street
Queens, NY 11101BBL 4-00472-0642Map
Owner of record: 12 Street Hotel, LLC
38-43 12 Street is a hotel built in 2019 in Queens, 11101. The owner of record is 12 Street Hotel, LLC. HPD has recorded 18 housing violations here, most recently on May 8, 2026.
- HPD violations
- 18
- DOB violations
- 25
- ECB violations
- 31
- HPD complaints
- 10
What to know
No open immediately-hazardous violations among recent records.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 18
- ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
May 8, 2026
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Jun 16, 2025
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 29, 2024
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 17, 2024
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Oct 22, 2018
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 30, 2017
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 16, 2016
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Oct 14, 2015
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Feb 25, 2015
Closed — Violation closed - BHazardous
Repair or replace the smoke detector missing in the entire apartment located at apt 2, 2nd story
Feb 12, 2007 · Apt 2
Closed — Violation closed
Show 8 more ↓
- BHazardous
Provide an approved and operational carbon monoxide detecting device, installed in accordance with applicable law and rules. in the entire apartment located at apt 2, 2nd story
Feb 12, 2007 · Apt 2
Closed — Violation closed - BHazardous
Provide an approved and operational carbon monoxide detecting device, installed in accordance with applicable law and rules. located at apt 3, 3rd story, 1st apartment from north at east
Apr 8, 2006 · Apt 3
Closed — Violation closed - BHazardous
Repair or replace the smoke detector missing located at apt 3, 3rd story, 1st apartment from north at east
Apr 8, 2006 · Apt 3
Closed — Violation closed - ANon-hazardous
Paint with light colored paint to the satisfaction of this department , ceiling in the bathroom located at apt 3, 3rd story, 1st apartment from north at east
Apr 8, 2006 · Apt 3
Closed — Violation closed - ANon-hazardous
Paint metal in accordance with dept. regulation , 1st radiator from east at south wall, ceiling in the bathroom located at apt 3, 3rd story, 1st apartment from north at east
Apr 8, 2006 · Apt 3
Closed — Violation closed - ANon-hazardous
Properly repair with similar material the broken or defective kitchen base wood cabinet. in the kitchen located at apt 3, 3rd story, 1st apartment from north at east
Apr 8, 2006 · Apt 3
Closed — Violation closed - BHazardous
Properly repair with similar material the broken or defective ceramic floor tile. in the bathroom located at apt 3, 3rd story, 1st apartment from north at east
Apr 8, 2006 · Apt 3
Closed — Violation closed - CImmediately hazardous
Correct the lead-based paint hazard - paint that tested positive for lead content and that is peeling or on a deteriorated subsurface - using work practices set forth in 28 rcny §11-06(b)(2) north wall, south wall, east wall, 1st window frame from north at east wall, 2nd window frame from north at east wall in the 1st room from east at north located at apt 3, 3rd story, 1st apartment from north at east
Apr 8, 2006 · Apt 3
Closed — Violation closed
DOB building violations · 25
- Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Nov 2, 2023
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2023
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 2, 2023
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Feb 2, 2023
Dob violation - dismissed - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Dec 1, 2022
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Nov 2, 2022
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2022
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jun 1, 2022
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Feb 2, 2022
Dob violation - dismissed - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Dec 1, 2021
Dob violation - dismissed
Show 15 more ↓
- Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Nov 2, 2021
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2021
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jul 7, 2021
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jun 2, 2021
Dob violation - dismissed - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Apr 29, 2021
Dob violation - dismissed - Plumbing none
I observed unapproved material installed in the gravity tank on the roof at 38-43 12th st. st. a bag pvc liner, which is prohibited. tank shall comply with nfpa 22, building code 903 & 905, and 28-113.2.2. of nyc admin code..
Apr 12, 2021
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Feb 2, 2021
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Nov 2, 2020
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2020
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 2, 2020
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Sep 19, 2019
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jul 9, 2019
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Apr 3, 2019
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Apr 3, 2019
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Dec 27, 2017
Dob violation - dismissed
ECB violations · 31
- Class - 2
Observed on the roof fire pump gage is reading almost at zero. on the 9th floor in mechanical room hot water heater exhausted vent not fully connected. also, on the ground floor using prohibited material on exh
Sep 3, 2025
Resolve - Class - 1
I observed in the hallways the failure to install tamper resistant outlets as required by ll 39/2015. this si an immediate shock hazard.; ll39/2015, comply with ec code; install tamer resistant outlets.
Sep 11, 2024 · Penalty $1,630
Resolve - Class - 1
Observed improper ventilation in the mechanical room located in the cellar. the mechanical room which houses a gas fired water heater is being vented to the common space not outside., repair and/replace
Sep 11, 2024 · Penalty $1,280
Resolve - Class - 2
Observed active water leak in the water meter room located in cellar, as per 102.3 of the plumbing code installations, both existing and new, and parts thereof shall be maintained in proper operating condition
Sep 11, 2024
Resolve - Class - 2
I observed on the 9th and 1st floors the failure to install a remote shutdown for the gasfired units in the mechanical rooms. as per mc 1006.8.1 a remote shutdown shall be installed at the point of egress.; mc
Sep 11, 2024
Resolve - Class - 1
I observed the main electrical room with excessive storage of furniture, building equipment, appliances and materials. this is an immediate safety and fire hazard., comply with ec; remove all non-electrical equ
Sep 11, 2024 · Penalty $1,200
Resolve - Class - 2
I observed on the roof level in the elevator and fire pump rooms the unpermitted use of emt through concrete. as per ec, comply with ec; use emt as permitted.
Sep 11, 2024 · Penalty $800
Resolve - Class - 2
Observed throughout building temporary caps( red) on the standpipe hose valve. as per 3308 of the new york fire code states temporary coverings shall be immediately removed upon the completion of the constructi
Sep 11, 2024
Active - Class - 1
Gas leak found on elbow fitting on gas pipe. con-ed tech found the leak and shut the gas to the appliance. as per 102.3 of the plumbing code installations, both existing and new, and parts thereof shall be main
Sep 11, 2024 · Penalty $1,250
Resolve - Class - 2
Unpermitted foam used at fire-stop to seal hole penetrations located throughout building., provide/maintain fire stopping
Sep 11, 2024
Active
Show 21 more ↓
- Class - 1
Observed excessive combustible storage in the mechanical room located on the 9th floor which houses 3 gas fired water heaters. . also the excessive combustible storage is making the workspace inaccessible., rep
Sep 11, 2024 · Penalty $1,250
Resolve - Class - 1
I observed on the roof area where the gravity tank is installed. inside the tank. unapprove material installed a bag pvc liner which is prohibited. tank shall comply with nfpa 22, building code 903 & 905, and 2
Apr 12, 2021 · Penalty $3,125
Resolve - Class - 2
The exterior walls on exposures #1 & #3 from 1st. to 9th. floor were installed without 2" rigid insulation contrary to exterior wall details on pages a-301.01 501.01 & a-506.01. it is permitted to perform work
Feb 26, 2020 · Penalty $3,125
Resolve - Class - 2
Failure to safeguard all persons and properties affected by construc tion operations. at time of inspection on a 9story new building observed at exp4 a plywood gate in place for access to adjacent property. th
Jul 18, 2019 · Penalty $5,000
Resolve - Class - 1
Work not does not conform to approved documents/plans. at the time of inspection of a 9 story building active job site competent person varindergit singh present i observed hoist located at exp 1 in operat
May 23, 2019 · Penalty $2,500
Resolve - Class - 1
Bc-3303.8 standpipe not in state of readiness. at time of inspection on an active jobsite of a 9 story building,topped off at roof level,it was observed that standpipe was stopped at the 7 fl permanent stairs w
Apr 20, 2019 · Penalty $2,500
Resolve - Class - 2
(pb)signs. sidewalk shed parapet panel sign not provided or not compliance w/ section. noted:at time of inspection i observed sws in place w/ shed missing a job sign in shed parapet. remedy: comply with code
Jan 17, 2019
Resolve - Class - 2
Jobsite fence not constructed or maintained pursuant to subsection. atthe time of my inspection of a proposed 9 story building i observed fencing that is inadequate. it is not solid has loose boards and missing
Jan 17, 2019
Resolve - Class - 2
Daily inspection report. a written record of such inspections shall bemaintained by the contractor. noted:at time of inspection i observed sws in place w/o a written record of the daily inspection on site/avail
Jan 17, 2019
Resolve - Class - 1
Construction superintendent failed to perform duties as per rule. at time of inspection i observed on construction site where work does not conform to plan, missing guardrail/toe board, inadequate installation
Jan 11, 2019
Resolve - Class - 1
Work contrary to drawings. at time of inspection, i observed shear wall platforms located at exp #2 & #4 exterior. upon review of these platforms, i observed that the platform was not constructed as per the eng
Jan 11, 2019 · Penalty $2,500
Resolve - Class - 1
Failure to institute/maintain safety equipment measures or temporary construction guardrails/no toe boards. at time of inspection, i observed inadequate guardrail installation. guardrail was installed and suppo
Jan 11, 2019 · Penalty $2,500
Resolve - Class - 1
Bc3305.3.6.1.1 shores. at time of inspection, i observed shores/reshores at the perimeter of the jobsite not adequately secured and tied down. several shores were not secured whatsoever and others were tied dow
Jan 11, 2019 · Penalty $2,500
Resolve - Class - 1
No design drawings. at time of inspection, i observed temporary platforms located on the elevator shafts. upon request for design drawings on the platform none were provided. failure to provide design drawings
Jan 11, 2019 · Penalty $2,500
Resolve - Class - 2
Failed to perform proper concrete washout. at time of inspection, i observed excessive concrete washout run-off on the street side curb of the construction site. showing that contractor failed to perform proper
Jan 11, 2019
Resolve - Class - 1
Bc3301.4 inspection of temporary construction equipment (safety strap). at time of inspection, i observed an active construction site where construction competent person failed to provide concrete embedded safe
Jan 11, 2019 · Penalty $2,500
Resolve - Class - 1
Failure to provide protection at side of excavation.at the time of inspection a 4' to 8'ft deep excavation was observed along exp#2 without protection.no sharing or angle of repose provided to prevent the side
Sep 5, 2018 · Penalty $5,000
Resolve - Class - 2
Work does not conform to approved conform to the approved soe & fo plan.the approved soe plan shows shoring/piles with logging at exp# 1,2, & 4 and soil slaped 1:1 at exp#3 the contractor did not install the sh
Sep 5, 2018 · Penalty $625
Resolve - Class - 1
Failure to monitor adjoining structures for movement in all directioins during excavation underpining activity.at the time of inspection it was observd that the contractor excavated 4' to 8ft deep along the adj
Sep 5, 2018 · Penalty $2,500
Resolve - Class - 2
Construction superintendent failed to perform duties as per code;at the time of inspection the following was observed under the supervision of c.s.harjinder singh.super was mot on site a log book is maintained
Sep 5, 2018 · Penalty $2,500
Resolve - Class - 1
Work without premit.at the time of inspection observed site had job fence up fence was blue in color had no viewing prots and research in bis indicated no valid permits are active for this site.stop all work on
Sep 30, 2017 · Penalty $4,000
Resolve
Complaints
- Unsanitary condition
Mold
Mar 28, 2026 · Apt 701
Close - Safety
Window guard broken/missing
Sep 30, 2023 · Apt 706
Close - Safety
Window guard broken/missing
Jul 19, 2023 · Apt 503
Close - Heating
Heat related
Feb 8, 2007 · Apt 2
Close - Heating
Heat related
Feb 8, 2007 · Apt 3FL
Close - Nonconst
Vermin
Apr 2, 2006 · Apt 3
Close - General
Windows
Apr 2, 2006 · Apt 3
Close - Plumbing
Bathtub/shower
Apr 2, 2006 · Apt 3
Close - General
Cabinet
Apr 2, 2006 · Apt 3
Close - General
Floor
Apr 2, 2006 · Apt 3
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Hotel (H3)
- Year built
- 2019
- Floors
- 9
- Residential units
- —
- Building area
- 30,802 ft²
- Lot area
- 5,160 ft²
- Zoning
- M1-3
- Community board
- 401
- Council district
- 26
- Block / lot
- 472 / 642
- Assessed value
- $3,266,550
- Landmark / historic district
- No
HPD registration #434234, last renewed Aug 27, 2025.
Questions about 38-43 12 Street
Who owns 38-43 12 Street?
The owner of record in NYC Department of City Planning PLUTO data is 12 Street Hotel, LLC.
Does 38-43 12 Street have violations?
Yes. NYC HPD has recorded 18 housing violations at this property.
Is 38-43 12 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 38-43 12 Street built?
City records list 2019 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.