37-02 37 Street
Queens, NY 11101BBL 4-00228-0020Map
Owner of record: NYC Department Of Education
37-02 37 Street is a school building built in 1931 in Queens, 11101. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 41
- ECB violations
- 79
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 41
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 24, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 24, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed
Show 31 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 19, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 19, 2015
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 13, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 13, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 13, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 13, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 20, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 10, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 10, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 8, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 8, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 3, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed
ECB violations · 79
- Class - 2
Reissue#35725316m failure to maintain building in code-compliant manner.noted:interior fpsc doors do not self-close properly when tested at 4th flr-staircase y.3rd flr-staircase x.1st flr-main entrance interior
Jul 17, 2026 · Penalty $3,125
Active - Class - 2
Class 2 rts:failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the only device in the section of the building is found to be out of serv
Oct 20, 2025 · Penalty $625
Active - Class - 2
Reissue: 35682875l-failure to maintain building in code-compliant manner. self-closing doors not working properly at 3rd floor stair a, 2nd fl. stair x, corridor smoke doors #260e. remedy: comply with code.
Sep 11, 2025 · Penalty $3,125
Active - Class - 2
Reissue: 35682876n-failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1026.1; 27-381. 14 emergency lights not working at gym, exit #16, au
Sep 11, 2025 · Penalty $3,125
Resolve - Class - 2
Reissue: 35682877p-failure to maintain building in code-compliant manner. stair c 2nd fl. and 1st floor and landing, outer panels are cracked. remedy: comply with code.
Sep 11, 2025 · Penalty $3,125
Resolve - Class - 2
Reissue #35674992k. failure to maintain building in code-compliant manner. noted interior fireproof self closing doors not working properly.at 3rd fl stair a, 2nd fl stair x and corridor smoke doors #260e, 1st
Jun 21, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted exterior steps at exit #3, with spalling concrete and missing chunks at landing. remedy: repair and/or replace.
Jun 18, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted at auditorium left stage exit path destructed by storage at furniture and equipment. remedy: comply with motive of violation.
Jun 18, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner: use of prohibted door and/or hardware per bc 1008.1.8; 27-371(j). noted illegal kick down door stops equipped on classroom doors #407, 425 and 416. remedy:
Jun 18, 2024 · Penalty $625
Resolve - Class - 2
Exit door not self-closing. noted exterior doors at exits #15, #1 and #0, mentioned are rusted, rub a frame as saddle, difficult to open without excessive force and not self closing. remedy: repair/replace door
Jun 18, 2024 · Penalty $625
Resolve
Show 40 more ↓
- Class - 2
Reissue #35674990r. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted approx. 14 emergency lights not working when
Jun 18, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue #35674988h. failure to maintain building in code-compliant manner. noted at stair c 2nd and 1st floor midlanding, outer window panelis cracked. remedy: repair and/or replace.
Jun 18, 2024 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at auditorium at stage,both left and right exit doors were obstructed by boxes,chairs,trash cans,all piled up infront of the exit doors.rem:remove obs
May 18, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35578203z failure to maintain building in code-compliant manner.noted:at 2nd floor midlanding,outer window pome cracked.rem:repair or/replace.
May 18, 2023 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at cellar next to electrical room,gas powered snow blower and vacume machine being stored.rem:comply with notice of violation.
May 18, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at exit 15stair c one of four door with broken door closer.rem:repair/replace.
May 18, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridor per bc 1006.1;27-381.noted:at gym,exit 16 and at auditorium 6 emergency exit lighting found inoper
May 18, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35578201p failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc1006.1;27-381.noted observed during inspection of emergency lights,hallw
May 26, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35578202r failure to maintain building in code compliant manner.noted observed during inspection of roof level bulkhead,stair z peeling/spalling plaster due ro water penetration of wall and ceiling.reme
May 26, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner.no fire stoppingper bc712.3;27-345.noted observed during inspection of cellar level electrical room opening in wall approx 1ft by 1ft with conduit pipe goin
May 26, 2022 · Penalty $1,250
Resolve - Class - 1
Unsafe storage of combustible materials and equipment-noted,at 1st fl room#148,gas powered snow blowers,grass trimmers,lawn mowers stored.(all gas powered) remedy:maintain storage in compliance w/ fire code
Oct 8, 2021 · Penalty $6,250
Resolve - Class - 1
Unsafe storage of combustible material and equipment.noted:observed at cellar storage room several combustible equipment such as snow blowers,lawn mowers, grass trimmers, etc stored.
Aug 9, 2021 · Penalty $6,250
Resolve - Class - 1
Unsafe storage of combustible3 material&equipment.noted:observed@cellar level,snowblowers,lawnmower,grass trimmers (all gas powered).all being stored w/i bldg cellar.maintain storage in compliance w/fire code.
Jun 8, 2021 · Penalty $2,500
Resolve - Class - 2
Reissued35498248m failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:observed@1fl,existing emergency lights labeled8&9 werent oper
Jun 8, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner noted:observed@stairzbulkhead spalling missing plaster of walls,some have fallen off wall,due to water penetration.repair &/or replace.
Jun 8, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner:noted:observed outer window pane@2fl midlanding cracked.repair &/or replace.
Jun 8, 2021 · Penalty $625
Resolve - Class - 2
Control piping has wrong material on pigtails, correct violating condition and submit a certificate of correction
Jun 3, 2021 · Penalty $625
Resolve - Class - 2
Control piping on pigtails wrong material, correct violating condition and submit a certificate of correction
Jun 3, 2021 · Penalty $625
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm, and perf
May 24, 2021 · Penalty $1,250
Active - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm, and perf
May 24, 2021 · Penalty $1,250
Active - Class - 2
Re-issue #35447856x failure to maintain bldg in code compliant manner:illumination for exits,exits discharges & public corridors per bc1006.1,27-381.noted: on the 1st fl auditorium,2 of the emergency lights wer
Jun 30, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: leak(ceiling)at cafeteria due toi defective roof. remedy: make necessary repairs.
Aug 19, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: atauditorium 2 exit emergency lighting imperative.
Aug 19, 2019 · Penalty $625
Resolve - Class - 2
Reissue:35222150r exit doors not self closing. exit doors not self closing at following locations 4 floor at roof, exit x on second floorrmdy: repair/replace doors.
Jul 18, 2017
Resolve - Class - 2
Reissue:35093251h exit door not self closing. 2t flr vestibule exit (1,2,3) 2nd flr stair (b,c,x) 3rd floor stairs (b,c,x,y) 4 flr near rm4607z. rmdy: repair/replace.
Jul 18, 2017
Resolve - Class - 2
Reissue:35129477m failure to maintain building in code compliant manner. exit doors defective not opening/closing properly at stair (z)4 floor, stair(y) 3rd flr, 1 floor room 203 also cafeteria doors. rmdy
Jul 18, 2017
Resolve - Class - 2
Reissue 35129477m exit door does not self closing. the exit door to the roof is not closin,also the doors near exit 2 staircase is not closing properly also the door near exit x on the seecond flr is not closin
Dec 5, 2016
Resolve - Class - 2
Reissue #35093251h failure to maintain bldg in code compliant manner.note:exit doors defective not opening + closing properly locations:stair z-4th floor 2 doors.stair y -3rd fl 1 door,room #203 1 door cafeteri
Jul 20, 2015
Resolve - Class - 2
Work w/o a permit:work noted @ cellar"pipe storage room".installed full height partition,creating an "office".installed 220c electrical for use of 3d printer & electrical outlet & lighting in "office area".rem:
Mar 14, 2014
Resolve - Class - 2
Reissue ecb #34932771j.failure to maintain bldg wall(s)or appurtenances(1)bulkhead "x"&"z" have moisture penetrations & walls have become porous.(2)new bldg roof has leakage @ penetrations.rem:waterproof bulkhe
Mar 14, 2014
Resolve - Class - 2
Reissue 35023762x.exit doors not self closing:1st fl:vestibule doors exit 1,2&3;2nd fl.stairs "b","c","x" & "y";3rd fl:doors next to rm311,stairs "b","c","x"&"y" 4th fl:doors next to rm 460e;bulkhead doors @ st
Mar 14, 2014
Resolve - Class - 2
Failure to maintain bldg in code compliant manner;lack of emergency lighting for exits,exit discharges & public corridors oer bc 1006.1;27-542.emergency lighting in auditorium needs bulb replacement @ several l
Mar 14, 2014
Resolve - Class - 2
Occupancy contrary to that allowed by cert of occupancy or bldg dept of records.noted @ cellar level:"pipe storage room"is now being used asa office space & shop area w/installation of full height partition w/d
Mar 14, 2014
Resolve - Class - 1
Failure to maintain bldg in code-compliant manner.@ gym ceiling:diffuser @ vent hanging & not secure & in danger of falling.rem:repair &/or replace immediately.
Mar 13, 2014
Resolve - Class - 2
Doors not closing. at 1st story stair c at 2nd story stairs b,c,x,y (up), cafeteria exit doors to corridor at 3rd story stairs b,c,x,y & zat 4th story stairs x ad y...remedy: repair and/or replace doors noted
Jul 3, 2013
Resolve - Class - 2
Reissue 34932774p no fire stopping. at basement electric panel room conduit penetrations not fire stopped. rmdy: provide firestopping.
Jul 3, 2013
Resolve - Class - 2
Defective doors at 2nd floor stairway c and x; doors not properly self-closing. remedy: repair and/or replace so doors properly self-close.
Feb 9, 2012
Resolve - Class - 2
Unauthorized storage at 3rd floor room 348 electric service room, storage of various school furniture and supplies. remedy: remove all items, maintain service room clear.
Feb 9, 2012
Resolve - Class - 2
Moisture penetration at stairway z bulkhead; the exterior walls have become porous allowing moisture to penetrate into bulkhead walls. remedy: waterproof exterior walls.
Feb 9, 2012
Resolve - Class - 2
Partial corridor obstruction at 2nd floor corridor adjacent to room 214, partial obstruction with table, rolling cart, cardboard boxes & other combustible items.remedy:remove all items;maintain corridor w/clear
Feb 9, 2012
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1931
- Floors
- 4
- Residential units
- —
- Building area
- 145,872 ft²
- Lot area
- 54,000 ft²
- Zoning
- R5
- Community board
- 402
- Council district
- 26
- Block / lot
- 228 / 20
- Assessed value
- $19,440,000
- Landmark / historic district
- No
Questions about 37-02 37 Street
Who owns 37-02 37 Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 37-02 37 Street have violations?
NYC HPD has no housing violations on record for this property.
Is 37-02 37 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 37-02 37 Street built?
City records list 1931 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.