37-02 37 Street

Queens, NY 11101BBL 4-00228-0020Map

Owner of record: NYC Department Of Education

37-02 37 Street is a school building built in 1931 in Queens, 11101. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
41
ECB violations
79
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 41

  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 24, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 24, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
Show 31 more ↓
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 19, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 19, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 13, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 13, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 20, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 10, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 10, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 8, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 8, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 3, 2006

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed

ECB violations · 79

  • Class - 2

    Reissue#35725316m failure to maintain building in code-compliant manner.noted:interior fpsc doors do not self-close properly when tested at 4th flr-staircase y.3rd flr-staircase x.1st flr-main entrance interior

    Jul 17, 2026 · Penalty $3,125

    Active
  • Class - 2

    Class 2 rts:failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the only device in the section of the building is found to be out of serv

    Oct 20, 2025 · Penalty $625

    Active
  • Class - 2

    Reissue: 35682875l-failure to maintain building in code-compliant manner. self-closing doors not working properly at 3rd floor stair a, 2nd fl. stair x, corridor smoke doors #260e. remedy: comply with code.

    Sep 11, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35682876n-failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1026.1; 27-381. 14 emergency lights not working at gym, exit #16, au

    Sep 11, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue: 35682877p-failure to maintain building in code-compliant manner. stair c 2nd fl. and 1st floor and landing, outer panels are cracked. remedy: comply with code.

    Sep 11, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue #35674992k. failure to maintain building in code-compliant manner. noted interior fireproof self closing doors not working properly.at 3rd fl stair a, 2nd fl stair x and corridor smoke doors #260e, 1st

    Jun 21, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted exterior steps at exit #3, with spalling concrete and missing chunks at landing. remedy: repair and/or replace.

    Jun 18, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at auditorium left stage exit path destructed by storage at furniture and equipment. remedy: comply with motive of violation.

    Jun 18, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: use of prohibted door and/or hardware per bc 1008.1.8; 27-371(j). noted illegal kick down door stops equipped on classroom doors #407, 425 and 416. remedy:

    Jun 18, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. noted exterior doors at exits #15, #1 and #0, mentioned are rusted, rub a frame as saddle, difficult to open without excessive force and not self closing. remedy: repair/replace door

    Jun 18, 2024 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Reissue #35674990r. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted approx. 14 emergency lights not working when

    Jun 18, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35674988h. failure to maintain building in code-compliant manner. noted at stair c 2nd and 1st floor midlanding, outer window panelis cracked. remedy: repair and/or replace.

    Jun 18, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at auditorium at stage,both left and right exit doors were obstructed by boxes,chairs,trash cans,all piled up infront of the exit doors.rem:remove obs

    May 18, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35578203z failure to maintain building in code-compliant manner.noted:at 2nd floor midlanding,outer window pome cracked.rem:repair or/replace.

    May 18, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at cellar next to electrical room,gas powered snow blower and vacume machine being stored.rem:comply with notice of violation.

    May 18, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at exit 15stair c one of four door with broken door closer.rem:repair/replace.

    May 18, 2023 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridor per bc 1006.1;27-381.noted:at gym,exit 16 and at auditorium 6 emergency exit lighting found inoper

    May 18, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35578201p failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc1006.1;27-381.noted observed during inspection of emergency lights,hallw

    May 26, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35578202r failure to maintain building in code compliant manner.noted observed during inspection of roof level bulkhead,stair z peeling/spalling plaster due ro water penetration of wall and ceiling.reme

    May 26, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.no fire stoppingper bc712.3;27-345.noted observed during inspection of cellar level electrical room opening in wall approx 1ft by 1ft with conduit pipe goin

    May 26, 2022 · Penalty $1,250

    Resolve
  • Class - 1

    Unsafe storage of combustible materials and equipment-noted,at 1st fl room#148,gas powered snow blowers,grass trimmers,lawn mowers stored.(all gas powered) remedy:maintain storage in compliance w/ fire code

    Oct 8, 2021 · Penalty $6,250

    Resolve
  • Class - 1

    Unsafe storage of combustible material and equipment.noted:observed at cellar storage room several combustible equipment such as snow blowers,lawn mowers, grass trimmers, etc stored.

    Aug 9, 2021 · Penalty $6,250

    Resolve
  • Class - 1

    Unsafe storage of combustible3 material&equipment.noted:observed@cellar level,snowblowers,lawnmower,grass trimmers (all gas powered).all being stored w/i bldg cellar.maintain storage in compliance w/fire code.

    Jun 8, 2021 · Penalty $2,500

    Resolve
  • Class - 2

    Reissued35498248m failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:observed@1fl,existing emergency lights labeled8&9 werent oper

    Jun 8, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner noted:observed@stairzbulkhead spalling missing plaster of walls,some have fallen off wall,due to water penetration.repair &/or replace.

    Jun 8, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:noted:observed outer window pane@2fl midlanding cracked.repair &/or replace.

    Jun 8, 2021 · Penalty $625

    Resolve
  • Class - 2

    Control piping has wrong material on pigtails, correct violating condition and submit a certificate of correction

    Jun 3, 2021 · Penalty $625

    Resolve
  • Class - 2

    Control piping on pigtails wrong material, correct violating condition and submit a certificate of correction

    Jun 3, 2021 · Penalty $625

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm, and perf

    May 24, 2021 · Penalty $1,250

    Active
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm, and perf

    May 24, 2021 · Penalty $1,250

    Active
  • Class - 2

    Re-issue #35447856x failure to maintain bldg in code compliant manner:illumination for exits,exits discharges & public corridors per bc1006.1,27-381.noted: on the 1st fl auditorium,2 of the emergency lights wer

    Jun 30, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: leak(ceiling)at cafeteria due toi defective roof. remedy: make necessary repairs.

    Aug 19, 2019 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: atauditorium 2 exit emergency lighting imperative.

    Aug 19, 2019 · Penalty $625

    Resolve
  • Class - 2

    Reissue:35222150r exit doors not self closing. exit doors not self closing at following locations 4 floor at roof, exit x on second floorrmdy: repair/replace doors.

    Jul 18, 2017

    Resolve
  • Class - 2

    Reissue:35093251h exit door not self closing. 2t flr vestibule exit (1,2,3) 2nd flr stair (b,c,x) 3rd floor stairs (b,c,x,y) 4 flr near rm4607z. rmdy: repair/replace.

    Jul 18, 2017

    Resolve
  • Class - 2

    Reissue:35129477m failure to maintain building in code compliant manner. exit doors defective not opening/closing properly at stair (z)4 floor, stair(y) 3rd flr, 1 floor room 203 also cafeteria doors. rmdy

    Jul 18, 2017

    Resolve
  • Class - 2

    Reissue 35129477m exit door does not self closing. the exit door to the roof is not closin,also the doors near exit 2 staircase is not closing properly also the door near exit x on the seecond flr is not closin

    Dec 5, 2016

    Resolve
  • Class - 2

    Reissue #35093251h failure to maintain bldg in code compliant manner.note:exit doors defective not opening + closing properly locations:stair z-4th floor 2 doors.stair y -3rd fl 1 door,room #203 1 door cafeteri

    Jul 20, 2015

    Resolve
  • Class - 2

    Work w/o a permit:work noted @ cellar"pipe storage room".installed full height partition,creating an "office".installed 220c electrical for use of 3d printer & electrical outlet & lighting in "office area".rem:

    Mar 14, 2014

    Resolve
  • Class - 2

    Reissue ecb #34932771j.failure to maintain bldg wall(s)or appurtenances(1)bulkhead "x"&"z" have moisture penetrations & walls have become porous.(2)new bldg roof has leakage @ penetrations.rem:waterproof bulkhe

    Mar 14, 2014

    Resolve
  • Class - 2

    Reissue 35023762x.exit doors not self closing:1st fl:vestibule doors exit 1,2&3;2nd fl.stairs "b","c","x" & "y";3rd fl:doors next to rm311,stairs "b","c","x"&"y" 4th fl:doors next to rm 460e;bulkhead doors @ st

    Mar 14, 2014

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner;lack of emergency lighting for exits,exit discharges & public corridors oer bc 1006.1;27-542.emergency lighting in auditorium needs bulb replacement @ several l

    Mar 14, 2014

    Resolve
  • Class - 2

    Occupancy contrary to that allowed by cert of occupancy or bldg dept of records.noted @ cellar level:"pipe storage room"is now being used asa office space & shop area w/installation of full height partition w/d

    Mar 14, 2014

    Resolve
  • Class - 1

    Failure to maintain bldg in code-compliant manner.@ gym ceiling:diffuser @ vent hanging & not secure & in danger of falling.rem:repair &/or replace immediately.

    Mar 13, 2014

    Resolve
  • Class - 2

    Doors not closing. at 1st story stair c at 2nd story stairs b,c,x,y (up), cafeteria exit doors to corridor at 3rd story stairs b,c,x,y & zat 4th story stairs x ad y...remedy: repair and/or replace doors noted

    Jul 3, 2013

    Resolve
  • Class - 2

    Reissue 34932774p no fire stopping. at basement electric panel room conduit penetrations not fire stopped. rmdy: provide firestopping.

    Jul 3, 2013

    Resolve
  • Class - 2

    Defective doors at 2nd floor stairway c and x; doors not properly self-closing. remedy: repair and/or replace so doors properly self-close.

    Feb 9, 2012

    Resolve
  • Class - 2

    Unauthorized storage at 3rd floor room 348 electric service room, storage of various school furniture and supplies. remedy: remove all items, maintain service room clear.

    Feb 9, 2012

    Resolve
  • Class - 2

    Moisture penetration at stairway z bulkhead; the exterior walls have become porous allowing moisture to penetrate into bulkhead walls. remedy: waterproof exterior walls.

    Feb 9, 2012

    Resolve
  • Class - 2

    Partial corridor obstruction at 2nd floor corridor adjacent to room 214, partial obstruction with table, rolling cart, cardboard boxes & other combustible items.remedy:remove all items;maintain corridor w/clear

    Feb 9, 2012

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1931
Floors
4
Residential units
—
Building area
145,872 ft²
Lot area
54,000 ft²
Zoning
R5
Community board
402
Council district
26
Block / lot
228 / 20
Assessed value
$19,440,000
Landmark / historic district
No

Questions about 37-02 37 Street

Who owns 37-02 37 Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 37-02 37 Street have violations?

NYC HPD has no housing violations on record for this property.

Is 37-02 37 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 37-02 37 Street built?

City records list 1931 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.