21-10 Borden Avenue

Queens, NY 11101BBL 4-00068-0002Map

Owner of record: NYC Department Of Homeless Services

21-10 Borden Avenue is a care facility built in 1963 in Queens, 11101. The owner of record is NYC Department Of Homeless Services. HPD has recorded 1 housing violation here, most recently on January 10, 2016.

HPD violations
1
DOB violations
16
ECB violations
25
HPD complaints
2

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
Last violation Jan 10, 2016

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 1

  • B

    Repair the roof so that it will not leak ,at skylight

    Jan 10, 2016

    Closed — Violation closed

DOB building violations · 16

  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Feb 24, 2010

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
Show 6 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 28, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 28, 1993

    Dob violation - dismissed
  • Construction other optional

    Mm

    Feb 15, 1990

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 25, 1989

    Dob violation - dismissed

ECB violations · 25

  • Class - 2

    Observed on the ground floor sprinkler head obstructed also no fire stop protection around pipe penetration. water fountain and waste line going through electrical room which is contrary to code sections ec 110

    Jan 12, 2026 · Penalty $1,250

    Active
  • Class - 2

    Observed not having proper gas appliance shut off valves for cooking equipment and hot water heaters. vents to hot water heater exhaust and gas dryers not using the proper material. using pvc waste lines for wa

    Jan 12, 2026 · Penalty $1,250

    Active
  • Class - 1

    Failure to maintain building in code-compliant manner. detected gas leak at boiler room. located on first floor., repair and/replace

    Jan 12, 2026 · Penalty $2,500

    Active
  • Class - 2

    At exposure # 2 (kitchen emergency exit way ) , displacement of the last three courses of brick in the upper part of the walls & missing mortar, also, at cafeteria/bathroom entrance cmu walls cracked., maintain

    Oct 25, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Gas line to regulator to be hard piped,fluepipe to be welded (federal blr) remove stopper on barometric damper ,inter lock comb air fan,correct violation and send in certificate of correction

    Sep 27, 2021 · Penalty $625

    Resolve
  • Class - 2

    Draft ind.cannot run continous must be nterlocked ,and combustion air fan to be interlocked,this is a water htr with h stamp

    Sep 27, 2021 · Penalty $625

    Active
  • Class - 2

    Federal fst-150 boiler. motorized valve on top of boiler corroded. correct violating conditions and submit a certificate of correction.

    Sep 24, 2019

    Resolve
  • Class - 2

    Failure to provide/maintain sufficietn access/work space about electrical equipment. observed in gas meter room (2) circuit breaker panels block by gas pipes w/o sufficient work space required. photos taken.

    Jan 24, 2019

    Resolve
  • Class - 2

    Failure to provide, maintain sufficient access, work space about electrical equipment. observed in gas meter room. two electrical panels (42 ckt) being obstructed by gas piping. rmdy: provide maintain access

    Aug 10, 2018

    Resolve
  • Class - 1

    Gas piping not labeled. observed on 7/24/18 at above address gas pip ing in ceiling from boiler room through corridor to laundry room for gas dryers not labeled. rmdy: comply with summons.

    Jul 24, 2018

    Resolve
Show 15 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner: failure to com ply with law for drainage system per pc 702.1: 27-911. observed on 7/24/18 at above address sink in the maintenance room being drained in

    Jul 24, 2018

    Active
  • Class - 2

    4a,24b,50a,50b,50c,50d,50e-federal fst-150 heating boiler gas-fired. 50a)draft regulator missing. 50b)spill switch missing. 50c)remove cap from chimney termination. 50d)support discharges on boiler relief valve

    Jul 11, 2018

    Resolve
  • Class - 2

    24b,50a,50b,50c-ao smith model hw1340 lp hot water boiler. 50a)missing manual reset low water cut-off. 50b)fresh air fan not interlocked with boiler. 50c)termination of chimney to be at least 3ft away from fres

    Jul 11, 2018

    Resolve
  • Class - 1

    Unlawful acts failure to comply w/an order of the commissioner.recordsindicate bi application was made to correct and certify removal of violation contained in summons #35272091l. rmdy: comply w/commissioners

    Mar 29, 2018

    Resolve
  • Class - 1

    Failure to comply with the commissioners order contained in summons/violation #35272091l issued on 07/11/2017 and to file a certificate of correction pursuant to 28-201.1,28-204.4 and 1rcny 102-01.summons 35272

    Jan 8, 2018

    Resolve
  • Class - 1

    Failure to comply with commissioners order contained in summons/violation#35272426y issued on 07-11-17 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01.for work w/o permit at laundr

    Aug 18, 2017

    Active
  • Class - 1

    Work w/out a permit. observed in laundry room on main flr (1 story) gas plumbing connections made to dryers w/out permit. photos taken. rem: obtain all required permits.

    Jul 11, 2017

    Active
  • Class - 1

    Failure to ground electrical systems. observed @ water main pipe: main grounding conductor for bldgs electrical systems disconnected from water main; floating ground. failure to ground electrical systems can re

    Jul 11, 2017

    Resolve
  • Class - 1

    Failure to have new or altered plumbing system tested. observed from dob records that no test was performed on plumbing gas connections made to dryers in laundry on main flr. photo taken. rem: perform test.

    Jul 11, 2017

    Active
  • Class - 1

    Residential gas flex used on commercial equipemtn. at time of my inspection i observed in the laundry room commercial gas fired dryers beingsupplied gas with flexible residential gas hoses.photo taken.rmdy:com

    Jan 13, 2017

    Active
  • Class - 2

    Operating a place of assembly w/o a current certificate of operation (paco) noted: cafeteria/dining room with 13 tables arranged w/seating for 101 persons. no maximum occupancy sign posted w/dining area apprx

    Jul 28, 2016

    Resolve
  • Class - 2

    Operating a place of assembly w/o a current cert of operation. note: cafeteria/dining room w/tables and chairs arranged for 96 persons (12 tables w/8 seating)dining area greater than 1,500 sq ft.no occ sign po

    Feb 24, 2016

    Resolve
  • Hazardous

    4a,19b

    Aug 5, 2003

    Resolve
  • Non-hazardous

    50. 50)manhole at top of boiler is leaking.

    Aug 5, 2003

    Resolve
  • Non-hazardous

    Altered building occupied without a valid certificate of occupancy.ex-pired certificate of occupancy #c.o. q211603 under alt 614/86.remedy: obtain a certificate of occupancy forthwith.

    Jul 18, 1990

    Resolve

Complaints

  • Heating

    Heat related

    Jan 23, 2014 · Apt 3

    Close
  • Heating

    Heat related

    Jan 22, 2014 · Apt NA

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Care facility (N2)
Year built
1963
Floors
1
Residential units
—
Building area
55,000 ft²
Lot area
71,000 ft²
Zoning
M3-2
Community board
402
Council district
26
Block / lot
68 / 2
Assessed value
$5,128,200
Landmark / historic district
No

Questions about 21-10 Borden Avenue

Who owns 21-10 Borden Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Homeless Services.

Does 21-10 Borden Avenue have violations?

Yes. NYC HPD has recorded 1 housing violations at this property.

Is 21-10 Borden Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 21-10 Borden Avenue built?

City records list 1963 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.