100 Fillmore Avenue

Brooklyn, NY 11229BBL 3-08496-0100Map

Owner of record: NYC Department Of Education

100 Fillmore Avenue is a school building built in 1960 in Brooklyn, 11229. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
36
ECB violations
63
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 36

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 25, 2009

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 27, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 26, 2008

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2008

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 2, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 14, 2006

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 14, 2006

    Vw*-violation - work w/o permit dismissed
Show 26 more ↓
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 3, 2003

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    3s5311

    Feb 21, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 10, 2000

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 26, 1999

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 17, 1995

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 28, 1993

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Oct 12, 1989

    Dob violation - dismissed
  • Elevator elevatorrequired

    51)restore sidewalk elevator 5311 to service or file a bn and pla place out of active service (dismantle)or permanently discontinue (remove)

    Mar 1, 1989

    Dob violation - resolved

ECB violations · 63

  • Class - 2

    Re-issue 35721270h. at the time of inspection, the doors were not self-closing:-302, 305, 303a, 309, corridor door next to 308, 311, 310, 313, staircase "d" on 3rd floor, 315, 320, 319, 327, 317, 329, 332, 338,

    May 1, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). at the time of inspection, the following doors had turn knob handles:-306, 309, 311, 313

    May 1, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection, the following emergency lights were inoperab

    May 1, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issue 35721268z. at the time of inspection, the gas and electrical meter rooms had ceiling/wall penetrations, gas and electrical meter rooms are not fire-stopped. remedy: provide/maintain fire stopping.

    May 1, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue 35721272l. at the time of inspection, bulkhead "c" wall has spalled, however the repaired areas had bubbling. the same wall location on 3rd floor had bubbling. remedy: repair and/or replace.

    May 1, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue 35721269k. at the time of inspection, the oil tank room had acrack in concrete wall that had water trickling down. remedy: repair and/or replace.

    May 1, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.classroom door not self closing missing hardware in room 202,205,207,209,208,211,213,217,219,249,231,232,234,229,320,317,313,310,311,309,308,305.rem:repair

    Jul 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. cracks in retaining wall in rear by park and on side of school under rail parks of wall broken. remedy: repair and/or replace.

    Jul 22, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.large open holes in electrical and gas meter room firestop not done.rem:provide maintain firestopping.

    Jul 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.oil tank room crack in wall leaking and oil tank support one site has crack in the concrete support.rem:repair and/or replace.

    Jul 22, 2025 · Penalty $1,250

    Active
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner.roof level much of roofing material lifting up and cracking and coming apart under thesolar paneling on most of the roof.rem:repair and/or replace.

    Jul 22, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.crack in bulkhead and down the stairs from water leaks coming from roof level.rem:repair and/or replace.

    Jul 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35672611z. failure to maintain building in code-compliant manner: illumination for exit, exit discharges and public corridors per bc 1006.1; 27-381; noted: next to room 326, and exit and b, all these l

    Jul 1, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination exit,exit discharges & public corridor per bc 1006.1;27-381.noted:at 1st fl exit, f & g 4 lights.also at 1st corridor none of the lights operat

    Mar 20, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35495850l date of issue:06.02.2020 failure to maintain building in code compliant manner illumination for exits.exit discharges and public corridors per bc 1006.1;27-381.at at first floor gym 4 place

    May 27, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.no fire stopping per bc 712.3;27-345.in basement level electrical room fue place in wall hole with pipes in gas meter room in basement level fue holes no fi

    May 27, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not self closing properly at basement level lunch room one exit door(exit way to yeard)exit door not self closing properly.at 2nd floor stair way "6" one exit door not self closing properly at time of

    May 27, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: onthe 1st fl gymnasium & in the cafeteria at basement 2 & 3 of the emerg

    May 8, 2020 · Penalty $625

    Resolve
  • Class - 3

    Failure to maintain reissue #35328668r failure to maintain building incode-compliant manner. multiple areas of roof failing buble up, cracking let watering. rem:reoair and/or replace.

    May 15, 2019

    Resolve
  • Class - 3

    Failure to maintain building in code compliant manner.noted:at roof level,northside,multiple areas of roof membrane blistering,approx16 blisterobserved.failing flashing at same area around bulhead located at

    Apr 16, 2018

    Resolve
  • Class - 2

    Exit door not self closing. observed @ 3rd flr exit staircase 'd' & exit h, 1st flr exits g & f, basement exit a & b & cafeteria kitchen doors non self closing. rem: repair &/or replace.

    May 16, 2017

    Resolve
  • Class - 2

    Sec: 28-301.1. unlawful placement of furnishings, decorations or otherobjects @ exits that obstruct access to egress from or visibility thereof per fdny 2008 code; fc 803.3.2. noted: @ 1st flr exit f & g & back

    May 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illumination for exits, exit discharges & public corridors per bc 1006.1; 27-381. observed @ the basement exit staircase 'e' & the cafeteria not operational em

    May 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: use of prohibited door &/or handware per bc 1008.1.8, 27-371(j). observed @ all flrs installed kick stops on multiple doors. rem: provide level handrail.

    May 16, 2017

    Resolve
  • Class - 2

    Re-issue ecb# 35023312z the following doors are racked and not closingproperly : 3rd fl stair d, croadd corridor door near room 315; 2nd fl stair case a,b,c; 1st fl stair g, f. remedy: repair or replace doors

    Jul 23, 2014

    Resolve
  • Class - 2

    Reissue 34953916y defective doors at 3rd flr stair d,corridor door near 315, 2 floor stair a,b,c, 1flr stair g,f. rmdy: repair/replace doors.

    Jun 19, 2013 · Penalty $2,500

    Resolve
  • Class - 2

    Doors not closing. at: various locations throughout all stairs and levels. at: basement cross corridor door near rm b29. remedy: repair/replace doors.

    Apr 19, 2012

    Resolve
  • Class - 2

    Water damaged/displaced concealed spline ceiling. at: 3rd sty room 304approx 26 sf of ceiling tile delaminated/dislodged/displaced/water damaged. remedy: repair/replace defects noted.

    Apr 19, 2012

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.failure to comply w/law for drainage system per pc702.1.observe in basement intermediate school 278 in kitcehn area not installed indirect waste for all sinks a

    Oct 4, 2011

    Resolve
  • Class - 2

    Sec. 3301.9.5;28-105.11 failure to post a readily visible sign w/permit # on sidewalk shed. at p.s.278 id #k278 sidewalk shed erected under job #30256066 does not have the job # posted. job #302559050 is posted

    Sep 16, 2011 · Penalty $400

    Resolve
  • Class - 2

    Missing fire stop fire stop missing at conduit and pipe penetration at cellar gas meter room cellar electric room cafeteria east exit vestibule rem: provide fire stop

    Sep 16, 2011

    Resolve
  • Class - 2

    Prohibited hardware at auditorium lobby doors installed door stop latches prevent proper operation of self closing doors rem: remove illegal hardware

    Sep 16, 2011

    Resolve
  • Class - 2

    Broken door checks the fire proof doors have broken door checks and are not self closing at 3fl stairway c 2fl stairway b & c room 118a cellar stairway b room b26 smoke doors adjacent to room b29 rem: replace

    Sep 16, 2011

    Resolve
  • Class - 2

    Racked doors the fire proof doors are racked to frame and/or drag on floor at 1fl stairway a & b gym 2fl stairway c smoke door adjacent to room 226a missing rem: repair replace doors to properly open and self c

    Sep 16, 2011

    Resolve
  • Class - 2

    Failure to maintain observed: open holes in corridors,stairwells,around electrical conduit installed for camera system. note: contractor work complete. remedy: repair penetrations.

    May 12, 2010

    Resolve
  • Class - 2

    Failure to maintain observed: at entrance to electric room,trip hazardcreated by 4" change in floor elevation. potential fall into open electrical connections. remedy: provide safe egress/passage.

    May 12, 2010

    Resolve
  • Class - 2

    Sec. 28-301.1 reissue 34792384h failure to maintain observed at schoolroof,standing/poundings water,bubbles under roofing - throughout. remedy: maintain building.

    May 12, 2010

    Resolve
  • Class - 2

    Failure to maintain observed: no fresh air ventilation gas meter room.remedy: provide ventilation.

    May 12, 2010

    Resolve
  • Class - 2

    Failure to maintain observed: in gas meter room - standard toggle light swich located in unvented room. remedy: maintain building per code.

    May 12, 2010

    Resolve
  • Class - 2

    Failure to maintain adequate fire stopping observed: at gas & electricrooms,open(grills) on entrance doors to rooms,unrated. remedy: maintain fire stopping.

    May 12, 2010

    Resolve
  • Class - 2

    Reissue - 34698109m. plaster damage in following areas - room 315, 329,330,333 spalling at bulkheads: d/e, c, h 2nd flr t section off rm 240/246 water stains basement - b21 plaster ceiling defective. remedy:

    Jun 24, 2009

    Resolve
  • Class - 2

    Defective roofing - pooling and bubbles throughout 3rd flr roofs. remedy: repair/replace according to code.

    Jun 24, 2009

    Resolve
  • Class - 2

    Fire door interior - defective and/or missing - 1- 2nd flr - fire doors missing at t. remedy: install fire doors as per code.

    Jun 24, 2009

    Resolve
  • Class - 2

    Door overhang - defective - exit #3 - ground flr - concrete overhang 8' horizontal cracks at exterior. remedy: repair/replace according to code.

    Jun 24, 2009

    Resolve
  • Class - 2

    Sec. 1017.1;27-369. corridor width decreased auditorium - right exit door partially blocked w/school drama props and misc school equipment. auditorium - right exit to green room. remedy: remove all obstructions

    Jun 24, 2009

    Resolve
  • Class - 1

    Boiler room/fuel oil tank room defective concrete block and/or missingblock. 1- boiler room - over entrance - defective cmu. 2- fuel tank room - missing cmu in rear of room. remedy: restore fireproof enclosure.

    Jun 24, 2009

    Resolve
  • Class - 3

    Plaster damage in classroom 315 on rear wall, also stairway d bulkheadwall. remedy: repair plaster.

    Aug 20, 2008

    Resolve
  • Non-hazardous

    50a,b. fitzgibbon ftfb boiler, lpsion, ok. 50a original safety valves mounted on the referenced boiler are obsolete not serviceable and mustbe replaced w/asme - approved devices of similar pressure settings

    Feb 25, 2008

    Resolve
  • Non-hazardous

    50a,50b. fitzgibbon ftfb boiler, lpsion, oil. 50a. original safety valves mounted on the referenced boiler are obsolete, not serviceable andmust be replaced w/asme-approved devices of similar pressure settings

    Feb 25, 2008

    Resolve
  • Non-hazardous

    50a,b. fitzgibbon ftfb boiler, lp sion, oil. 50a. original safety valves mounted on the referenced boiler are obsolete, not serviceable and must be replaced w/asme-approved devices of similar pressure settings

    Feb 25, 2008

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1960
Floors
3
Residential units
—
Building area
155,720 ft²
Lot area
92,765 ft²
Zoning
R4
Community board
315
Council district
46
Block / lot
8496 / 100
Assessed value
$15,462,000
Landmark / historic district
No

Questions about 100 Fillmore Avenue

Who owns 100 Fillmore Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 100 Fillmore Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 100 Fillmore Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 100 Fillmore Avenue built?

City records list 1960 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.