2929 West 2 Street
Brooklyn, NY 11224BBL 3-07281-0001Map
Owner of record: NYC Department Of Education
2929 West 2 Street is a school building built in 1931 in Brooklyn, 11224. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 14
- ECB violations
- 53
- HPD complaints
- 5
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 14
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
Show 4 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active
ECB violations · 53
- Class - 2
Reissue#35719930l failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:there were several emergency lights that were not o
Jun 22, 2026 · Penalty $3,125
Active - Class - 2
Exit door not self closing.noted:the 3 exit doors at exit#2,and the 2 exit doors at exit#3,do not self close properly.they are also very difficult to open.rem:repair/replace all 5 exit doors.
Jun 22, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at exit 4 and 5 the ceilings are damaged and peeling and cracking from water penetration from above.rem:repair leak/repair paint ceilings.
Jun 22, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:the gas meter is located in the cellar.but not in a separate room.there is an abundant amount of storage too close.rem:remove storage from gas meter a
Jun 22, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:the condition of the parking lot,adjacent to the school is in poor condition.cracks,pot holes and uneven surface needs to be required.rem:repair/repla
Jun 22, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:the entry doors at main entry#1 and exit 7 are loose with large gaps at bottoms and tops.winds,heat and cold drafts and rain can easily get through.re
Jun 22, 2026 · Penalty $1,250
Active - Class - 2
Reissue #35672617j: failure to maintain building in code-compliant manner: illumination for exits, exit corridors per bc 1006.1(2014 code); 27-381, bc 1008.1(2022 code). observed and tested @ cafeteria, gymnasi
Jun 2, 2025 · Penalty $3,125
Active - Class - 2
Re-issue #35672617j. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors perbc 1006.1; 27-381. noted: in the gymnasium, two lights, stairwell 2e,
Jul 19, 2024 · Penalty $1,562
Active - Class - 2
Exit door not self-closing. noted: exit 1 on the first floor, exit 3, 4, 6, and 7 all these doors were not opening and closing properly. remedy: repair/replace door.
Jul 19, 2024 · Penalty $625
Active - Class - 2
Re-issue #35657689n failure to maintain building in a code complaint manner. noted:observed in the kitchen, the gas stove does not have an ansul system.remedy:repair and/or replace
Apr 13, 2023 · Penalty $1,562
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code compliant manner:illumination for exit, exit discharges and public corridors per bc 1006.1;27-381. noted:observed on the 3rd fl in the gymnasium one light, also on the 3rd f
Apr 13, 2023 · Penalty $625
Active - Class - 2
Reissue35561187r failure to maintain bldg in codecompliant manner.noted:observed during insp of cafeteria kitchen gas stove doesnt have ansul system.repair &or replace
May 18, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of roof level, parapet brick walls missing mortar thruout.repair &or replace
May 18, 2022 · Penalty $625
Resolve - Class - 2
Reissue:35495236l.failure to maintain building in code complian mannernoted:at cekkar/basement boys bathroom/below-spalling master.remedy:comply with code.
May 20, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue:35495238p.failure to maitnain bldg in code-compliant manner.noted:at kitchen,commercial gas stove dont have ansul system.remedy:comply with code-provide ansul system.
May 20, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at 1st fl exit'h'&'i' leak above the exit doors due to defective roof. also at 5th fl next to room #502,active leak coming from roof. remedy: make neces
May 1, 2020 · Penalty $625
Resolve - Class - 2
Reissue#35235449y failure to maintain bldg in code compliant manner. noted: at basement,under boys bathroom,spalling plaster have fallen off the structural steel beam. remedy: make necessary repairs.
May 1, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at kitchen,commercial gas stove do not have ansul system. remedy: provide ansul system to gas stove.
May 1, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. illumination for exits,exit discharges & public corridor per bc 1006.1;27-381. noted: emergency exit lighting observed inoperative when tested at following loc
May 1, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in a code compliant manner. noted: staircasesd & e basement level, wall tiles are cracked, broken & some are missing, basement 'a' under boys bathroom the structure steel beam's 2 in co
Apr 19, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: water penetration in room 302. water penetrating above window on ceiling from facade in room 302. rmdy: comply w/nov.
Apr 27, 2015
Resolve - Class - 2
Failure to maintain building wall(s) and or appurtenances; lentils above room 302 windows water penetration. water penetrating above window lentils in room 302 from facade. rmdy: comply w/nov.
Apr 27, 2015
Resolve - Class - 2
Re-issue # 35023808m. failure to maintain. spalling plaster above door to court yard from south cafeteria vestibule. remedy: repair defect.
May 21, 2014
Resolve - Class - 2
Failure to maintain. note: steel housing over main roof ventilators is in disrepair with loose/rusted & missing sections of metal. remedy: maintain & repair defect.
May 21, 2014
Resolve - Class - 2
Spalling plaster ceiling at south cafeteria exit vestibule. remedy: repair plaster surfaces.
Jul 3, 2013
Resolve - Class - 2
Water penetrating masonry facade:at various locations throughout all exposures/levels. rem: repair defect noted;maintain weatherproof integrity of bldg envelope.
Apr 2, 2012
Resolve - Class - 2
Water damaged plaster ceilings & walls at various locations throughout all levels. remedy:repair defects noted.
Apr 2, 2012
Resolve - Class - 2
Spalling buttress at east side, exposed flashing, roof level. remedy: repair.
Aug 16, 2011
Resolve - Class - 2
Re 34861710k.portail obstruction on 2nd flr. corridor front of auditorium.display installed approx 2'x6', trip hazard.remedy:remove obstruction.
Aug 16, 2011
Resolve - Class - 3
Occupancy contrary to that allowed by the certificate of occupancy or dob records.noted:reissue nov34791455l.2 playgrounds are occupied as parking lots.remedy:discontinue illegal use or amend c of o.
Jun 17, 2010
Resolve - Class - 3
Failure to maintain bldg in code compliant manner.noted:2nd corridor display box filled w/ sand 2'x6' obstructing corridor to main staircase.remedy:maintain bldg-remove obstruction.
Jun 17, 2010
Resolve - Class - 2
Failure to maintain bldg walls & appurtenances.noted:main roof east side parapet over courtyard (stairway e)has 2 cracks in bricks & spalding bricks.remedy:maintain bldg,repair and/or replace.
Jun 17, 2010
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted:bsmnt level exits adjacent to gas meter & electric panel(main)have no exit
Jun 17, 2010
Resolve - Class - 3
Failure to maintain bldg in a code-compliant manner. noted: @ roof, parapet buttresses, masonry caps cracked, revealing reinforcing steel beneath. remedy: repair/replace concrete caps @ buttresses.
Jun 12, 2009
Resolve - Class - 3
Failure to maintain bldg in a code-compliant manner. 1) 3rd flr corridor obstructions: 8 desks, 11 chairs. 2) 2nd flr storage in stairwell @stage left. 3) 2nd flr static display (2' x 12") w/sand, lighthouse
Jun 12, 2009
Resolve - Class - 3
Occupancy contrary to that allowed by bldg dept records. noted: 2 playyards are occupied as parking lots. evidence of play yard equipment present. remedy: discontinue illegal use or amend c of o.
Jun 12, 2009
Resolve - Class - 2
Failure to maintain bldg in a code-compliant manner. defect noted: 3' x 6' pc of concrete dislodged & hanging approx 18' above flr @ boiler room above exit door. remedy: remove & replace concrete.
Jun 12, 2009
Resolve - Class - 2
Failure to maintain bldg in a code-compliant manner. noted: emergency lighting throughout school inoperative. remedy: replace lights, bulbs,or battery packs as required.
Jun 12, 2009
Resolve - Non-hazardous
50/ 50) condensation tawte cotted & leaking water and steam must replace immediatly
Feb 27, 2004
Resolve - Non-hazardous
Panic hardware inoperative. note: autorium south side exit door panic hardware defective. remedy: repair and/ or replace panic hardware
Apr 29, 2003
Resolve - Non-hazardous
Failure to maintain. defect is: large vertical and horizontal cracks at various locations in front facade. (sidewalk shed erected) remedy: repair front facade
Apr 29, 2003
Resolve - Non-hazardous
Failure to maitnain biulding noted. defect broken window & frame & glass. exit 2 & 3 at bilhead. remedy; make repairs.
Feb 8, 2002
Resolve - Non-hazardous
Failure to maintain. defect's are as follows. 1,water penetration from ceiling at pipes in ceiling,room #212. remedy: make all repairs forthwith.
May 16, 2001
Resolve - Non-hazardous
Failure to maintain defects are as follows. 1,rm 459(bathroom)missing floor tiles thru out floor. remedy: make all repairs.
May 16, 2001
Resolve - Non-hazardous
Failure to maintain. defects are as follows. 1,exit 2 & 3 at roof bulkhead has broken window. fram & glass are ripped out. (see photo) remedy: make all repairs.
May 16, 2001
Resolve - Non-hazardous
Failure to maintain. defects are as follows. spalling plaster & broken plaster on walls & ceilings or both at the following locations. 1,stairway #2,3 #5 to roof bulkheads spalling plaster. (see photo)2, room #
May 16, 2001
Resolve - Non-hazardous
Failure to maintain defects are as follows. 1,stress crack in concrete ceiling in room #507. 2, stress cracks in ceiling at stairway #4. remedy: make all repairs.
May 16, 2001
Resolve - Non-hazardous
Failure to provide 3fl number signs at stair landing on all fl.failure to provide 3'letter stair i.d.signs on all fl.rem:provide signage as for local-law 16/84 code.
Feb 20, 2001
Resolve - Non-hazardous
Failure to provide emergency power exit lights on all fl,corridors andstairs.failure to provide emergency power to exit lights on all fl,corridors and stairs.failure to provide adequate exit/directional signs o
Feb 20, 2001
Resolve - Non-hazardous
49)1cr#4 4-6.6 (c)must install second exit from top of boiler only one means of egress from top of boiler feed water control system
Oct 11, 2000
Resolve
Complaints
- General
Mold
Aug 12, 2004 · Apt 10H3
Close - Plumbing
Bathtub/shower
Aug 12, 2004 · Apt 10H3
Close - General
Windows
Aug 12, 2004 · Apt 10H3
Close - General
Doors
Aug 12, 2004 · Apt 10H3
Close - General
Locks
Aug 12, 2004 · Apt 10H3
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1931
- Floors
- 5
- Residential units
- —
- Building area
- 107,630 ft²
- Lot area
- 46,200 ft²
- Zoning
- R6
- Community board
- 313
- Council district
- 48
- Block / lot
- 7281 / 1
- Assessed value
- $6,016,950
- Landmark / historic district
- No
Questions about 2929 West 2 Street
Who owns 2929 West 2 Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 2929 West 2 Street have violations?
NYC HPD has no housing violations on record for this property.
Is 2929 West 2 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 2929 West 2 Street built?
City records list 1931 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.