2840 West 12 Street
Brooklyn, NY 11224BBL 3-07266-0040Map
Owner of record: NYC Department Of Parks And Recreation
2840 West 12 Street is a school building built in 1964 in Brooklyn, 11224. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 27
- ECB violations
- 46
- HPD complaints
- 1
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 27
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed
Show 17 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 4, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 17, 2014
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 12, 2013
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2010 inspection/test
Dec 13, 2011
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 17, 2010
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active
ECB violations · 46
- Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges, and public corridors per bc 1006.1; 27-381. noted: in the auditorium four emergency lights were not operational wh
Jul 19, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.noted:@1fl cafeteria entrance by 138,cafeteria,gym light&exit signs,&1fl thruout corridor@stiara side:emergency lights arent working.repair/replace lighting.
May 18, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.noted:door to rm314&212 isnt working properly.repair &or replace.
May 18, 2022 · Penalty $625
Resolve - Class - 2
Reissue35561185n noted:@3fl smoke by 300,smoke by 204,&exterior door@exit8:exit doors arent working properly.repair/replace door.
May 18, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.3rd floor corridors by rm/exit c does not close property.door check missing.remedy:comply with code.
May 20, 2021 · Penalty $625
Resolve - Class - 2
Provide keys in order to perform proper inspection of device
Feb 26, 2021 · Penalty $625
Active - Class - 2
Replace worn gibs where needed. provide access point for governor. missing data plate for dlm installation
Feb 26, 2021 · Penalty $625
Active - Class - 2
Failure to maintain bldg in code compliant manner. noted: at gas meterroom,water seeps through the concrete pad from underground. water puddle observed outside of gas meter door. remedy: make necessary repairs.
May 1, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: at gym,3 emergency exit lighting inoperative when tested. remedy: repair
May 1, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner:provide required corridor width per bc 1016.2; 27-369 @main entrance vestibule 1st fl:sercuity desk blocking exit door,handicap elevator.rem:comply w/notice of
Apr 24, 2015
Resolve
Show 36 more ↓
- Class - 2
Failure to maintain bldg in code compliant manner glass vision panels @every level on almost every door there are single panel glass vision panels insteads of the required wired glass vision panels.rem:comply w
Apr 24, 2015
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner:emergency stop for interior roll dowm gates.@1st fl main hallway,there are 2 roll down gates w/no emergency stops.rem:comply w/notice of vio.
Apr 24, 2015
Resolve - Class - 3
Failure to maintain. note: defective doors/frames rusted/not operating properly locations: 2nd floor stair "b" (2) doors,1st floor exit #4 to court yard (2) doors. remedy: replace defective doors/frames.
May 21, 2014
Resolve - Class - 2
Door not closing at 2nd story cross corridor doors near room 204 at 3rd story stair a remedy : repair and / or replace doors
Mar 26, 2012
Resolve - Class - 2
Re-issue # 34926997l fire dampers not opeperating at basement adjacentto elevator machine room. remedy : repair &/or replace defect noted
Mar 26, 2012
Resolve - Class - 2
Defective fire dampers at basement adjacent to elevator machine room.remedy:repair/replace fire dampers.
Aug 15, 2011
Resolve - Class - 2
Exit passageway partially obstructed. exit corridor 2nd flr blocked also stiar case 3, also cafeterial doors blocked by tables/chairs.remedy:remove all obstructions.
Aug 15, 2011
Resolve - Class - 3
Defective lighting fixture at westside roof.exposed wiring.remedy:repair fixtures.
Aug 15, 2011
Resolve - Class - 2
Book storage room converted to office w/no ventilation room 110(pta),126.remedy:provide ventilation or remove desk, chairs.
Aug 15, 2011
Resolve - Class - 2
Re 34861629n water penetration into crawl space of gym/auditorium room b12 & boiler room.remedy:seal all penetrations.
Aug 15, 2011
Resolve - Class - 3
28-302.1)failure to maintain bldg walls & appurtenances.noted:reissue nov's 34698122r & 34779775z for no protective guards on roof parapet approx 20" high w/ recent construction on roof.remedy:maintain bldg,ins
Jun 15, 2010
Resolve - Class - 2
Failure to maintain bldg walls & appurtenances.noted:roofing material over gym & auditorium shows signs of deteriorating.cracks @ seams bubbling.maintain bldg.repair &/or replace.
Jun 15, 2010
Resolve - Class - 2
Failure to maintain bldg walls & appurtenances.noted:water penetration into crawl space of gym/auditorium & room b12 & boiler rm gast wall.remedy:stop water penetration,maintain bldg.
Jun 15, 2010
Resolve - Class - 2
Failure to maintain bldg walls & appurtenances.noted:stairs leading to prek playground front of bldg on w 12 st has no handrails installed.remedy:maintain bldg.install handrails.
Jun 15, 2010
Resolve - Class - 3
Sec. 1509.8;27-334. re 34698122r. no protective guards on roof. 3 sty bldg w/recent construction to roof. parapet approx 20" high. remedy: provide guardrails.
Jun 5, 2009
Resolve - Class - 1
Haz - large stone in danger of falling @ ne corner (top stone) loose, also multiple areas of bulging w/missing/loose mortar. northside facade/southside facade has missing/loose mortar. install shed forthwith!
Jun 5, 2009
Resolve - Class - 3
Sec. bc1509 no protective guards on roof 3 story building with recent construction to roof approx 20 inches high. remedy: provide guardrails
Aug 22, 2008
Resolve - Class - 2
Illegal hardware at roof access doors. noted: key cylinder lock engaged at time of insp. remedy: remove hardware.
Aug 22, 2008
Resolve - Non-hazardous
Reissue 34442263l. water penetration through floor into basement rm #b11, boiler room workshop and exit next to bio. remedy: stop water penetration make all necessary repairs.
Apr 28, 2005
Resolve - Non-hazardous
Failure to maintian defects are water through floor in boiler room at various area's remedy:make repairs
Jul 13, 2004
Resolve - Non-hazardous
Failure to maintain defects are cracked defective marble tiled coloumnin cafeteria and on corridor wall leading to cafeteria remedy:make re pairs replacements
Jul 13, 2004
Resolve - Non-hazardous
Use of illegal hardware - note - 1 door off auditorium has illegal hardware - padlock with slide bolt door open at time of insp. remedy : remove illegal hardware
Mar 8, 2004
Resolve - Non-hazardous
Failure to maintain - note - in cafeteria. glazed brick column in cafeteria has horizontal cracking at top of column. remedy: -repair column.
Mar 8, 2004
Resolve - Non-hazardous
Reissue: failure to maintain noted water is puddling and icing present at handicap ramp by room 107. surface needs to be pitched towards drain. remedy; repair surface as so no flooding occvrs.
Feb 13, 2003
Resolve - Hazardous
Failure to maintain building noted defects exit #4 stairwell, missing ceiling tiles & falling plaster hazardous. remedy: make repairs.
Feb 13, 2002
Resolve - Non-hazardous
Failure to maintain building noted defects center support column in cafeterion has stress cracks. remedy: make repairs.
Feb 13, 2002
Resolve - Non-hazardous
Failure to maintain building noted defects exterior flooring and pinding water at handicap ramp by room 107. remedy: make repairs.
Feb 13, 2002
Resolve - Non-hazardous
Failure to maintain upon inspection of the above address. 1 fan room partition wall located outside of stage door exit, is loose and in danger of falling. wall is approximately 14' long x 8' high made of cinder
Apr 20, 2001
Resolve - Non-hazardous
Failure to maintain upon inspection of the above address. 1-cafeteia-column in center of room has stress cracks in tile and broken files. remedy: make all repairs.
Apr 20, 2001
Resolve - Non-hazardous
Failure to maintain upon inspetion of the above address. bulkhead in exit #3 has water penetration through wall and ceiling. remedy: make all repairs
Apr 20, 2001
Resolve - Non-hazardous
Failure to maintain upon inspection of the above address. boiler room fl drain at rear of the boiler in between boiler #1 & #2 does not drain. drain under hot water tank are also clogged. remedy: make all repa
Apr 20, 2001
Resolve - Non-hazardous
Failure to maintain upon inspection of the above address. the following areas have spalling plaster on ceiling. 1-stair well #3 in between 2nd and 3rd fl. 2- romm #201.
Apr 20, 2001
Resolve - Non-hazardous
Failure to maintain upon inspection of the above address. childrens play ground-water doesn't drain and water gathers at bottom of handicap ramp (outside room 107). remedy: make all repairs.
Apr 20, 2001
Resolve - Non-hazardous
Failure to maintain school defects are:slate tiles are main entry is damage causing a trip hazard,cracks on wall in rm 308,306,302,303.crackon ceiling in rms 128,119 and bulkhead of stair 300 3rd floor level.re
Jun 15, 2000
Resolve - Non-hazardous
Failure to maintain. defect is: a) broken concrete slabs at main ent- rance. b) cracks at retaining wall, damaged out of plumb perimeter iron fence. c) at third floor, classrooms & hallways, ceiling & walls
Jun 2, 1999
Resolve - Non-hazardous
Failure to maintain. defect is door on gym area-south side of bldg. hard to open. remedy: repair exit door.
Jun 13, 1991 · Penalty $1,000
Resolve
Complaints
- Heat/hot water
Entire building
Mar 31, 2023 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1964
- Floors
- 3
- Residential units
- —
- Building area
- 64,600 ft²
- Lot area
- 116,400 ft²
- Zoning
- R6
- Community board
- 313
- Council district
- 47
- Block / lot
- 7266 / 40
- Assessed value
- $7,748,100
- Landmark / historic district
- No
Questions about 2840 West 12 Street
Who owns 2840 West 12 Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.
Does 2840 West 12 Street have violations?
NYC HPD has no housing violations on record for this property.
Is 2840 West 12 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 2840 West 12 Street built?
City records list 1964 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.