3302 Neptune Avenue

Brooklyn, NY 11224BBL 3-07006-0001Map

Owner of record: NYC Department Of Education

3302 Neptune Avenue is a school building built in 1923 in Brooklyn, 11224. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
22
ECB violations
58
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 22

  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 3, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 26, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
Show 12 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 26, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active

ECB violations · 58

  • Class - 2

    Reissue#35719944m failure to maintain building in code-compliant manner.noted:the exterior fencing at front of building in need of alteration.rust and deteriorating bending and tilted.rem:repair/replace exit fe

    May 27, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35719749r exit door not self closing.noted:several doors throughout the school corridor and stairway doors,and various exit.exit doors are not self closing as they should.rem:repair/replace self closing

    May 27, 2026 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted:there weresome classrooms with hanging combustible materials as displays.some lights were also observed.rem:remove all hanging combustible materials a

    May 27, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35677341k exit door not self-closing various locations add 4 levels exit doors,smoke door,corridor doors not closing properly when tested.rem:repair/replace door.

    May 21, 2025 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35677332z failure to maintain building in code-compliant manner.observed exterior fences with in the prompt of the building.condition are in deteriorated as rusted,bending,tilted etc.rem:repair/replace.

    May 21, 2025 · Penalty $3,125

    Active
  • Class - 2

    At the time of my inspection of a 6 story building, i observed sidewalk shed in place at exposure # 1,2 and 4 with a valid permit expiration date 04-01-2025, sidewalk shed post was struck out of place and 3 jun

    Jan 21, 2025 · Penalty $2,400

    Resolve
  • Class - 1

    I observed sidewalk shed in place at exposure #2, shed post was struck out of place and 3 junior beams was left hanging, upon review of the department record no notification was made, school personnel informed

    Jan 21, 2025 · Penalty $5,000

    Resolve
  • Class - 2

    Reissue#35672074m failure to maintain building in code compliant manner.exterior fence show signs of deteriorated conditions in several arearem:repair and/or replace.

    Jul 10, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35672073r exit door not self-closing various floors,several tested and not close properly.rem:repair and/or replace door.

    Jul 10, 2024 · Penalty $1,562

    Active
  • Class - 3

    Laars pwo-325 hot water heater=wires exposed+front flame cover jacket not in place+chimney base cleanout door inoperable, maintain boiler; correct violation+submit certificate of correction

    May 23, 2024 · Penalty $500

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner.older cast iron fence fully deteriorated (rust) in most areas newer fence base of fence cracking & falling apart.remedy:repair and/or replace

    Mar 30, 2023 · Penalty $625

    Active
  • Class - 2

    Reissue 35654724j exit door not self-closing.fls 4,3,2,1 in various locations older classroom doors aren't self-closing.remedy:repair/replace doors

    Mar 30, 2023 · Penalty $1,562

    Active
  • Class - 2

    Reissue 35654735l failure to maintain building in code-compliant manner.roof level bulkhead staircase b&f wall & ceiling have spalling plaster & paint fall due to water penetration.remedy:repair and/or replace.

    Mar 30, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not selfclosing.noted:@4,3,2,1fl in various locations several classrm doors arent selfclosing due to missing/defective door closers.repair&replace door.

    May 12, 2022 · Penalty $625

    Active
  • Class - 2

    Failure to maintain bldg in codecompliant manner:noted:@roof level bulkheads stairb&f walls&ceilings have damaged (spalling plaster&paint) due to water penetration w/cracks in walls.repair &or replace

    May 12, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted at 2nd floor class room 210 door drags on teh floor repair/replace door

    Apr 21, 2020 · Penalty $625

    Resolve
  • Class - 3

    Failure to maintain building in code compliant manner noted at exp #1 both custodian bells do not work repair & or replace

    Apr 21, 2020 · Penalty $500

    Resolve
  • Class - 2

    Failure to maintain a bldg in code compliant manner: illumination for exits, exit discharges & public corridors per bc 1006.1; 27-3810 existing emergency tight @ gym (4 pcs). not work when tested. rem: replace

    Apr 20, 2017

    Resolve
  • Class - 2

    Exit door not self-closing: observed @ kitchen 2 tight door & @ left 2 door not self-closing. rem: repair/replace door.

    Apr 20, 2017

    Resolve
  • Class - 2

    Reissue 35085142z water penetration into corridor b rms 508,512 fromrooftop blower duct (). also, room 501 plaiter damage ceiling. rmdy: repair and maintain.

    Feb 4, 2015

    Resolve
  • Class - 2

    Water penetration into corridor by rooms 508,512 from rooftop blower ductwork. remedy: maintain building.

    May 21, 2014

    Resolve
  • Class - 3

    Re-issue # 35018958l. roof drain leaking at stair d 5th floor. remedy: maintain building.

    May 21, 2014

    Resolve
  • Class - 2

    Re-issue # 35018960k. at main entrance, cafeteria f.p.s.c. doors to east & west of lobby missing panic bars. remedy: maintain building.

    May 21, 2014

    Resolve
  • Class - 2

    Reissue # 34950379y defective door. at 5th floor stairway g, steel door delaminating - minor repair is not adequate w/ door sticking closed.remedy: replace door

    Jun 21, 2013

    Resolve
  • Class - 2

    Doors not closing at 2nd fl. classrooms 210, 211, 212, 213, door not self closing, missing door closers. remedy : provide door closers/ maintain doors self closing.

    Jun 21, 2013

    Resolve
  • Class - 3

    Reissue # 34950378m defective roof drain. at 5th fl stairway d, storm drain fitting cracked allowing rain water to enter. remedy: repair interior storm piping.

    Jun 21, 2013

    Resolve
  • Class - 2

    Broken panic bars at cafeteria rear center, double doors not closing w/ panic bars broken preventing doors from closing properly or opening also missing door closers. remedy: provide adequate panic hardware & d

    Jun 21, 2013

    Resolve
  • Class - 2

    Door not closing at 5th story stair g door steel clading declaminating rem: replace door

    Mar 16, 2012

    Resolve
  • Class - 2

    Roof storm drain leaking at 5th story stair d 90 degree elbow joint leaking rem; repair defect noted

    Mar 16, 2012

    Resolve
  • Class - 2

    Failure to maintain bldg walls or appurtenances.noted:water penetration into rooms 305 & 351 @ windows/ceiling area.remedy:maintain bldg-repair and/or replace.

    Jun 17, 2010

    Resolve
  • Class - 2

    Failure to maintain bldg walls & appurtenances.noted:roof level main flasing & parapet wall dislodged & missing throughout.remedy:maintain bldg,repair and/or replace.

    Jun 17, 2010

    Resolve
  • Class - 1

    Haz - re 34698135x. corridor width totally obstructs 6y on 5th flr w/bean bags, tables, chairs. also noted: on all flrs obstructing corridorwidth combustible bean bags, tables, chairs. also on all flrs art work

    Jun 3, 2009

    Resolve
  • Class - 2

    Corridor width decreased by obstructions noted on 2nd flr in front of auditorium water foundation with bricks around it,also noted on all flrs bean bags in corridor. remedy: remove obstructions.

    Aug 28, 2008

    Resolve
  • Non-hazardous

    Reissue 34442289j missing door checks at all class room doors on all floors remedy : install door checks (5.c.)

    Apr 21, 2005

    Resolve
  • Non-hazardous

    Plaster cracked, spalling from wall and ceiling in vestibule exit e remedy : repair plaster walls and ceiling

    Apr 21, 2005

    Resolve
  • Non-hazardous

    Vertical stress crack in brick wall in courtyard west wall under 2nd fl window ~~ 101 remedy : repair brickwork / stress crack______________

    Apr 21, 2005

    Resolve
  • Non-hazardous

    Water penetration through roof into class room # 501 and at vestibule roof exit e reissue 34317606l remedy : repair roof

    Apr 21, 2005

    Resolve
  • Non-hazardous

    Failure to maintain defects are masonry cracks on walls & ceilings location cafeteria over exit h and on 4 walls and ceiling area of fouer at exit 4 remedy: make repairs

    Jul 25, 2004

    Resolve
  • Non-hazardous

    Failure to maintain defects are broken missing door checks & door stops allowing doors to shower exit (doors have glass panels)remedy: make safe repairs

    Jul 15, 2004

    Resolve
  • Non-hazardous

    Failure to maintian hazardous defects are broken cracked missing auditorium seats and patio remedy:make safe make repairs

    Jul 15, 2004

    Resolve
  • Hazardous

    Failure to maintian defects are exterior ground drain are in operable allowing rain water to accumulate and stand in rear yard w 33 st side and ground drians in w 35 street side are pitched too deep and create

    Jul 15, 2004

    Resolve
  • Non-hazardous

    Failure to maintian defects are roof & roof drain over boielr room areallowing water to leak into boiler room along walls and around drain area water is puddling in boiler room also water leaks in to room 501

    Jul 15, 2004

    Resolve
  • Non-hazardous

    Reissue. failure to maintain noted. at front entrance there are broken cracked loose slate step treads. remedy; repair replace broken steps.

    Feb 13, 2003

    Resolve
  • Non-hazardous

    Failure to maintain noted: roof and roof drain over boiler room water leaking into boiler room along walls and around roof drain, water is puddling in boiler room. remedy: repair roof and roof drain over boiler

    Feb 13, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building noted defects spalling plaster exit(e) ground floor. & ceiling in vestibule. remedy: make repairs.

    Feb 19, 2002

    Resolve
  • Hazardous

    Failure to maintain building noted defects stress cracks in basement walls some crackes openned up 2 inches. remedy: make repairs.

    Feb 19, 2002

    Resolve
  • Non-hazardous

    Failure to maintain building noted defects main entre to school has broken slate treaks on steps. remedy: make repairs.

    Feb 19, 2002

    Resolve
  • Hazardous

    Failure to maintain building noted defects play yard has sunken drains uneven surfaces trip hazard. remedy; makes repairs.

    Feb 19, 2002

    Resolve
  • Hazardous

    Failure to maintain bldg.defects are:major cracks on con. ceiling wall s. masonry cols and flooring at basement level in old coal bunker room and boiler room ceiling in bunker room is in danger condition,remedy

    Jun 18, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defects are as follows major cracks in brickwork of basement walls parts of wall have separated up to 2" stress cracks are throughout basement area (old coal bunke room) i question structura

    May 15, 2001

    Resolve

Complaints

  • Heating

    Heat related

    May 31, 2004 · Apt 13H

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1923
Floors
6
Residential units
—
Building area
87,860 ft²
Lot area
49,651 ft²
Zoning
R5
Community board
313
Council district
47
Block / lot
7006 / 1
Assessed value
$5,330,700
Landmark / historic district
No

Questions about 3302 Neptune Avenue

Who owns 3302 Neptune Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 3302 Neptune Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 3302 Neptune Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 3302 Neptune Avenue built?

City records list 1923 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.