1701 Avenue S
Brooklyn, NY 11229BBL 3-06821-0244Map
Owner of record: NYC Department Of Education
1701 Avenue S is a school building built in 1938 in Brooklyn, 11229. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 20
- ECB violations
- 63
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 20
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 17, 2017
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 29, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 4, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 15, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 4, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 13, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 11, 2006
Dob violation - resolved
Show 10 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Construction other optional
C-construction other optional
May 20, 1999
Dob violation - dismissed - Construction other optional
C-construction other optional
May 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed
ECB violations · 63
- Class - 2
Atoi, failure to provide and maintain required safety debris netting at scaffold, not only in loading area but in multiple sections of fixed safety netting observed missing, creating a falling-object hazard. pr
Sep 15, 2026 · Penalty $2,500
Active - Class - 2
Failure to maintain building in code-compliant manner.at the time of inspection the following room doors were not self-closing-416,411,414,408,409,405,403,303,309,307,313,321,319,219,214,205,203,109,117,118,120
Mar 12, 2026 · Penalty $1,250
Active - Class - 2
Reissued 35720626p 2 emergency lights in gym on 4th floor was operable3 emergency lights in gym on 3rd floor was operable.emegency lights#76,#18 were not working.rem:repair/replace lighting.
Mar 12, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).at the time of inspection,the following room doors had turn knob handles-421,420,418,417,41
Mar 12, 2026 · Penalty $1,250
Active - Class - 2
Reissued:35720627r broken mirror in dance room(406),cracks and spalling in rooms staircase a,b,classroom#312,308,303.gas meter room had efforescence from matter infiltration along east 17th street.rem:repair an
Mar 12, 2026 · Penalty $3,125
Active - Class - 2
Reissued 35719747n temporary certificate of occupancy 300911770 expired on 1/30/2001.no superseded tco in effect.rem:obtain valid cofo or discontinue illegal occupancy.
Mar 12, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.at the time of inspection,electrical meter room had multiple through wall penetration with no firestopping.rem:provide/m
Mar 12, 2026 · Penalty $1,250
Active - Class - 2
Altered/changed building occupied without a valid certificate of occupancy as per 28-118.3.1-28.118.3.2.issue sumppers where alt type job 30091770 permit was issued and signed off.cofo#30091770 temporary expire
Mar 19, 2025 · Penalty $1,250
Active - Class - 2
Reissue #35682862m: failure to maintain building in code-compliant manner: observed at staircase a and b included classroom a312, 308a, a303cracks, spalling on walls, ceiling. remedy: repair and/or replace.
Mar 19, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35682863y failure to maintain building in code-compliant manner.illumination exits,exit dischanges and public coridors per bc 1006.1;27-381.observed at stair b and 3rd gym,4th floors gym not operational
Mar 19, 2025 · Penalty $3,125
Active
Show 40 more ↓
- Class - 2
Reissue#35682862m failure to maintain building in compliant manner.stair b,stair a and classrooms#a303,a308,a312 crack,leaks on walls,ceilings.rem:repair/and or replace.
Mar 19, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35682863y; failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per 1006.1, 27-381. existing emergency light are not operational when test
Mar 19, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:on the fourth floor gymnasium two lights,third floor gymnasium two lig
Jun 12, 2024 · Penalty $625
Active - Class - 2
Reissue#35672066m failure to maintain building in code-compliant manner.noted:observed at stair b,stair a,and class rooms a303,a308,a312.there are cracks at all these location listed above.rem:repair and/or rep
Jun 12, 2024 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code-compliant manner.new wing of school staircase 1&b cracks in side staircase & on old side facade.3rd fl cracks on fl going from rm 312 across hall to rm 309.2nd fl cracks on
Mar 16, 2023 · Penalty $1,562
Active - Class - 2
Reissue35560957j(4/30/21) exit door not selfclosing@3fl next to rm310,4fl corridors near 415,@2fl near rm201,281 not selfclosing when tested.repair/replace door
May 9, 2022 · Penalty $1,562
Resolve - Class - 2
Exit door not selfclosing properly@4fl 1corridor exit door not selfclosing properly (near rm415).@3fl (near rm302)(exit door) 1exit not selfclosing properly,@3fl (near rma310) 1exit door no selfclosing properly
Apr 30, 2021 · Penalty $625
Resolve - Class - 2
Re-issue #3533089p.noted:at cellar level,electrical room,holes in wallabove door from electrical (circuits).rem:provide /maintain fire stop ping.
May 13, 2019
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: at the 3rd floor classroom 303a, 320, 4th floor 416, not working properly due to defective hardware. remedy: repair and/or replace
May 13, 2019
Resolve - Class - 2
Exit door not self closing. noted:at the 1st fl,exit(l),2nd fl,exit(l),3rd fl main entrance of the gymnasium,room 302,exit doors not workingproperly due to defective hardware. remedy: repair/replace door
May 13, 2019
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at inspection doors are defective and or racked at 4th floor exit "e", 3rd floor exit ";d" and 2d floor exit "l". rmdy: repair and or replace.
Oct 1, 2018
Resolve - Class - 2
Reissue of non#35260310y.occupancy contrary to that allowed by cofo and bldg dept records.noted:10 storage rooms converted to office space with no fresh air(window or mechanical violation).rem:comply with notic
Apr 11, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: room 117,118,119,308 have inoperable doors due to defective hardware. also smoke doors @ 1st,2nd & 3rd fl are racked & do not close properly. remedy: re
May 10, 2017
Resolve - Class - 2
Reissue ecb #34953673z ash hoist doors.@ front of bldg,ash hoist door rusted & deteriorated.rem:replace ash hoist doors.
Jul 18, 2014
Resolve - Class - 2
Reissue 34953670n defective doors. 1flr auditorium exit doors 1 flr auditorium exit doors, exit m,e, stairs l,corridor door near room 101,stair j 2fl stair d. remedy: repair/replace.
Jun 20, 2013
Resolve - Class - 2
Roof leaks at various locations throughout water penetrating roof rem: repair defect noted maintain water proof integrity of roof
Apr 12, 2012
Resolve - Class - 2
Doors not closing at 1st story auditorium exit discharge door at 1st story exit m discharge door stair e stair l cross corridor door near room 113 cross corridor door near room 101 at 2nd story stairs d & j at
Apr 12, 2012
Resolve - Class - 2
Ash hoist doors rusted deteriorated at front of premises bilco ash hoist doors rusted deteriorated steel frame rusted deteriorated rem; repair &/or replace ash hoist doors
Apr 12, 2012
Resolve - Class - 2
Exterior stair steel thread nosing displaced at exit h adjacent to handi cap ramp steel anti stair nosing displaced missing 2 treads rem: repair/replace defects noted
Apr 12, 2012
Resolve - Class - 2
Defective shed illumination sidewalk shed illuminated under job#b339178 has defective lighting illumination noted 9 light bulbs burned out rem: maintain proper shed illumination
Sep 15, 2011
Resolve - Class - 2
Failed to obtain permit sidewalk shed erected at each entry exit and along ave 5 w/o obtaining a temporary construction permit to install use sidewalk shed rem: obtain temp permit
Sep 15, 2011
Resolve - Class - 2
Missing fire stop at cellar electric room no fire stop at ceiling conduit penetration and right rear wall at concealed penetration of wall to service panel rem: provide fire stop seal all penetrations
Sep 15, 2011
Resolve - Class - 2
Partial corridor obstruction partial corridor obstruction at corridor adjacent to elevator bank a 2 3 4th fl w/ tv cart desk paper rolls andcabinets rem: remove all items maintain corridor width clear
Sep 15, 2011
Resolve - Class - 2
Concealed water leak at room 304 concealed water leak in suspended ceiling damaging many ceiling tiles rem: repair concealed leak
Sep 15, 2011
Resolve - Class - 2
Occupancy contrary to c/o at auditorium lobby dance class in session closes corridor passageway for egress at time of insp rem: discontinue illegal use
Sep 15, 2011
Resolve - Class - 2
Broken door checks the fire proof doors are not self closing w/ broken door checks at 2fl stairway d 3fl stairway l em: replace door checks so doors properly self close
Sep 15, 2011
Resolve - Class - 2
Fail to maintain observed open penetrations around ceiling conduits open diamond lathe transom over entry doors. remedy: maintain firestopping
Jun 3, 2010
Resolve - Class - 2
Fail to maintain observed. defective door closer 1fl stair e. remedy: maintain bldg
Jun 3, 2010
Resolve - Class - 2
Fail to maintain observed racked fpsc door stair a 2 fl wont close. remedy: maintain bldg
Jun 3, 2010
Resolve - Class - 3
Fail to maintain observed missing ceiling tile 3rd fl elevator lobby. remedy: maintain bldg
Jun 3, 2010
Resolve - Class - 3
Fail to maintain. observed: spalling plaster ceiling & walls 4th fl gym ceiling. remedy: maintain bldg
Jun 3, 2010
Resolve - Class - 1
A/c unit installed in window over the main entrance - no supports. remedy: remove a/c unit - and/or install a/c supports. make area safe.
Jun 18, 2009
Resolve - Class - 2
Reissue - 34570087h. interior doors not fully functional. 1- 2nd flr stair a - door hits block. 2- 1st flr. exit k - interior door not self-closing. 3- 1st flr interior door exit e - no stricks in hour. 4- 1st
Jun 18, 2009
Resolve - Class - 2
Roof parapet - interior side missing mortar. 1- main bldg - missing mortar approx 25 lf 12" down from coping (school yard side). 2- main bldg - missing mortar approx 25 l.s. (ave s side) remedy: repair parapet
Jun 18, 2009
Resolve - Class - 3
Defective exterior exit doors (all) frames rotted,hinges loose,some doors stuck shut. remedy: repair/replace doors.
Aug 18, 2008
Resolve - Hazardous
Re-issue # 34504848h.noted:all interior fire/smoke doors defective,loose hinges,bent doors causing doors not to operate as required.remedy:repair/replace doors.
May 10, 2007
Resolve - Hazardous
Reissue # 34504847x.noted: the roof above the gym is defective,water penetration @ ceiling. remedy:repair or replace.
May 10, 2007
Resolve - Hazardous
Reissue # 34504846y: noted: water penetrating through roof into 3fl girls rest room rms 305 & 312. remedy: repair or replace roof
May 10, 2007
Resolve - Non-hazardous
Exit doors not self-closing. location: all stairwells, all floors, (entire building) all interior corridor fire/smoke doors defects noted: loose hinges, doors are bent, sticking to floor. all defects causing
Feb 15, 2006
Resolve - Non-hazardous
Failure to maintain, in that the roof of the 4th floor gym is defective. allowing water to penetrate through. remedy: make all necessary repairs to prevent water to enter.
Feb 15, 2006
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1938
- Floors
- 4
- Residential units
- —
- Building area
- 79,330 ft²
- Lot area
- 84,000 ft²
- Zoning
- R4-1
- Community board
- 315
- Council district
- 48
- Block / lot
- 6821 / 244
- Assessed value
- $11,604,600
- Landmark / historic district
- No
Questions about 1701 Avenue S
Who owns 1701 Avenue S?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 1701 Avenue S have violations?
NYC HPD has no housing violations on record for this property.
Is 1701 Avenue S rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1701 Avenue S built?
City records list 1938 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.