890 Flatbush Avenue

Brooklyn, NY 11226BBL 3-05102-0001Map

Owner of record: Ref Dutch Ch

890 Flatbush Avenue is a religious facility built in 1850 in Brooklyn, 11226. The owner of record is Ref Dutch Ch. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
35
ECB violations
20
HPD complaints
8

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 35

  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 6, 2021

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 2, 2020

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 2, 2020

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Feb 5, 2020

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - active
Show 25 more ↓
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Apr 17, 2019

    Dob violation - dismissed
  • Construction other optional

    Failure to maintain building wall(s0 or appurentances remedy; provide structural stability engineers report, maintain exteri or bldgwall

    Sep 20, 2011

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 10, 1997

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 10, 1997

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 10, 1997

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - active
  • Emergency none

    Egncy-emergency none

    Jul 15, 1994

    Dob violation - active
  • Emergency none

    Egncy-emergency none

    Apr 7, 1994

    Dob violation - active
  • Construction other optional

    C-construction other optional

    Dec 19, 1990

    Vw-violation work without permit - active
  • Construction other optional

    C-construction other optional

    Dec 19, 1990

    Vw-violation work without permit - active

ECB violations · 20

  • Class - 1

    Failure to maintain bldg in code compliant manner. noted: at the roof level;the steeple is out if plumb & is leaning towards flatbush avenue. creating a hazardous condition to the public. obtain an engineers re

    Jan 29, 2021 · Penalty $6,250

    Resolve
  • Class - 1

    Failure to maintain bldg in code compliant manner. noted: at roof level church steeple out at plum leaning outwards towards flatbush ave. previous ecb#35465462m. remedy: repair &/or replace.

    Oct 13, 2020 · Penalty $3,125

    Resolve
  • Class - 1

    Failure to maintain bldg in code compliant manner. noted: the church located at the corner of flatbush & church ave;the steeple is out of plumb & is leaning towards flatbush ave. creating a hazardous condition

    Feb 29, 2020 · Penalty $3,125

    Resolve
  • Class - 1

    Failure to maintain building wall(s) or appurtenances. noted:church located at corner of flatbush ave&church ave has church steeple leaning towards flatbush ave. remedy:maintain exterior. provide lic. engineer

    Jan 6, 2020 · Penalty $12,500

    Active
  • Class - 2

    Failure to provide project information panel at jobs site. note: at time of inspection of a 2 story building with sidewalk shed and scaffold erection on roof. i observed that there were no information panel

    Nov 16, 2019 · Penalty $3,125

    Resolve
  • Class - 1

    Netting on scaffold not maintained. noted: at time of inspection of a 2 story alt 3 type building with sws and supported scaffolding erections, i observed that the netting on supported scaffold was not maintain

    Nov 16, 2019 · Penalty $6,250

    Resolve
  • Class - 2

    Temporary construction equipment on site-expired permit. at time of inspection i observed supported scaffold 96ft high in place w/ expired permit. non compliant. job#340528735. remedy:comply to code. renew perm

    Jan 24, 2019 · Penalty $1,250

    Active
  • Class - 2

    Failure to obtain a temporary construction permit prior to installation/use of temporary construction equipment. at time of inspection i observed construction fence in place w/ no permit. non compliant. remedy:

    Jan 24, 2019 · Penalty $1,250

    Active
  • Class - 2

    Pedestrian protection does not meet code specifications. at time of inspection i observed sidewalk shed in place. failure to provide protective caps for bolts causing an unsafe condition for pedestrians. bolts

    Jan 24, 2019 · Penalty $2,400

    Active
  • Class - 2

    Temporary construction equipment on site-expired permit. at time of inspection i observed sidewalk shed in place with expired permit. job#340528708 remedy: comply with code/renew permit

    Jan 24, 2019 · Penalty $6,250

    Active
Show 10 more ↓
  • Class - 1

    3314.1 at time of inspection i observed supported scaffold in place 96ft high. failure to maintain debris netting on scaffold loose and damaged at exp#1,exp#2,exp#3 exp#4 causing an unsafe and hazardous conditi

    Jan 24, 2019 · Penalty $12,500

    Active
  • Non-hazardous

    20m7/2x10/25d6/34q3/41e10/8v1/36w6 20-m)car door vision panel. 41-e)selector tape.

    Dec 22, 2004 · Penalty $350

    Resolve
  • Non-hazardous

    36/ 49/ 4b/ no pig tails on controlls low water out off not wired up

    Sep 4, 2001 · Penalty $1,300

    Active
  • Non-hazardous

    36/ 4b/ 49/ no pig tailes in controlls low wster cut off not wired up

    Sep 4, 2001 · Penalty $1,300

    Active
  • Non-hazardous

    19b/ 49/ install check value ( back flow preventor)

    Sep 4, 2001 · Penalty $350

    Active
  • Non-hazardous

    Work without permit: 1 steel plates const at reer of roof & rear of premises obstruting egress doors at rear of 892, 894, 896, 898, 902 - flatbush ave. commercial stores 2 cell windows sealed at 2nd sty with ma

    Dec 19, 1990 · Penalty $860

    Resolve
  • Non-hazardous

    Work without permit. mechanical conveyor belt constructed in stair well from 1st to 2nd sty obstruting egress from 2nd sty to street south side of premises remedy: obtain permits & approvals from this departmen

    Dec 19, 1990

    Active
  • Hazardous

    Boiler room covered with soot inadequate ventilation install fresh air vent & exhaust vent to outdoor breeching cleanout door defective not secure. remove paints and all flamable liquids from boiler room

    Sep 6, 1988 · Penalty $150

    Active
  • Hazardous

    Boiler room covered with soot inadequate ventilation install fresh air vent & exhaust vent to outdoors breeching cleanout door not secure remove paint and all flamable liquids from boiler rm not a storage room

    Sep 6, 1988 · Penalty $35

    Active
  • Hazardous

    Inadequate ventilation install fresh air & exhaust vent to outdoors 71/2 horsepower organ vaccum motor drawing air hot water connections corroded

    Sep 6, 1988 · Penalty $35

    Active

Complaints

  • Heat/hot water

    Apartment only

    Jan 16, 2022 · Apt 5J

    Close
  • Electric

    No lighting

    Oct 5, 2015 · Apt 309

    Close
  • Water leak

    Slow leak

    Oct 5, 2015 · Apt 309

    Close
  • Door/window

    Door

    Oct 5, 2015 · Apt 309

    Close
  • Door/window

    Door frame

    Oct 5, 2015 · Apt 309

    Close
  • Door/window

    Door

    Oct 5, 2015 · Apt 309

    Close
  • Door/window

    Door frame

    Oct 5, 2015 · Apt 309

    Close
  • Door/window

    Door

    Oct 5, 2015 · Apt 309

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Religious facility (M1)
Year built
1850
Floors
2
Residential units
—
Building area
24,800 ft²
Lot area
39,039 ft²
Zoning
R7A
Community board
314
Council district
40
Block / lot
5102 / 1
Assessed value
$2,941,650
Landmark / historic district
INDIVIDUAL LANDMARK

Questions about 890 Flatbush Avenue

Who owns 890 Flatbush Avenue?

The owner of record in NYC Department of City Planning PLUTO data is Ref Dutch Ch.

Does 890 Flatbush Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 890 Flatbush Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 890 Flatbush Avenue built?

City records list 1850 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.