599 Utica Avenue

Brooklyn, NY 11203BBL 3-04604-0052Map

Owner of record: Saanya Hospitality LLC

599 Utica Avenue is a hotel built in 2004 in Brooklyn, 11203. The owner of record is Saanya Hospitality LLC. HPD has recorded 9 housing violations here, most recently on November 18, 2025.

HPD violations
9
DOB violations
16
ECB violations
25
HPD complaints
10

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
Last violation Nov 18, 2025

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 9

  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 18, 2025

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 17, 2024

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 31, 2023

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 10, 2022

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 20, 2021

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Oct 29, 2018

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Dec 12, 2017

    Closed — Violation dismissed
  • C

    Provide hot water at all hot water fixtures in the entire apartment located at apt 506, 5th story, 2nd apartment from west at north

    Dec 16, 2016 · Apt 506

    Closed — Violation closed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 30, 2016

    Closed — Violation dismissed

DOB building violations · 16

  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 23, 2018

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 21, 2018

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 18, 2017

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 18, 2017

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 18, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 17, 2014

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
Show 6 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 4, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 8, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 3, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 3, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 20, 2006

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed

ECB violations · 25

  • Class - 1

    Failure to maintain building in code-compliant manner. observed hole penetrations throughout it rooms and sprinkler room. located basement., repair and/replace

    Jun 30, 2026 · Penalty $2,500

    Active
  • Class - 1

    Class 1 c/u: door zone restrictor inoperative as per asme a17.1/csa b44. this condition compromises door safety and creates a hazard requiring a cease-use order. remedy: restore proper door zone restrictor oper

    Jun 30, 2026 · Penalty $1,280

    Active
  • Class - 1

    Failure to maintain building in code-compliant manner. observed suv gas powered vehicle, obstructing emergency exit leading from basement., repair and/replace

    Jun 30, 2026 · Penalty $2,500

    Active
  • Class - 2

    Failure to maintain building in code compliant manner. class 2 items: maintenance log missing in the machine room, perform routine maintenance and provide an up-to-date maintenance log. in car communication ino

    Jul 24, 2024 · Penalty $312

    Resolve
  • Class - 2

    Hot water heater #3 is defective/hot water heater#3 is missing weather cap at top of flue/hot water heater#6 is defective, maintain boiler; correct violation and submit the certificate of correction

    Sep 15, 2021 · Penalty $625

    Resolve
  • Class - 2

    Provide a code compliant shackle for the hoist ropes and the governor cable. file for a test (code: 2.20.9.5 wedge rope sockets. wedge socket assemblies shall be of a design as shown in fig. 2.20.9.5, and shall

    Jul 14, 2021 · Penalty $310

    Resolve
  • Class - 1

    Class 1 : no door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm

    Dec 22, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    52k2 hoist cables rusted clean and monitor condition.

    Oct 18, 2018 · Penalty $655

    Resolve
  • Class - 1

    Failure to maintain bldg in code compliant manner. in cellar level mechanical room door no self closing, door to electrical room is missing room is a fire rated room. room has no rating w/out door & gas meter i

    Aug 14, 2018 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.observed on 08/14/18 at above address sprinkler head on the 2nd flr installed to deep into ceiling.rem:repair and or replace. photo taken

    Aug 14, 2018 · Penalty $625

    Resolve
Show 15 more ↓
  • Class - 1

    Failure to install grounding electrode conductor in accordance w/ section. observed the grounding electrode connected directly to main switch marked 3rd-4th flr. grounding electrode shall be installed onto a co

    Dec 19, 2017 · Penalty $4,800

    Resolve
  • Class - 2

    Failure to comply with the commissioner's order contained in summons/violation #35287056h issued 07/26/17 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. department records indica

    Oct 25, 2017 · Penalty $800

    Resolve
  • Class - 2

    Failure to comply w/the comm's order contained in sum/vio#35287056h issued on 07/26/17 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. 250.4 failure to install grounding conductor in accordance w/sectio

    Aug 30, 2017 · Penalty $800

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:no fire stoppingper bc 712.3;27-345.noted:observed at cellar level within the mechanical room(electrical room,gas meter room,sprinkler main)holes in ceiling

    Jul 26, 2017 · Penalty $530

    Resolve
  • Class - 1

    250.4 failure to install grounding electrical conductor in accordance with section.observed the grounding electrical connected directly to main switch marked 3rd -4th floor.grounding electrical shall be install

    Jul 26, 2017 · Penalty $8,000

    Resolve
  • Class - 1

    250.68 building ground clamp inaccessible. observed grounding conductor and conduit in area of water service pipe unable to verify connection or conditions due to installation of sprinkler and waste pipes block

    Jul 26, 2017 · Penalty $8,000

    Resolve
  • Class - 1

    Electrical work without a permit.observed exposed energized wires on rooftop which were previously connected to signs on exposures 1,2 and 4 which are the front left side and right side of building as your faci

    Jul 26, 2017 · Penalty $1,600

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:lack of emergency lighting for exits,exit discharges and public corridors per bc1006.1;27-542.note:inoperative emergency lights with battery back up at 3rd flr

    Feb 3, 2017 · Penalty $250

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.observed on 2/3/17 no inpsectors test gauge on upper most flr.rem:repair and or replace.

    Feb 3, 2017 · Penalty $500

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.observed on 2/3/17 no boiler records on file at the dob.rem:repair and or replace.

    Feb 3, 2017 · Penalty $500

    Resolve
  • Class - 2

    31j01,52k11,61b07,70o02,39o02,05x10. 05x10-front door restrictor need a new latch plate; 31j01-leveling slightly off (rust in the shaft); 52k11-ropes are rusty; 39002-car top is dirty; 61b07-company on mainline

    Jun 1, 2016

    Resolve
  • Class - 2

    40r09,17d06,10d06,17m07,41b07,70y02,08v01,08j01,46q03,37q03,14m07,05x10. 40r- remove non elevator material. 17/10d- secure where needed. 17m- provide where missing 41b- fire rating tag. 70y seal leaks. 08v- adj

    Dec 1, 2010

    Resolve
  • Class - 2

    70y10,70y02,77x10 77x-undercar light

    Jun 26, 2009 · Penalty $250

    Resolve
  • Hazardous

    41n09.12q03.39r09.66y02.17h11.17d06.10h11.71x10.08v01.09i10. 41n by passed fuse 12q unguarded cab lights 39r remove non elevator material 17h,d properly secure or replace hoistway gibs where needed 10m replace

    Feb 20, 2008 · Penalty $180

    Resolve
  • Non-hazardous

    Questionable construction in basement, steel is to be supported block/concrete wall (anchor on pressure plate) however, area in question is block wall in basement located on utica ave. side. block wall used for

    Jul 2, 2004 · Penalty $400

    Resolve

Complaints

  • Heat/hot water

    Entire building

    May 14, 2020 · Apt 408

    Close
  • Heat/hot water

    Entire building

    May 13, 2020 · Apt 506

    Close
  • Heat/hot water

    Entire building

    Dec 27, 2019 · Apt 513

    Close
  • Heat/hot water

    Entire building

    Dec 16, 2019 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Feb 1, 2019 · Apt 313

    Close
  • Electric

    Power outage

    Feb 1, 2019 · Apt 313

    Close
  • Heat/hot water

    Entire building

    Mar 19, 2018 · Apt 502

    Close
  • Electric

    No lighting

    Jan 10, 2017 · Apt 513

    Close
  • Heat/hot water

    Entire building

    Dec 16, 2016 · Apt 506

    Close
  • Nonconst

    Vermin

    Dec 16, 2011 · Apt 511

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hotel (H4)
Year built
2004
Floors
5
Residential units
—
Building area
23,000 ft²
Lot area
10,000 ft²
Zoning
C8-2
Community board
317
Council district
41
Block / lot
4604 / 52
Assessed value
$5,056,200
Landmark / historic district
No

HPD registration #386524, last renewed Jul 20, 2026.

Questions about 599 Utica Avenue

Who owns 599 Utica Avenue?

The owner of record in NYC Department of City Planning PLUTO data is Saanya Hospitality LLC.

Does 599 Utica Avenue have violations?

Yes. NYC HPD has recorded 9 housing violations at this property.

Is 599 Utica Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 599 Utica Avenue built?

City records list 2004 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.