1036 Sheffield Avenue
Brooklyn, NY 11207BBL 3-04411-0024Map
Owner of record: Bgflatlands LLC
1036 Sheffield Avenue is a hotel built in 1988 in Brooklyn, 11207. The owner of record is Bgflatlands LLC. HPD has recorded 4 housing violations here, most recently on November 26, 2024.
- HPD violations
- 4
- DOB violations
- 30
- ECB violations
- 44
- HPD complaints
- 13
What to know
No open immediately-hazardous violations among recent records.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 4
- IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 26, 2024
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 2, 2022
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Mar 2, 2022
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 13, 2021
Closed — Violation dismissed
DOB building violations · 30
- Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 5, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 5, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 5, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 5, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 26, 2024
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 21, 2024
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 20, 2024
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 16, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 13, 2020
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Feb 5, 2020
Dob violation - dismissed
Show 20 more ↓
- Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 3, 2017
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 26, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 10, 2014
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 22, 2013
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2010 inspection/test
Dec 13, 2011
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 8, 2011
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 27, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 31, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 24, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 28, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 22, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 29, 2004
Dob violation - resolved - Elevator elevatorrequired
3p7909
Aug 23, 2002
Dob violation - resolved - Elevator elevatorrequired
3p7909
Sep 6, 2001
Dob violation - resolved - Construction other optional
C-construction other optional
Apr 7, 1988
Vw*-violation - work w/o permit dismissed
ECB violations · 44
- Class - 2
Failure to comply with the commissioner's order to file a certificate of correction with the dept. of buildings for violation #39185425m, file a certificate of correction
Jun 9, 2026 · Penalty $6,250
Active - Class - 2
Failure to comply with the commissioner's order to file a certificate of correction for violation #39185426y, file a certificate of correction
Jun 9, 2026 · Penalty $3,125
Resolve - Class - 1
Electrical work without a permit. observed in the main electric rm one new panel installed with new conduits also new electric heaters installed in lobby and water main rm. the hw tank have new switches for pow
Apr 21, 2026 · Penalty $2,530
Active - Class - 1
Unapproved/unsafe/unsuitable electrical equipment, apparatus, materials, devices, appliances or wiring in use. observed in the elevator machine rm extension cord passing thru doorway. the elevator main disconne
Apr 21, 2026 · Penalty $1,630
Resolve - Class - 1
Failure to comply with the commissioner's order to obtain work permits for violation #39132555l. no permit on file to install gas fired water heaters., comply with commissioner's order
Feb 17, 2026 · Penalty $2,500
Resolve - Class - 2
Failure to comply with the commissioner's order to file a certificate of correction with the dept. of buildings for violation #39132557p, file a certificate of correction
Feb 17, 2026 · Penalty $3,125
Resolve - Class - 2
Exit door not self-closing. observed non self closing doors at all utility/ mechanical rooms located on throughout first floor. in an emergency all doors must function properly., repair/replace door
Dec 10, 2024
Resolve - Class - 1
Work without a permit. observed new gas piping to 2 gas fired water heaters and also to commercial laundry equipment ( dryer). no permits on file at the dob for the new gas work., obtain permit
Dec 10, 2024 · Penalty $2,500
Resolve - Class - 1
Observed gas leak on the 1 inch elbow to the water heater located on the main floor. as per 102.3 of the plumbing code installations, both existing and new, and parts thereof shall be maintained in proper opera
Dec 10, 2024 · Penalty $1,250
Resolve - Class - 1
Failure to maintain building in code-compliant manner. observed wall at exposure 1 inside the parking lot area. wall is protruding outward. potential overhead hazard., repair and/replace
Dec 10, 2024 · Penalty $1,250
Resolve
Show 34 more ↓
- Class - 1
Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed excessive unpermitted foam hole penetrations inhot water heater room. lo
Dec 10, 2024 · Penalty $2,500
Resolve - Class - 2
Observed pex piping ( red & blue) installed to slop sink. pex piping is not allowed for domestic use. pex can only be used for heat., obtainall permits
Dec 10, 2024 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code compliant manner. class 2 items: 1) excessive oil in the pit, seal the oil leak and clean the pit. 2) in car communication inoperative, repair.
Dec 9, 2024
Resolve - Class - 1
I observed the completion of the branch circuit wiring from the ground floor electrical room to the 4th kitchen to supply power for the food warmer. as per ecbs#39099395j, 96l and 97n the stop work order must b
Jun 17, 2024 · Penalty $5,000
Resolve - Class - 1
I noted in dob records the failure to obtain a permit for violations stated in ecb# 39099397n as pursuant to 28-201.1 and 1rcny 102-01 for electrical work without a permit., comply with commissioner's order; ob
Jun 17, 2024 · Penalty $6,280
Resolve - Class - 1
I observed in the fourth floor kitchen the installation of an outlet, junction box and emt raceway in the hallway from the ground floor electrical room to supply power for the food warmer. no permit on file for
Jun 17, 2024 · Penalty $4,000
Resolve - Class - 1
I observed in the front entrance the installation and secured extension cord passing through the drop ceiling to supply power to the security desks near the windows. as per ec 400.8 no flexible cord shall be us
Nov 15, 2023 · Penalty $1,600
Resolve - Class - 1
I observed the installation on branch circuit wiring from the garage area to the third floor passageway en-route to the 4th floor kitchen to supply power to a new food warmer oven. this is an immediate hazard a
Nov 14, 2023 · Penalty $800
Resolve - Class - 1
I observed mr. ravinder singh in the process of installing bx cabling from the the garage area to the 4th floor kitchen to supply power for a new food warmer. as mr singh is not a licensed electrical contractor
Nov 14, 2023 · Penalty $4,800
Resolve - Class - 1
I observed ravinder singh a maintenance worker in the midst of installing bx cabling from the garage area to the fourth floor kitchen to supply power to a new food warmer. mr. singh is not a licensed electrical
Nov 14, 2023 · Penalty $4,800
Resolve - Class - 2
Hole penetration found in elevator and boiler mechanical rooms, ground level., maintain exterior building wall
Oct 16, 2023
Resolve - Class - 2
Illegal hardware, (sliding lock latches) installed on exit doors throughout building., provide legal hardware
Oct 16, 2023
Resolve - Class - 2
Excessive foam in sprinkler room ground level., repair and/or replace
Oct 16, 2023
Resolve - Class - 2
Observed in the laundry area located on ground floor gas piping not being supported properly. the gas piping was being supported with black wire not with a hanger as per pc 308.4 structural attachment. hangers
Oct 16, 2023
Resolve - Class - 2
I observed in the laundry/ boiler room failure to maintain access / workspace in front of the electrical panel at the entrance of the room. the panel is blocked by materials and appliances. photos taken, provid
Jan 24, 2023
Resolve - Class - 2
I observed the installation wall mounted led lights in the parking lot, there isno electrical permit in dob records that covers this installation. photos taken, obtain permit; obtain permit and call for inspect
Jan 24, 2023
Resolve - Class - 2
I observed in the laundry/ boiler room the installation of a black flexible rubber cord supplying power to the parking lot lights. flexible cords are not permitted to be used as permanent wiring per 400.8.; ec
Jan 24, 2023
Resolve - Class - 2
I observed in the front of the premises a receptacle not of the gfci type nor gfci protected,, also noted in the rear parking lot the use of pvc conduit to supply power to the led wall lights., provide approved
Jan 24, 2023 · Penalty $1,000
Resolve - Class - 2
#2 hot water heater safety valve inlet and outlet piping is incorrect+it is not125psi/#1 hwh draftstat defect/hw temperature gauge defect/expansion tank psi gauge defect/mixing valve cold water thermo loop is n
Sep 28, 2021 · Penalty $655
Resolve - Class - 2
Failure to maintain building in code compliant manner.observed at first floor exp #2 and #3 perimeter walls or enclosure walls have several horizontal and vertical cracks with lengths between 10 to 60 ft openin
Aug 27, 2021
Resolve - Class - 2
Failure to maintain building in code-compliant manner.not fire stopping per bc 712.3;27-345.observed at first floor mechanical rooms several holes in concrete slab walls due to penetration of pipes and cables w
Aug 27, 2021
Resolve - Class - 1
14m7, (c/u 42g11); 67x10: (14,m,7) in car mirror missing provide. (42,g,11) improper fuses on the controller four fuses bypass. (67,x,10) incar phone not working
Oct 31, 2019 · Penalty $1,250
Resolve - Class - 2
I observed in the ground floor laundry area the installation of convenience receptacle outlets not of the gfci type nor gfci protected within 6 feet of a sink., install gfc1 protection
Aug 28, 2019 · Penalty $1,200
Resolve - Class - 1
I observed on the ground floor laundry area the improper wiring of an equipment disconnect for a gas dryer. i observed the wiring of the load side terminals with the incoming feed and the line side terminals to
Aug 28, 2019
Resolve - Class - 2
Failure to property connect cnductors to terminals. observed in the laundry area, the installation of equipment disconnects (fused) armor ed cables to supply power to washing and drying units. the branch cir
Mar 11, 2019
Resolve - Class - 1
Failure to maintain bldg walls or appurtenances. noted: at roof,cable tray covers are loose from trays & in danger of flying off of roof. cable trays are for telephone communication cables. remedy: maintain ext
Mar 11, 2019 · Penalty $2,500
Resolve - Class - 2
Exit door not self closing. noted: at bulkhead,door to roof not self closing. also,at 1st sty in laundry em,exit door to parking lot not self closing. remedy: repair/replace door.
Mar 11, 2019
Resolve - Class - 1
Failure to protect against deteriorating agents. observed in electrical equipment room located in parking lot area, a continous flow of water above sevice disconnect and metering equipment causing corrosion and
Mar 11, 2019 · Penalty $1,600
Resolve - Class - 1
Failure to maintian bldg in code compliant manner. noted: in electrical panel room,water penetrating ceiling. water pentrating ceiling w/active flow & dripping directly onto pqanels & waters. remedy: repair &/o
Mar 11, 2019 · Penalty $1,250
Resolve - Class - 1
Electrical work w/o a permit. observed on 1st floor, laundry area. theinstallation of branch ckt wiring, equipment disconnects for washing macines and dryers. no active or previously issued permit covers the
Mar 11, 2019 · Penalty $800
Resolve - Class - 2
Illegal storage of non-elevator items in machine room, maintenance log missing detailed info, missing controller prints, secure spare controller wires, missing cat one tag, oil and water in pit, worn cab mirro
Dec 11, 2018
Resolve - Class - 1
Cease use. 70y2,81y13,38i11. (70y)pit has excessive oil,clean. (81y)piston is leaking,seal. (38i)traveling cable near pit has cut through the moulation,replace.
Oct 31, 2017 · Penalty $1,000
Resolve - Class - 1
Residence altered for occupancy as a dwelling for more than the legally approved # of families.dob record indicates premises to be legally approved for a (2) family store,cellar storage/boiler room, now premise
Oct 21, 2010
Resolve - Class - 2
40b09,40r09,60q03,48bb05,69m07,70o02,77q03,34o02,70m07,17o06,10h11,100d06,34b03,67x10,97x10.40br access blocked & non elevator material in mr,60q-install lightguards,48bb-expired pressure test tag,69m-code dat
Sep 18, 2009 · Penalty $500
Resolve
Complaints
- Heat/hot water
Entire building
Oct 15, 2025 · Apt 304
Close - Heat/hot water
Entire building
Feb 24, 2024 · Apt 311
Close - Heat/hot water
Entire building
Dec 14, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Mar 14, 2023 · Apt BLDG
Close - Unsanitary condition
Pests
Aug 27, 2019 · Apt 1
Close - Unsanitary condition
Pests
Aug 27, 2019 · Apt 1
Close - Flooring/stairs
Floor
Aug 27, 2019 · Apt 1
Close - Door/window
Window frame
Aug 27, 2019 · Apt 1
Close - Plumbing
Bathtub/shower
Jun 5, 2013 · Apt 301
Close - Plumbing
Shower-stall
Jun 5, 2013 · Apt 301
Close
Show 3 more ↓
- Heating
Heat related
Jan 25, 2005 · Apt 1
Close - Heating
Heat related
Oct 23, 2004 · Apt 1
Close - Heating
Heat related
Oct 22, 2004 · Apt 1
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Hotel (H4)
- Year built
- 1988
- Floors
- 4
- Residential units
- —
- Building area
- 20,200 ft²
- Lot area
- 15,500 ft²
- Zoning
- M1-1
- Community board
- 305
- Council district
- 42
- Block / lot
- 4411 / 24
- Assessed value
- $3,617,100
- Landmark / historic district
- No
HPD registration #389511, last renewed Aug 20, 2025.
Questions about 1036 Sheffield Avenue
Who owns 1036 Sheffield Avenue?
The owner of record in NYC Department of City Planning PLUTO data is Bgflatlands LLC.
Does 1036 Sheffield Avenue have violations?
Yes. NYC HPD has recorded 4 housing violations at this property.
Is 1036 Sheffield Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1036 Sheffield Avenue built?
City records list 1988 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.