Owner of record: Bgflatlands LLC

1036 Sheffield Avenue is a hotel built in 1988 in Brooklyn, 11207. The owner of record is Bgflatlands LLC. HPD has recorded 4 housing violations here, most recently on November 26, 2024.

HPD violations
4
DOB violations
30
ECB violations
44
HPD complaints
13

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
Last violation Nov 26, 2024

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 4

  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 26, 2024

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 2, 2022

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Mar 2, 2022

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 13, 2021

    Closed — Violation dismissed

DOB building violations · 30

  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 5, 2025

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 5, 2025

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 5, 2025

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 5, 2025

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 26, 2024

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Aug 21, 2024

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 20, 2024

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 16, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 13, 2020

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Feb 5, 2020

    Dob violation - dismissed
Show 20 more ↓
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 3, 2017

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2016 inspection/test

    Sep 15, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 26, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 10, 2014

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 22, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 8, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 27, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 31, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 24, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 28, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 22, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 29, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    3p7909

    Aug 23, 2002

    Dob violation - resolved
  • Elevator elevatorrequired

    3p7909

    Sep 6, 2001

    Dob violation - resolved
  • Construction other optional

    C-construction other optional

    Apr 7, 1988

    Vw*-violation - work w/o permit dismissed

ECB violations · 44

  • Class - 2

    Failure to comply with the commissioner's order to file a certificate of correction with the dept. of buildings for violation #39185425m, file a certificate of correction

    Jun 9, 2026 · Penalty $6,250

    Active
  • Class - 2

    Failure to comply with the commissioner's order to file a certificate of correction for violation #39185426y, file a certificate of correction

    Jun 9, 2026 · Penalty $3,125

    Resolve
  • Class - 1

    Electrical work without a permit. observed in the main electric rm one new panel installed with new conduits also new electric heaters installed in lobby and water main rm. the hw tank have new switches for pow

    Apr 21, 2026 · Penalty $2,530

    Active
  • Class - 1

    Unapproved/unsafe/unsuitable electrical equipment, apparatus, materials, devices, appliances or wiring in use. observed in the elevator machine rm extension cord passing thru doorway. the elevator main disconne

    Apr 21, 2026 · Penalty $1,630

    Resolve
  • Class - 1

    Failure to comply with the commissioner's order to obtain work permits for violation #39132555l. no permit on file to install gas fired water heaters., comply with commissioner's order

    Feb 17, 2026 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to comply with the commissioner's order to file a certificate of correction with the dept. of buildings for violation #39132557p, file a certificate of correction

    Feb 17, 2026 · Penalty $3,125

    Resolve
  • Class - 2

    Exit door not self-closing. observed non self closing doors at all utility/ mechanical rooms located on throughout first floor. in an emergency all doors must function properly., repair/replace door

    Dec 10, 2024

    Resolve
  • Class - 1

    Work without a permit. observed new gas piping to 2 gas fired water heaters and also to commercial laundry equipment ( dryer). no permits on file at the dob for the new gas work., obtain permit

    Dec 10, 2024 · Penalty $2,500

    Resolve
  • Class - 1

    Observed gas leak on the 1 inch elbow to the water heater located on the main floor. as per 102.3 of the plumbing code installations, both existing and new, and parts thereof shall be maintained in proper opera

    Dec 10, 2024 · Penalty $1,250

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner. observed wall at exposure 1 inside the parking lot area. wall is protruding outward. potential overhead hazard., repair and/replace

    Dec 10, 2024 · Penalty $1,250

    Resolve
Show 34 more ↓
  • Class - 1

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed excessive unpermitted foam hole penetrations inhot water heater room. lo

    Dec 10, 2024 · Penalty $2,500

    Resolve
  • Class - 2

    Observed pex piping ( red & blue) installed to slop sink. pex piping is not allowed for domestic use. pex can only be used for heat., obtainall permits

    Dec 10, 2024 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. class 2 items: 1) excessive oil in the pit, seal the oil leak and clean the pit. 2) in car communication inoperative, repair.

    Dec 9, 2024

    Resolve
  • Class - 1

    I observed the completion of the branch circuit wiring from the ground floor electrical room to the 4th kitchen to supply power for the food warmer. as per ecbs#39099395j, 96l and 97n the stop work order must b

    Jun 17, 2024 · Penalty $5,000

    Resolve
  • Class - 1

    I noted in dob records the failure to obtain a permit for violations stated in ecb# 39099397n as pursuant to 28-201.1 and 1rcny 102-01 for electrical work without a permit., comply with commissioner's order; ob

    Jun 17, 2024 · Penalty $6,280

    Resolve
  • Class - 1

    I observed in the fourth floor kitchen the installation of an outlet, junction box and emt raceway in the hallway from the ground floor electrical room to supply power for the food warmer. no permit on file for

    Jun 17, 2024 · Penalty $4,000

    Resolve
  • Class - 1

    I observed in the front entrance the installation and secured extension cord passing through the drop ceiling to supply power to the security desks near the windows. as per ec 400.8 no flexible cord shall be us

    Nov 15, 2023 · Penalty $1,600

    Resolve
  • Class - 1

    I observed the installation on branch circuit wiring from the garage area to the third floor passageway en-route to the 4th floor kitchen to supply power to a new food warmer oven. this is an immediate hazard a

    Nov 14, 2023 · Penalty $800

    Resolve
  • Class - 1

    I observed mr. ravinder singh in the process of installing bx cabling from the the garage area to the 4th floor kitchen to supply power for a new food warmer. as mr singh is not a licensed electrical contractor

    Nov 14, 2023 · Penalty $4,800

    Resolve
  • Class - 1

    I observed ravinder singh a maintenance worker in the midst of installing bx cabling from the garage area to the fourth floor kitchen to supply power to a new food warmer. mr. singh is not a licensed electrical

    Nov 14, 2023 · Penalty $4,800

    Resolve
  • Class - 2

    Hole penetration found in elevator and boiler mechanical rooms, ground level., maintain exterior building wall

    Oct 16, 2023

    Resolve
  • Class - 2

    Illegal hardware, (sliding lock latches) installed on exit doors throughout building., provide legal hardware

    Oct 16, 2023

    Resolve
  • Class - 2

    Excessive foam in sprinkler room ground level., repair and/or replace

    Oct 16, 2023

    Resolve
  • Class - 2

    Observed in the laundry area located on ground floor gas piping not being supported properly. the gas piping was being supported with black wire not with a hanger as per pc 308.4 structural attachment. hangers

    Oct 16, 2023

    Resolve
  • Class - 2

    I observed in the laundry/ boiler room failure to maintain access / workspace in front of the electrical panel at the entrance of the room. the panel is blocked by materials and appliances. photos taken, provid

    Jan 24, 2023

    Resolve
  • Class - 2

    I observed the installation wall mounted led lights in the parking lot, there isno electrical permit in dob records that covers this installation. photos taken, obtain permit; obtain permit and call for inspect

    Jan 24, 2023

    Resolve
  • Class - 2

    I observed in the laundry/ boiler room the installation of a black flexible rubber cord supplying power to the parking lot lights. flexible cords are not permitted to be used as permanent wiring per 400.8.; ec

    Jan 24, 2023

    Resolve
  • Class - 2

    I observed in the front of the premises a receptacle not of the gfci type nor gfci protected,, also noted in the rear parking lot the use of pvc conduit to supply power to the led wall lights., provide approved

    Jan 24, 2023 · Penalty $1,000

    Resolve
  • Class - 2

    #2 hot water heater safety valve inlet and outlet piping is incorrect+it is not125psi/#1 hwh draftstat defect/hw temperature gauge defect/expansion tank psi gauge defect/mixing valve cold water thermo loop is n

    Sep 28, 2021 · Penalty $655

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.observed at first floor exp #2 and #3 perimeter walls or enclosure walls have several horizontal and vertical cracks with lengths between 10 to 60 ft openin

    Aug 27, 2021

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.not fire stopping per bc 712.3;27-345.observed at first floor mechanical rooms several holes in concrete slab walls due to penetration of pipes and cables w

    Aug 27, 2021

    Resolve
  • Class - 1

    14m7, (c/u 42g11); 67x10: (14,m,7) in car mirror missing provide. (42,g,11) improper fuses on the controller four fuses bypass. (67,x,10) incar phone not working

    Oct 31, 2019 · Penalty $1,250

    Resolve
  • Class - 2

    I observed in the ground floor laundry area the installation of convenience receptacle outlets not of the gfci type nor gfci protected within 6 feet of a sink., install gfc1 protection

    Aug 28, 2019 · Penalty $1,200

    Resolve
  • Class - 1

    I observed on the ground floor laundry area the improper wiring of an equipment disconnect for a gas dryer. i observed the wiring of the load side terminals with the incoming feed and the line side terminals to

    Aug 28, 2019

    Resolve
  • Class - 2

    Failure to property connect cnductors to terminals. observed in the laundry area, the installation of equipment disconnects (fused) armor ed cables to supply power to washing and drying units. the branch cir

    Mar 11, 2019

    Resolve
  • Class - 1

    Failure to maintain bldg walls or appurtenances. noted: at roof,cable tray covers are loose from trays & in danger of flying off of roof. cable trays are for telephone communication cables. remedy: maintain ext

    Mar 11, 2019 · Penalty $2,500

    Resolve
  • Class - 2

    Exit door not self closing. noted: at bulkhead,door to roof not self closing. also,at 1st sty in laundry em,exit door to parking lot not self closing. remedy: repair/replace door.

    Mar 11, 2019

    Resolve
  • Class - 1

    Failure to protect against deteriorating agents. observed in electrical equipment room located in parking lot area, a continous flow of water above sevice disconnect and metering equipment causing corrosion and

    Mar 11, 2019 · Penalty $1,600

    Resolve
  • Class - 1

    Failure to maintian bldg in code compliant manner. noted: in electrical panel room,water penetrating ceiling. water pentrating ceiling w/active flow & dripping directly onto pqanels & waters. remedy: repair &/o

    Mar 11, 2019 · Penalty $1,250

    Resolve
  • Class - 1

    Electrical work w/o a permit. observed on 1st floor, laundry area. theinstallation of branch ckt wiring, equipment disconnects for washing macines and dryers. no active or previously issued permit covers the

    Mar 11, 2019 · Penalty $800

    Resolve
  • Class - 2

    Illegal storage of non-elevator items in machine room, maintenance log missing detailed info, missing controller prints, secure spare controller wires, missing cat one tag, oil and water in pit, worn cab mirro

    Dec 11, 2018

    Resolve
  • Class - 1

    Cease use. 70y2,81y13,38i11. (70y)pit has excessive oil,clean. (81y)piston is leaking,seal. (38i)traveling cable near pit has cut through the moulation,replace.

    Oct 31, 2017 · Penalty $1,000

    Resolve
  • Class - 1

    Residence altered for occupancy as a dwelling for more than the legally approved # of families.dob record indicates premises to be legally approved for a (2) family store,cellar storage/boiler room, now premise

    Oct 21, 2010

    Resolve
  • Class - 2

    40b09,40r09,60q03,48bb05,69m07,70o02,77q03,34o02,70m07,17o06,10h11,100d06,34b03,67x10,97x10.40br access blocked & non elevator material in mr,60q-install lightguards,48bb-expired pressure test tag,69m-code dat

    Sep 18, 2009 · Penalty $500

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Oct 15, 2025 · Apt 304

    Close
  • Heat/hot water

    Entire building

    Feb 24, 2024 · Apt 311

    Close
  • Heat/hot water

    Entire building

    Dec 14, 2023 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Mar 14, 2023 · Apt BLDG

    Close
  • Unsanitary condition

    Pests

    Aug 27, 2019 · Apt 1

    Close
  • Unsanitary condition

    Pests

    Aug 27, 2019 · Apt 1

    Close
  • Flooring/stairs

    Floor

    Aug 27, 2019 · Apt 1

    Close
  • Door/window

    Window frame

    Aug 27, 2019 · Apt 1

    Close
  • Plumbing

    Bathtub/shower

    Jun 5, 2013 · Apt 301

    Close
  • Plumbing

    Shower-stall

    Jun 5, 2013 · Apt 301

    Close
Show 3 more ↓
  • Heating

    Heat related

    Jan 25, 2005 · Apt 1

    Close
  • Heating

    Heat related

    Oct 23, 2004 · Apt 1

    Close
  • Heating

    Heat related

    Oct 22, 2004 · Apt 1

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hotel (H4)
Year built
1988
Floors
4
Residential units
—
Building area
20,200 ft²
Lot area
15,500 ft²
Zoning
M1-1
Community board
305
Council district
42
Block / lot
4411 / 24
Assessed value
$3,617,100
Landmark / historic district
No

HPD registration #389511, last renewed Aug 20, 2025.

Questions about 1036 Sheffield Avenue

Who owns 1036 Sheffield Avenue?

The owner of record in NYC Department of City Planning PLUTO data is Bgflatlands LLC.

Does 1036 Sheffield Avenue have violations?

Yes. NYC HPD has recorded 4 housing violations at this property.

Is 1036 Sheffield Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1036 Sheffield Avenue built?

City records list 1988 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.