1 Wells Street

Brooklyn, NY 11208BBL 3-04155-0075Map

Owner of record: NYC Department Of Education

1 Wells Street is a school building built in 1940 in Brooklyn, 11208. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
111
ECB violations
66
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 111

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 20, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 20, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 16, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 16, 2020

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 16, 2020

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 24, 2019

    Dob violation - active
Show 40 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 24, 2019

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 4, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 4, 2018

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 4, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 3, 2017

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 16, 2016

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 8, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 8, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 8, 2015

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 11, 2014

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 15, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 15, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 16, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 16, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 28, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    Removed

    May 28, 2010

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatorrequired

    Removed

    May 28, 2010

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 28, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 30, 2009

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 30, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 30, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 30, 2009

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 30, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 30, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2008

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2008

    Dob violation - resolved

ECB violations · 66

  • Class - 2

    Reissue:35720945m-exit door not self closing.noted:at exit 14,13,2 & 37,8 doors.rem:comply with code.

    Mar 30, 2026 · Penalty $1,562

    Active
  • Class - 2

    Reissue:35700949k-failure to maintain building in code-compliant manner.exit#11,12 stair d 1st floor.handrail missing 317 door closer missing.rem:comply with code.

    Mar 30, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at exit 11-12 stair d at first floor hand railing missing. also, class room door #317, door closer missing. remedy: replace door/repair. provide han

    Jul 14, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted: at exit 14, exit 13, exit 2-3, exit7-8, exit doors are not self-closing and need excessive force to open.remedy: repair/replace door.

    Jul 14, 2025 · Penalty $625

    Active
  • Class - 1

    Failure to institute adequate safety measures. note: at the rear transit tech career & technicial high school, job site erecting supported scaffold under permit b00768992-11-sf. during delivery of scaffolding a

    Feb 14, 2023

    Resolve
  • Class - 2

    Exit door not self-closing.noted observed during inspection exterior exit door#4 and fire proof self-closing door at cafeteria entrance werenot operational/self-closing due to racking/rubbing.remedy:repair and

    Feb 2, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted observed during inspection of generator in transit training room,hose broken leaking antifreeze.remedy:repair and/or repalce.

    Feb 2, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue35546505h failure to maintain bldg in codecompliant manner:illumination for exits,exitd discharge&public corridor per bc1006.1;27-381noted:@3fl staircasee,2fl staircasea&1fl by rm119,121 exit sign not wo

    Feb 11, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35546506j exit door not selfclosing noted:staircasef next to 331,staircaseb 2fl,staircasee 2fl&staircasea 1fl.also smoke doors in corridor not selfclosing@2fl next to rm225&girls lockerrm.repair/replace

    Feb 11, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at the roof level,adjacent to the elevator machine room(fountain ave side)the parapet wall has a running crack from the ground to the top of the parapet

    Mar 29, 2021 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at the roof level;the bulkhead adjacent to elevator machine room has running step cracks & is missing mortar in various areas throughout. remedy: repair

    Mar 29, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: the doors tothe roof at stair h bby room 430 are not working properly. remedy: repair &/or replace.

    Mar 29, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner;illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: at the 3rd fl stair e exit sign by 342,2nd fl stair a by 205,& the 1st fl

    Mar 29, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing. noted: at the 3rd fl girls locker room,stair f by 331b,1st fl smoke by stair d 153,auditorium left rear exteriorexit door#13,smoke by 127 & at the main entrance to the bldg;the doors

    Mar 29, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing noted 4th floor exit door by stair (d) is not self closing 3rd floor hallway exit to gym door is not self close also 1st floor exit door 9,10 to leading "rail car lab" all door is def

    Jun 18, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissued 35311831r (1/26/18) water penetration onto ceiling and walls causing plasters spalling at weight room on 4th floor probable cause from facade or roofs leaks. rmdy: repair and/or replace.

    Feb 12, 2019

    Resolve
  • Class - 2

    Reissued #35311832z (1/26/18) water penetrating through ceiling from 4th floor facade at weight rooms. rmdy: repair and/or replace.

    Feb 12, 2019

    Resolve
  • Class - 2

    Re-issue 335260676z.weight rm has water peneteration on ceilings and walls.rem:comply w/summons.

    Jan 26, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.water penetrating from facade into 4th fl weight rm.rem:comply w/summons.

    Jan 26, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.at 1st fl exit 1-a1,exit doors blocked by security desk,security personell and chairs.rem:comply w/summons.

    Jan 26, 2018

    Resolve
  • Class - 2

    Reissue#35177621y failure to maintain bldg in code compliant manner. noted: 4th fl @ wt-room water penetration causing spalling plaster. remedy: repair &/or replace.

    Apr 5, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ 4th flr @ wt-room water penetration causing spalling plaster. rem: maintain exterior bldg wall.

    Apr 13, 2016

    Resolve
  • Class - 2

    Reissue 35107754y.failure to maintain bldg in code-compliant manner.inroom 317 fl is buckled & raised along radiator side of room creating trip hazard.rem:repair/replace flooring.

    Jun 12, 2015

    Resolve
  • Class - 2

    Reissue 35107755x.failure to maintain roof cage door.roof cage doors @ stair"d" & f"are in disrepair & bent.rem:replace cage doors.

    Jun 12, 2015

    Resolve
  • Class - 2

    Reissue 355012363p.exit doors not self closing:the following doors areracked:3rd fl stair"d";r1;stair"e"@ 1st fl,exit 4 @ 1st fl,stair b @ 1st fl,exit 7/8 @ 1st fl,stair"d"exit 11/12.rem:repair/replace doors.

    Jun 12, 2015

    Resolve
  • Class - 2

    27-371(b)reissue 35107753m,vision panels:use of prohibited plexiglass @ the following auditrium stair f/g.weight room smoke corridor doors on3rd & 2nd fl door r1,219b,219a,smoke corridor doors @ bsmt.rem:provid

    Jun 12, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg code compliant manner.failure to provide wired vision panels per 27-371(b)noted,following doors do not have wired glass auditorium stair f/g weight room smoke corridor doors on 2nd & 3r

    Jun 12, 2015

    Resolve
  • Class - 2

    Reissue 35012363p exit doors not self closing. stair d 11/12 @3rd flr 2nd flr & basement (both sides), stair e 9/10 at 1st floor & 2nd flr, stair a 7/8 at 1st and 2nd flr, stair c 2/3 @3rd flr exit 4 at 1st fl

    Aug 12, 2014

    Resolve
  • Class - 2

    Failure to maintain at room 317 floor bucked and raised along radiator side of room creating trip hazard. rmdy: repair or replace.

    Aug 12, 2014

    Resolve
  • Class - 2

    Failure to maintain roof screen cage door bent & missing parts of wiremesh.roof cage door at stair "h: 4th flr other roof screen cage door bent. rmdy: repair or replace roof screen cage doors.

    Aug 12, 2014

    Resolve
  • Class - 2

    27-371(b) reissue 35012362n vision panels. prohibited plexiglass panels used in teh following: at rear of auditorim (both side stair f/g) weight room, exit 13 stair f, 336a,339b,341a,340a,342,smoke corridor

    Aug 12, 2014

    Resolve
  • Class - 1

    B188:46m07,42g11,52q03,77b11,34i10.action elevator inc d/b/a/ hudson elevator group.license #422-001 submitted an elv3 for cat 1 test on 8/19/2013.an inspection conducted on 12/11/2013 reveals the rpt is false.

    Dec 11, 2013

    Resolve
  • Class - 1

    B188:46m07,42g11,52q03,77b11,34i10.lec consulting and inspection group inc.license #491-001 submitted an elv3 for cat 1 test on 8/17/2013. an inspection conducted on 12/11/2013 reveals the report to be false.

    Dec 11, 2013 · Penalty $24,000

    Active
  • Class - 2

    17h11,17d06,46m07,60q03,42g11,56y13,52q03,77b11,34i10. 17h11-repalce secure where needed; 46m-required in conjunction w/static (); 42g-unreadable fuses; 56y-seal leaks; 52q-provide anti-spam; 77b-provide 21"

    Dec 11, 2013

    Resolve
  • Class - 2

    48v13,42g11,42y02,48t15,40m07,17h11,17d06,70y02,10j01,39x10,67l10,26d06. 48v-seal leaks; 42g-unreadable fuses; 42y-clean residue; 40m-ventilation per k3; 17h/d-replace/secure where needed; 70y-piston leaks;10j

    Dec 11, 2013

    Resolve
  • Class - 2

    27-371 (b) plexi vision panels installed on doors to rooms 100, 205, 206, 215, 219, 219a, 225, 236, 240, 241, 242, 341a, 340a, 324, 325b, 322, 321, 315, 308 & corridor doors next to rm 224. rem: provide req'd g

    Mar 5, 2013

    Resolve
  • Class - 2

    Door racked @ stair c 3rd flr, stair e 2nd flr exits 11 & 12, stair a basement doors stick exit 13 door sticks exit 10 door don't open. rem: repair or replace doors.

    Mar 5, 2013

    Resolve
  • Class - 2

    The brick column adjacent to the gas meter has a vertical crack approx4' long located at the cellar level. remedy: repair/replace vertical crack.

    Apr 20, 2012

    Resolve
  • Class - 3

    Re-issue #34846907z. at the cellar level side egress exit above a small section of concrete has come loose exposing steel lintel approx 4" x3'. remedy: patch & repair missing section of concrete.

    Mar 25, 2011

    Resolve
  • Class - 2

    Interior rm weight rm has an illegal hardware sliding dead bolt w/o a 2nd lock to prevent someone from locking the door located at the 3rd fl lvl gymnasium rem: removed sliding dead bolt lock

    Apr 22, 2010

    Resolve
  • Class - 2

    Reissue 34770772m interior concrete is spalling off the i-beam at cellar lvl located above entrance door way leading to pit area rem: repair and/or replace condcrete

    Apr 22, 2010

    Resolve
  • Class - 2

    57t16/ 68m07/ 61g11/ (52t) re shackle tag missing (68m) provide log (61g) unreadable

    Jan 11, 2010

    Active
  • Class - 2

    The concrete is spalling off the ibeam located above the entrance doorway leading to the pit at cellar level.remedy:repair/replace concrete.

    Apr 23, 2009

    Resolve
  • Class - 2

    Sec.27-369, bc 1020.1. gymnasium exit no #13 on the 4fl level is partially blocked by cabinets & chairs.remedy:remove obstruction.

    Apr 23, 2009

    Resolve
  • Class - 3

    50a,50b. erie city ft loco blr, lp stm oil, 1940 (#1) 50a duplex mounted safety valves installed in 1940 are obsolete. install asme approvedlow pressure steam replacement safety valves for code compliance 50b

    Feb 27, 2009 · Penalty $500

    Resolve
  • Class - 3

    50a,50b. erie city ft loco blr, lp stm, oil, 1940 (#4) 50a duplex mounted safety valves installed in 1940 are obsolete. install asme approved low pressure. low pressure steam replacement safety valves for code

    Feb 27, 2009

    Resolve
  • Class - 3

    50a,50b. erie city ft loco blr, lp star, oil, 1940 (#3) 50a duplex mounted safety valves installed in 1940 are obsolete. install asme approved low pressure steam replacement safety valves for code compliance.

    Feb 27, 2009

    Resolve
  • Class - 3

    50a,50b. erie city ft loco blr, lp star, oil, 1940 (#2) 50a duplex mounted safety valves installed in 1940 are obsolete. install asme approved low pressure steam replacement safety valves for code compliance,

    Feb 27, 2009

    Resolve
  • Hazardous

    Reissue 34568901h water penetrating skylight in rm r1 remedy:seal water penetration

    Jun 4, 2008

    Resolve
  • Hazardous

    Reissue 34563902j defective door missing doors noted at cellar near stairwell d 2 doors missing doors hitting frame at 2 fl stair e cellar stair b,d remedy:repair/replace doors

    Jun 4, 2008

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1940
Floors
5
Residential units
—
Building area
380,788 ft²
Lot area
108,163 ft²
Zoning
R5
Community board
305
Council district
37
Block / lot
4155 / 75
Assessed value
$21,106,350
Landmark / historic district
No

Questions about 1 Wells Street

Who owns 1 Wells Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 1 Wells Street have violations?

NYC HPD has no housing violations on record for this property.

Is 1 Wells Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1 Wells Street built?

City records list 1940 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.