2844 Fulton Street

Brooklyn, NY 11207BBL 3-03949-0018Map

Owner of record: NYC Department Of Education

2844 Fulton Street is a school building built in 1978 in Brooklyn, 11207. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
30
ECB violations
56
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 30

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 13, 2021

    Dob violation - resolved
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)

    Oct 10, 2021

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 10, 2020

    Dob violation - resolved
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2019

    Jun 29, 2020

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 19, 2013

    Dob violation - resolved
Show 20 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 7, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 28, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 27, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 23, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 30, 2006

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 2, 2004

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 20, 1999

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations · 56

  • Class - 2

    Exit door not self-closing. at the time of inspection, exit discharge #2 was not self-closing properly(frame shifted). remedy: repair/replace door.

    Mar 25, 2026 · Penalty $625

    Active
  • Class - 2

    28-301.1. unlawful placement of furnishings; decorations or other objects ay exits that obstruct access to egress from or visibilty thereof per fdny 2008 code, fc 1027.4. at the time of inspection, the security

    Mar 25, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issue 35692082k. at the time of inspection, the last certificate ofoccupancy on file from 1961 states that the occupancy classification is used car sales and parking lot. certificate of occupancy #174721. re

    Mar 25, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant. at the time of inspection, the following doors were not self-closing:-419, 421, 323, 301, 303, 305, 307, 309, 219, 223, 201, 203, 207, staircase "a" door on the 3

    Mar 25, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1; 27-371(j). at the time of inspection, the following doors had turn knob handles:-417, 423, 419, 421,

    Mar 25, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35663548k: altered/changed building(in code-compliant manner:) occupied without a valid certificate of occupancy as per 28-118.3.1 28-118.3.2 record stated c of o #172721 as auto service and parking lo

    Apr 8, 2025 · Penalty $3,125

    Active
  • Class - 2

    Found burnham boiler model-4f.360 with defects. breeching insulation defective. boiler insulation defective. rear door sight glass cracked. correct all violating conditions and submit a certificate of correctio

    Jul 17, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue #35692034l. altered/changed building occupied without a validcertificate of occupancy as per s28-118.3.1, sq28-118-7.2. noted at time of my inspection i observed the c of o was issued is for the parkin

    Feb 8, 2024 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35644196m altered/changed building occupied w/o a valid cofo as per 28-118.3.1,28-118.3.2.noted:cofo#b00172721 issued by the dob is for parking lot.now the building is occupied as a public school.rem:ob

    Jan 20, 2023 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at cellar at gas meter room illegal storage of cleaning supplies boxes piled up rem:remove illegal storage from gas meter room.

    Jan 20, 2023 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner.provide requiredcorridor with per bc 1016.2;27-369 noted at main entrance,security desk is blocking the exit door.rem:remove the obstruction.

    Jan 20, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency lighting at 2nd floor#19,at 3rd floor#21 and #24 not operati

    Jan 20, 2023 · Penalty $625

    Resolve
  • Class - 2

    Altered/change building occupied without a valid cofo as per 28-118.3.1-28-118.3.2 #b00172721 are level usc ess sales parking of more than 5 cars business district only.it's now occupied 4 story building with n

    Jan 31, 2022 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination ofr exits,exit discharges and public corridors per b1006.1;27-381 existing emergency light are not seperational what tested at crestena and gyn

    Jan 31, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Boiler over 8'' need ladders and platforms correct violating condition and submit a certificate of correction

    Aug 25, 2021 · Penalty $625

    Active
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at(3rd fl)stair b/hallway door(2nd fl)stair b/hallway door(1st fl)exit 3,cafeteria.stair a doors are in disrepair/racked. remedy: repair &/or replace.

    Feb 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1/27-381. noted: at (1st fl)cafeteria & gym emergency lights were non operational when tes

    Feb 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue ecb#35498361y alteered/changed bldg occupied w/o a valid cert of occupancy. noted: c of o#174721-61 indicates premises legally approved used car & parking lot premises now altered/occupied a public scho

    Feb 5, 2021 · Penalty $3,125

    Active
  • Class - 2

    Exit door not self closing. noted: at(3rd fl)stairs a&b(2nd fl)stair b/hallway door(1stfl)exit 2 & stair b door checks are in disrepair/non operational when tested. remedy: repair/replace door.

    Feb 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Re-issue ecb#35383979x issued 2/4/19.altered changed building occupiedwithout a valid certificate of occupancy.alt type 2 permit(nb 423/73)not on file 174721-61 records stated a used car and parking lot,not occ

    Jun 15, 2020 · Penalty $3,125

    Active
  • Class - 2

    Reissued 35311629n (01/23/18) alt type 1 permit (nb423/73) not on file174721-61 records stated a used car and parking lot not occupied as a 4story educational building w/o valid cofo. rmdy: obtain valid cofo or

    Feb 4, 2019

    Active
  • Class - 2

    Reissued #35311630k (1/23/18) failure to maintain building in code compliant manner. illumination for exts, exits discharge and public corridor per 1006.1 27-381 at sub 1st floor (gym, cafeteria and audi

    Feb 4, 2019

    Resolve
  • Class - 2

    Altered/changed bldg w/o valid cofo as per 28-118.3.1-28.118.3.2.re issue#35229220p on 03/10/17.note:cofo#174721-61 indicates a "used car and parking lot"now occupied as a 4 story public school w/o valid cofo.

    Jan 23, 2018

    Active
  • Class - 2

    Failure to maintain bldg in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.note:at sub 1st fl level in mixed used public assembly area(gym,cafe,auditorium

    Jan 23, 2018

    Resolve
  • Class - 2

    11m7,69b7,42b7,57b7,41j1,71q3. 11m7 car station access door missing.69b7 ncorrect year on code data tag.42b7 clearly mark controller to properly know terminals jumper in terminal.57b7 fire extinguisher insuffic

    Nov 28, 2017

    Active
  • Class - 2

    Reissue# 35171402r. altered/changed bldg occupied w/out a valid c of o. noted: altered 4 story bldg occupied as public school w/out a valid c of o. rem: obtain a valid c of o or discontinue illegal occupancy.

    Mar 10, 2017

    Active
  • Class - 2

    Reissue# 35177856z. failure to maintain bldg wall(s) or appurtenances. noted: @ schenck ave side of bldg, exterior parapet wall has horizontal crack. also @ fulton street side of bldg, crack from parapet wall d

    Mar 10, 2017

    Resolve
  • Class - 1

    Unsafe storage of combustible materials & equipment. noted: @ cellar in hvac room (c4) 2 gas powered snow blowers being stored. rem: maintain storage in compliance w/ fire code.

    Mar 10, 2017

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. reissued # 3512097k note: schenck side of bldg interior of parapet wall has horizontal cracks. at fulton st side of bldg step crack parapet to grade

    Apr 12, 2016

    Resolve
  • Class - 2

    Altered/changed bldg occupied w/o a valid cert of occupancy as per code. note:altered 4-story bldg occupied as public school without a valid c of o. rem:obtain valid c of o or discontinue illegal occupancy.

    Jan 29, 2016

    Active
  • Class - 2

    Reissue 35101442h.failure to maintain bldg in code compliant manner:use of prohibited hardware on doors:door stops on the following doors:411,417,419,421,423,401,403,405,407,317,319,321,323,322,301,303,305,307,

    Jun 9, 2015

    Resolve
  • Class - 2

    Reissue 35101440y.failure to maintain bldg in code compliant manner.ceiling tiles through out are either:loose,missing or sagging.rem:correct condition noted.

    Jun 9, 2015

    Resolve
  • Class - 2

    Reissue 35101439r,failure to maintain bldg wall(s)or appurtenances.@ schenck side of bldg:interior of parapet wall has horizontal cracks.@ fulton street side of bldg:sept crack parapet to grade level.@ barbey s

    Jun 9, 2015

    Resolve
  • Class - 2

    Re-issue 35012374k failure to maintain exterior. horizontal cracks at interior side of parapet @ schenck side of bldg(south) & s.e. corner horizontal cracks at exterior side of parapet at barbey st side. remedy

    Jul 25, 2014

    Resolve
  • Class - 2

    Failure to maintain in gas meter room : storage of file cabinets alongwall & next to gas meter. remedy: remove cabinets, keep meter room clear

    Jul 25, 2014

    Resolve
  • Class - 2

    Use of prohibited hardware use of door stops at each floor on numerousdoors. remedy: remove doors stops / prohibited hardware

    Jul 25, 2014

    Resolve
  • Class - 2

    Failure to maintain at bulkhead a : spalling plaster due to water penetration. remedy: maintain interior

    Jul 25, 2014

    Resolve
  • Class - 2

    Re-issue 35004024k failure to maintain ceiling tiles are loose, sagging or missing througout bldg. remedy: repair or replace ceiling tiles

    Jul 25, 2014

    Resolve
  • Class - 2

    Reissue: 34933313r in various classrooms and corridors throughout school, ceiling tiles are loose and sagging. remedy: replace ceiling tiles.

    Feb 13, 2013

    Resolve
  • Class - 2

    Horizontal cracks at interior side of parapet at south side of bldg & step cracks at se corner. remedy: make necessary repairs.

    Feb 13, 2013

    Resolve
  • Class - 2

    Reissue # 34900543l. the drop ceiling in various classrooms and corridor hallway is sagging and loose throuhgout the school. remedy: repair and/or replace drop ceiling.

    Feb 13, 2012

    Resolve
  • Class - 2

    Reissue #34846900x at the 2nd & 4th fl lvl drop ceiling in corridors & class rooms acoustical tiles are loose sagging & deteriorating rem: repair and /or replace ceiling @ the 2nd & 4th fl lvl

    Mar 9, 2011

    Resolve
  • Class - 2

    Reissue: 34770986h. interior drop ceiling tiles are loose & sagging located in room 403,405 & 400 on the 4th flr level. remedy: repair/replace drop ceiling.

    Apr 20, 2010

    Resolve
  • Class - 2

    Interior corridor hallway is partially obstructing the exit passagewaylocate by the main entrance on the 1st flr level by a security desk & chair. remedy: provide proper corridor width.

    Apr 20, 2010

    Resolve
  • Class - 2

    Drop ceiling tiles are loose & sagging located in room 403 & 405 on the 4th flr level. remedy: repair/replace drop ceiling tiles.

    Apr 16, 2009

    Resolve
  • Class - 2

    The gas meter room (c7) is missing fire stopping located on the cellar level. remedy: provide/maintain fire-stopping.

    Apr 16, 2009

    Resolve
  • Class - 2

    Illumination exit sign not lit at time of inspection in the classroom portables. remedy: replace/replace lighting.

    Apr 16, 2009

    Resolve
  • Non-hazardous

    27-127 reissue#34563372l storage in gas meeter room electrical room tables chairs mop buckets rem; remove storage

    May 30, 2008

    Resolve
  • Hazardous

    Failure to maintain-interior.cellar-east side-behind boiler #2-horizontal crack on plaster.remedy:repair cracks.

    Mar 6, 2007

    Resolve
  • Hazardous

    Failure to maintain-interior.cellar-electric room-gas meter room-used as storage(blueprints,tables,cots)remedy:remove storage

    Mar 6, 2007

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1978
Floors
4
Residential units
—
Building area
51,055 ft²
Lot area
20,570 ft²
Zoning
R6A
Community board
305
Council district
37
Block / lot
3949 / 18
Assessed value
$4,081,500
Landmark / historic district
No

Questions about 2844 Fulton Street

Who owns 2844 Fulton Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 2844 Fulton Street have violations?

NYC HPD has no housing violations on record for this property.

Is 2844 Fulton Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 2844 Fulton Street built?

City records list 1978 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.