411 Thatford Avenue

Brooklyn, NY 11212BBL 3-03604-0001Map

Owner of record: NYC Department Of Parks And Recreation

411 Thatford Avenue is a school building built in 1930 in Brooklyn, 11212. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
54
ECB violations
54
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 54

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
Show 40 more ↓
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 4, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 15, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 1, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 19, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 26, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 27, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 23, 2007

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 2, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 28, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 19, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 10, 2003

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    3s5441

    Mar 25, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 17, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Elevator elevatoroptional

    1

    Jun 28, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed

ECB violations · 54

  • Class - 2

    Reissue ecb#35717328j exit door not self closing.noted:at 1st fl exits2,3,4,5 doors in disrepair/not closing when tested.rem:repair/replace door.

    May 28, 2026 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 1st fl hallway installed/hung non fire retarted decorations/banners to ceiling.rem:comply with code.

    May 28, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:at 1st fl cafeteria,auditorium and from 1st fl thru 3rd fl all staircases/hallways in

    May 28, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue ecb#35717327h failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors as per bc 1006.1;27-381.noted:at 1st fl cafeteria,auditorium emergency lig

    May 28, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 1st fl exit 9,7,gym,stair e,d 2nd fl stair a/b 3rd fl stair c/d,a/b doors arein disrepair/racked when tested.rem:repair and/or replace.

    May 28, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted exit 3 both doors were not closing properly. remedy: repair/replace door.

    May 1, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: exit 1 four lights, cafeteria two lights, exit 9 four lights, op

    May 1, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:@cafeteria kitchen exit door:has rolldown gate that was down&very difficult to open.repair &/or replace.

    Apr 26, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not selfclosing.noted:@staird by 312,stairf by 302,staira&b by 334,staira&b by 234,stairf by 202,stairf by 102,exit door5,smoke byexit1,exit exterior door1,auditorium left&right stage,&smoke by main e

    Apr 26, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at kitchen area move removed/disconnect gas stove.exsisting gas piping capped/or plugged and closed.reissue#35434209r.remedy:repair and/or replace.

    Sep 3, 2019 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 1

    Failure to maintain building in code compliant manner.reissue #3900196-6x observed in kitchen future connection exists on gas piping where gas stove was disconnected.remedy: repair and or replace

    Jun 18, 2019

    Resolve
  • Class - 2

    Work without a permit. observed in kitchen gas stove disconnected and gas line plugged without a permit as dob records do not show any permits approvals being used for this job to be done. remedy: obtain

    Jun 18, 2019

    Resolve
  • Class - 1

    Failure to maintain building in code-complaint manner i observed removal of gas stove from kitchen area; however this removal created a future gas connection which is prohibited and not code complaint, repair a

    Apr 5, 2019

    Resolve
  • Class - 1

    Unlawful acts failure to comply with the commissioners order.i observed in cafeteria of school no fire supression (ansul system)for kitchen area.violation # 35352246r was never complied with and therefore

    Feb 25, 2019

    Resolve
  • Class - 2

    Unlawful acts failure to comply with an order of the commissioner. i observed in cafeteria no fire supression (ansul system) for kitchen area violation # 34896358k was never complied with and therefore there

    Oct 30, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compling manners: lack of emergency lighting for exits,exit discharges & public corridors per bc 1006.1;27-542. noted: at cafeteria,2 exit emergency lighting observed inoperativ

    Mar 19, 2018

    Resolve
  • Class - 2

    Re-issue # 35019275r. exit doors at exit 1 & 2 along osborn street missing saddle, not operating. remedy: maintain building.

    Jul 16, 2014

    Resolve
  • Class - 2

    Exit door not operating properly at exists 1 & 2 along osborn street noted door missing saddle and needs excessive force to open. rmdy: repair and/or replace.

    Apr 29, 2013

    Resolve
  • Class - 2

    Reissue # 34931301k. fire dampers not functioning at: boiler room. remedy: repair/replace dampers & controls.

    Feb 14, 2012

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner:installation/maintenance of plumbing materials/equipment per pc102.3.observed on 1st fl cafeteria of school pc/is 41k not installed ansul(fire suppression)syste

    Oct 24, 2011

    Resolve
  • Class - 2

    Exit sign obstructed w. banners on all floors remedy: remove fothwith

    Oct 11, 2011

    Resolve
  • Class - 2

    Defective doors 3 and 2 fl corridor doors kitchen vestibule / exit door. remedy : repair / replace doors

    Oct 11, 2011

    Resolve
  • Class - 2

    Fire dampers @ boiler room not operational @ time of inspection. remedy: make repair

    Oct 11, 2011

    Resolve
  • Class - 2

    Failure to maintain. noted: at rooms 325,225 & 212 entry doors to rooms missing viewing panel (glass wired vision parked). remedy: install viewing panels.

    Aug 4, 2010

    Resolve
  • Class - 3

    Reissue: 34711254m concrete block in gym under 2 radiators riverdale ave side of gym broken cracked block sides of door jamb exit 8 caf. vertical crack apprx 1/2" wide x 5' h on outside corner corridor wall

    May 22, 2009

    Resolve
  • Class - 2

    Concrete blocks are missing located in the gym 1st fl level 2 mortar between blocks is missing located at 3rd fl near room 336. remedy: replace missing concrete blocks & mortar.

    Nov 20, 2008

    Resolve
  • Class - 2

    Reissue: 34563068r. concrete blocks is out of plumb located at exit #8in the cafeteria 1st fl level. remedy: repair/replace concrete blocks.

    Nov 20, 2008

    Resolve
  • Hazardous

    Exit#8 to cafeteria side door buck has lose block on both sides from floor up about 3' on both sides. remedy: repair defect at above location

    Feb 13, 2007

    Resolve
  • Non-hazardous

    50 50-pipe down the saftey valve discharge to a safe point

    Nov 1, 2004

    Resolve
  • Non-hazardous

    50 50-pipe down saftey valve discharge to a safe point

    Nov 1, 2004

    Resolve
  • Non-hazardous

    "reissue" (34386076m).failure to maintain.defects are:metal windows throughout school are broken,defecting and bolted in closed position.remedy:repair and/or replace windows.

    May 18, 2004

    Resolve
  • Non-hazardous

    Failure to maintain.defects are;all metal windows throught the school are broken & defective

    Mar 25, 2003

    Resolve
  • Non-hazardous

    Failure to use panic hardware where required by law.gym occupancy #390 & no panic hardware install on east side exit doors.

    Feb 25, 2003

    Resolve
  • Non-hazardous

    Failure to use panic hardware when required by law.cafeteria occupancy #412 & no panic hardware install on south side exit doors.

    Feb 25, 2003

    Resolve
  • Non-hazardous

    Failure to maintain exteriol wall.defects are;at 3rd story north west & northe east corners are loose & sagging concrete columns

    Feb 25, 2003

    Resolve
  • Hazardous

    'reissue'failure to maintain.defects are;large cracks approx.2' wide,bulging & sagging court yard between kindergarden class rooms & main office.

    Feb 25, 2003

    Resolve
  • Non-hazardous

    Work w/o a permit. expired permit. note. sidewalk shed erected at reareast with permit # 301080425 and expired 11-02-02 ( osborn st. side ) remedy : renew permit

    Feb 25, 2003

    Resolve
  • Hazardous

    Failure to maintain building. noted defects. interior courtyard ouside main office has broken and uneven concrete. sharp edges. trip hazards. remedy: make repairs.

    Mar 20, 2002

    Resolve
  • Non-hazardous

    Exit doors @ main exit does not open or cloe properly remedy repair or replace door

    May 4, 2001

    Resolve
  • Non-hazardous

    Failure to maintain buildings defects are cracked walls in gym and room 145a remedy repair cracked walls

    May 4, 2001

    Resolve
  • Non-hazardous

    Failure to obtain a permit for temporary construction note no permit posted for side walk shed remedy obtain permit

    May 4, 2001

    Resolve
  • Hazardous

    Failure to maintain buiding defects are exit door to roof at stair c rusted difficault to open or close remedy repair or replace door

    May 4, 2001

    Resolve
  • Non-hazardous

    Failure to provide emnergency power exit lights on fls 2 3 fl and respective staircases failur eto provide emerg power to exit lights on 2 3 fls and at respective staircase remedy provide emergy power exxit lig

    Jul 12, 1999

    Resolve
  • Non-hazardous

    Failu reto provide 3 fl numbers on all stair landings fls failur eto provide 3 letter id for staircses all fls remedy provide signage as per ll 16/84

    Jul 12, 1999

    Resolve
  • Non-hazardous

    Failure to maintain building. defect is roof leaks causing wall to bulge out in draine room adjacent to swimming pool. repair or replace.

    Apr 20, 1999

    Resolve
  • Non-hazardous

    Failure to maintain building. defect is plaster loose and missing in enclosed staircase from swiming pool area to first floor story. repair or replace.

    Apr 20, 1999

    Resolve
  • Non-hazardous

    Failure to maintain building. defect is roof leaksover swiming pool causing plaster to become unkeyed and missing. repair or replace.

    Apr 20, 1999

    Resolve
  • Non-hazardous

    Failure to maintain building. defect is roof leaks causing phaster to became unkeyed, and loose in boys locker room. repair or replace.

    Apr 20, 1999

    Resolve
  • Non-hazardous

    Failure to maintain building. defect is phaster loose and unkeyed at walls and ceiling in female help room. repair or replace.

    Apr 20, 1999

    Resolve
  • Non-hazardous

    Failure to maintain building. defect is floor tiles missing in make helpers rrom. reparir or replace.

    Apr 20, 1999

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1930
Floors
2
Residential units
—
Building area
101,970 ft²
Lot area
100,000 ft²
Zoning
R6
Community board
316
Council district
41
Block / lot
3604 / 1
Assessed value
$6,301,350
Landmark / historic district
No

Questions about 411 Thatford Avenue

Who owns 411 Thatford Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.

Does 411 Thatford Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 411 Thatford Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 411 Thatford Avenue built?

City records list 1930 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.