Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 34
- Construction other optional
Ftm. obsrvd on exp 1 s.elev: missing mortar joints @ 4th fllintel & parpet; cracks in lintels, open mortar joints in sill on 4th fl. exp 2 w.elev: crack in brick work @ 4th fl lintel height; crack in mortar joint @ concrte lintel; crack in stucco, eroding brick @ parpet. exp 3 n.elev: crack in 3rd fl spandrel & @ parpet. remdy:repair &/orreplace
Aug 21, 2026
Dob violation - active - Construction other optional
Emergency work order due to severly cracked stone lintel @4fl, open mortar joints/shifted stone & 4fl lintel/eyebrow, open mortar joints, damaged/leaning canopy exp1 south. remedy: immediately install sidewalk shed along exposure 1 south (bartlett st) under direction of a licensed professional
Aug 21, 2026
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 4, 2023
Dob violation - dismissed - Immediate emergency anythingoptional
Install approxamatly thirty (30) linear feet of sidewalk shed in front of the main entrance of bldg. the sws shall extend to both setbacks on each side of the main ent.on the roof provide protection for four(4) skylights approx.8 feet x 4feet & the skylight over the main staircase approximately 12 feet x 8 feet shall be protected
Jan 12, 2023
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 28, 2020
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 14, 2020
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed
Show 24 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Jan 23, 2017
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 17, 2014
Dob violation - resolved - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jan 1, 2012
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 24, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 16, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 15, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 27, 2005
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Elevator elevatorrequired
3p3363
Aug 10, 1999
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 1, 1994
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Elevator elevatoroptional
3
Jun 28, 1993
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 1, 1993
Dob violation - dismissed - Elevator elevatoroptional
2
Apr 25, 1991
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed
ECB violations · 63
- Class - 1
Re-issue#35553873r failure to maintain building wall(s)or appurtenances.note:observed at roof level,the tower has several step cracks,bricksthat have shifted and on the corner exp#2 & #3 of the tower.there is a
Jan 11, 2023 · Penalty $2,500
Active - Class - 2
Reissue#35643269j failure to maintain building in code-compliant manner.note:observed at stair "a" bulkhead.the skylight has several crackedglass window panels overhead which have allowed water penetration to a
Jan 11, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner.bulkhead skilight has broken panes and exterior bulkhead has step cracks at various places.rem:comply with code.
Apr 5, 2022 · Penalty $625
Resolve - Class - 2
Reissue:35465579x-failure to maintain building in code-compliant manner:bulkhead roof skylight is in disrepair,broken panels,leaks.rem:comply with code.
Apr 5, 2022 · Penalty $1,562
Resolve - Class - 3
Reissue#35465580n.failure to maintain building in code-compliant manner.rear side of play groung have fence with barbed wire at top of it.remedy:repair and or replace.
Apr 12, 2021 · Penalty $500
Resolve - Class - 2
Reissue#35465579x.failure to maintain building in code-compliant manner.at bulkhead to roof skylight has a broken glass water coming in damage to walls.remedy:repair and or replace.
Apr 12, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building walls and or appurtenances.at roof level crack is in brickgoing up the tower walls on 2 sides.remedy:maintain exterior building wall.
Apr 12, 2021 · Penalty $1,250
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a
Mar 7, 2020
Resolve - Class - 3
Failure to maintain building in code code-compliant manner.at playground in rear 2 sides of playground have a fence with barbed wire at the top of fence.barbed wire present a potential hazard if a child were to
Feb 6, 2020 · Penalty $500
Resolve - Class - 2
Failure to maintain building in code compliant manner.at bulkhead to roof the skylight has a broken and severly cracked glass window pane overhead it has caused water leaking issue into the bulkhead and stairwe
Feb 6, 2020 · Penalty $625
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code compliant manner.noted:at 3rd & 1st floors stair a doors in disrepair/racked.rem:repair and or replace.
Feb 5, 2019 · Penalty $625
Resolve - Class - 2
Stair and or floor identification signs missing and or defective noted:at 3rd adn 2nd flr stair b missing flooring sign.rem:install and or repair signs.
Feb 5, 2019 · Penalty $625
Resolve - Class - 2
Exit door not self closing noted:at 1st flr exterior exit doors having no door closer installed and remain open after use.rem:repair replacedoor.
Feb 5, 2019 · Penalty $625
Resolve - Class - 2
Failru to maintain building in code compliant manner use of prohibited door and or hardware per bc1008.1.8 27-371(j).noted:at 1st flr main entry lobby installed hook latch/slide bolt door stopper and slide bolt
Feb 5, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner illumiation for exits,eixt dishcarges and public corridors per bc1006.1;27-381.noted:at 3rd,2nd,and 1st flrs emergency ligting not operational in various lo
Feb 5, 2019 · Penalty $625
Resolve - Class - 2
16b11,17h11,01l10,02x10,37y02,56y13,40r09,52i11,59v02,42d06. 16b-provide designated lobby braille tag; 17h-replace where eeded; 01,02-inaudible; 52o-inaudible; 52o-clean sections where needed; 56,37y-seal leak
Mar 19, 2018 · Penalty $310
Resolve - Class - 2
Stair and/or floor identifcation signs missing. noted: t stair a 4th floor and stair b 2nd and 3rd floors, missing flooring signs. rmdy: comply with code/install signs.
Feb 15, 2018
Resolve - Class - 2
Exit door not self closing. noted: at 1st floor, exit doors a,b,d, cafe exit, the doors have no closer and remain open after use. at 2nd floor, stair a, girl's bathroom boy's bathroom, room 210, the doors have
Feb 15, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. interior water dam age to plaster in bulkhead b and bulkhead at boiler room. reissue 35086027h. rmdy: repair walls.
Feb 3, 2015
Resolve - Class - 2
Reissue 35086026x failure to maintain bldg walls or appurtenances.water penetration through roof bulkheads at stair "b" and at boiler room bulkhead. rmdy: maintain weatherproof integrity of bulkhead.
Feb 3, 2015
Resolve - Class - 2
Reissue ecb #35016351x.failure to maintain bldg wall(s) or appurtenances.metal air conditioning support brackets @ several windows inadequately supported.rem:provide adequate support.
Mar 11, 2014
Resolve - Class - 2
Reissue ecb #34941012n.failure to maintain bldg wall(s)or appurtenancewater penetration through roof bulkhead @ stair"b" @ boiler room.rem:maintain weather proof integrity of bulkhead.
Mar 11, 2014
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.interior water damage to plaster in bulkhead boiler room.rem:repair &/or replace.
Mar 11, 2014
Resolve - Class - 2
Defective air conditioner support. at 4th flr rear - visible from schoolyard, several window mounted a/c units installed w/defective and/or inadequate support brackets. remedy: provide proper support or remove
Apr 23, 2013
Resolve - Class - 2
Water penetration thru roof bulkhead at stair b. remedy: repair/maintain weather proof integrity of bulkhead.
Jan 10, 2012
Resolve - Class - 2
Reissue # 34921948m. lack of metal support brackets for window mounted air conditioner. noted: at 4th story rear above play yard 2 window mounted a/c units missing metal support brackets. remedy: provide metal
Jan 10, 2012
Resolve - Class - 2
Exterior metal column has an metal overhang attachment approx. 5"x6" sticking out in the play area with children running around.(noted:metal over hang is approx. 3'-4' above ground level). remedy:remove metal o
Aug 4, 2011 · Penalty $2,500
Resolve - Class - 2
Exterior window air conditioner does not have any metal brackets for support located ont he 4th flr. above the children's play ground. remedy: install metal bracket for air conditioner.
Aug 4, 2011 · Penalty $2,500
Resolve - Class - 2
Exterior roof has become porous and allowing rain into the bldg causing interior damages below in room 401,403,404,303 & roof bulkhead at stair "b".remedy:waterproof exterior roof.
Feb 3, 2010
Resolve - Class - 2
Exit door @ stair "b" is defective located on the 2nd floor.noted:doorcloser is defective.remedy:repair and/or replace door closer.
Feb 3, 2010
Resolve - Class - 1
- haz - metal cover of waste tray, loose causing possible fall 8' deep(cover approx 2'x 2') also noted: servere rotting of metal framing & lather around waste trap, 1st flr front of handicapped entrance
Mar 20, 2009
Resolve - Class - 2
Missing luminated exit sign in cafeteria leading to school yard 1st flr (exits in school yard). remedy: install exit signs to original stateor provide pa plans at site for inspection.
Mar 20, 2009
Resolve - Class - 1
No 24 hour notice. noted: site at above address graded. bldg demolished. no 24 hr notice was provided as per dob record. remedy: provide notice.
Feb 20, 2009
Resolve - Class - 3
Plaster damage at roof boiler room around concrete beam. remedy: repair plaster.
Aug 1, 2008
Resolve - Hazardous
Failure to maintain.defect noted:cracks,missing mortar joints,missing brick,defective wood framing @ windows,thru-out brick bldg.remedy:maintain bldg as per code.obtain permits to repair defect noted forthwith.
May 31, 2007 · Penalty $800
Resolve - Hazardous
Re-issue:34504956p. water penetration thru pipes above located at multi-purpose room on the 1st floor. remedy: repair pipes.
Mar 20, 2007
Resolve - Hazardous
Re-issue:34504951x,34468709m. multi-purpose room condensate pump vent-ing to underside of the carport located on the north/east corner caus-ing deterioration to the soffit & framing system & floors in room 201.
Mar 20, 2007
Resolve - Non-hazardous
02-b-10,85-bb-05,55-y-02,55-y-13,58-y-11/02-b-10-emergency phone/58-y-11-replace oily brake shoe
Jul 10, 2006 · Penalty $2,500
Resolve - Non-hazardous
Re-issued vio #34468711l noted: stair "a" door at 2nd floor are not self closing. remedy: repair/replace door (fpsc).
Jan 18, 2006
Resolve - Non-hazardous
Re-issued: vio# 34468708k noted: fourth floor terrace water-proofing defective, water leaking through concrete ceiling slab onto class room #303, south east corner. remedy: repair/replace water proofing
Jan 18, 2006
Resolve - Non-hazardous
Re-issued vio #34468709m noted: multi-purpose room condensate pump venting to underside of car port northeast corner causing deterioration of soffit and framing system including insulation and flooring to
Jan 18, 2006
Resolve - Non-hazardous
Re-issued vio #34468710j noted: bartlett st. north end corridor exit door unable to be opened- defective door and hardware restraing door. (slide bolt) remedy: remove illegal hardware.
Jan 18, 2006
Resolve - Non-hazardous
Re-issued vio.# 34390712x noted: water penetrating through bricks mortar joints. location: rear of building (gerry st) stair way "b" penthouse (boiler room area). remedy: repoint as needed.
Jan 18, 2006
Resolve - Non-hazardous
Re-issued vio #34444800r. noted: water penetrated walls and ceiling inboiler room. remedy: make repairs.
Jan 18, 2006
Resolve - Non-hazardous
Water leaking (pipes) at multipurpose room (1st floor) trough concreteceiling slab. remedy: repair ceiling and water pipes.
Jan 18, 2006
Resolve - Non-hazardous
Noted: 4th ,3rd & 2nd floor corridor required width decreased by obstructions clothing,racks, tables,deeks,chairs, bookcases, copiers, etc. remedy: remove obstructions, maintain corrior passages clear.
Mar 11, 2005
Resolve - Non-hazardous
Noted: failure to provide/maintain required fire stopping within electric meter room at various locations. remedy: provide/maintain fire stopping as reqired.
Mar 11, 2005
Resolve - Non-hazardous
Noted: stair "a" doors at 4th, 3rd and 2nd floors are not self closing. remedy: repair/replace doors.
Mar 11, 2005
Resolve - Hazardous
Noted: bartlett st north end corridor exit door unable to be opened - defective door and hardware restraining door. remedy: repair/replace door and hardware as required, maintain exit door.
Mar 11, 2005
Resolve - Non-hazardous
Noted: multi-purpose room condensate pump venting to underside of car port northeast corner causing deterioration of soffit and framing system including insulation and flooring to classroom 201. remedy:
Mar 11, 2005
Resolve
Complaints
- Safety
Window guard broken/missing
Jan 26, 2022 · Apt 401402
Close - Heating
Heat related
Feb 27, 2010 · Apt 2FL
Close - Nonconst
Vermin
Jan 28, 2010 · Apt 2FL
Close - Nonconst
Vermin
Jan 28, 2010 · Apt 2FL
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W9)
- Year built
- 1929
- Floors
- 4
- Residential units
- —
- Building area
- 37,499 ft²
- Lot area
- 57,531 ft²
- Zoning
- M3-1
- Community board
- 301
- Council district
- 33
- Block / lot
- 2268 / 1
- Assessed value
- $1,134,000
- Landmark / historic district
- No
Questions about 611 Flushing Avenue
Who owns 611 Flushing Avenue?
The owner of record in NYC Department of City Planning PLUTO data is 11 Bartlett Owner, LLC.
Does 611 Flushing Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 611 Flushing Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 611 Flushing Avenue built?
City records list 1929 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.