83 Lexington Avenue
Brooklyn, NY 11238BBL 3-01967-0068Map
Owner of record: NYC Department Of Homeless Services
83 Lexington Avenue is a hospital / health built in 1965 in Brooklyn, 11238. The owner of record is NYC Department Of Homeless Services. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 30
- ECB violations
- 42
- HPD complaints
- 8
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 30
- Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 24, 2019
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 10, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 30, 2016
Dob violation - resolved - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 21, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 6, 2012
Dob violation - resolved
Show 20 more ↓
- Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 4, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 12, 2009
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 12, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 7, 2008
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 15, 2006
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Elevator elevatorrequired
3p8476
Nov 25, 1998
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 1, 1993
Dob violation - dismissed
ECB violations · 42
- Class - 1
Failure to provide unobstructed exit passageway. observed on the ground floor main entrance metal detector/ item scanner blocking emergency exit potential hazard and danger 27-369, bc 1020.2, remove obstruction
Feb 9, 2026 · Penalty $2,500
Active - Class - 1
Observed on the first floor storage room and laundry room, sprinkler heads are obstructed. throughout the building, sprinkler heads are not flushed to celling with the escutcheon plate, leaving an unsealed ceil
Feb 9, 2026 · Penalty $2,500
Active - Class - 1
Observed on the roof vent terminal not being supported properly. on first and second floors in the bathrooms not having insulation on traps under the sinks. in the sprinkler room the sprinkler system is broken.
Feb 9, 2026 · Penalty $2,500
Active - Class - 1
Observed slop sink room, there is no fire stop for the pipe penetration through walls. there is no air gap at mop sink drain line and under the ice machine drain line and the sprinkler system drain line. in the
Feb 9, 2026 · Penalty $2,500
Active - Class - 2
Failure to maintain building in code-compliant manner. observed a flexgas cord on a commercial fixed oven. potential hazard., repair and/or replace
Apr 10, 2025 · Penalty $1,250
Active - Class - 2
Exit door not self-closing. observed non self closing door at 1st floor e dorm room. potential fire hazard., repair/replace door
Apr 10, 2025 · Penalty $625
Resolve - Class - 1
Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed 2 unpermitted plastic access panels. located in ac hvac on 1st and 2nd f
Apr 10, 2025 · Penalty $2,500
Resolve - Class - 1
On 1st floor at end of hallway exit door is locked obstructing egress., remove obstruction
Sep 27, 2024 · Penalty $1,250
Resolve - Class - 2
I observed in dob records no permit for the installation of branch circuit wiring for three split unit a.c. units along exposure #2., obtain permit
Dec 7, 2023 · Penalty $800
Resolve - Class - 2
I observed in the rooftop disconnect for the exhaust fan the failure to install the equipment ground conductor., provide adequate grounding
Dec 7, 2023 · Penalty $2,400
Resolve
Show 32 more ↓
- Class - 2
I observed in the side yard( exp #2) the installation of conduits, wiring and fittings to supply power for three ac units. no permits on file in dob records., obtain permit; obtain permit and call for inspectio
Jun 1, 2023 · Penalty $800
Resolve - Class - 2
I observed in the disconnect switch for the rooftop exhaust fan failure to install an equipment grounding conductor required for affixed equipment using flexible raceways to supply power., provide adequate grou
Jun 1, 2023 · Penalty $2,400
Resolve - Class - 2
I observed in the parking area along exp #2 the installation of a.c. units without equipment disconnect switches prior to power entering the units., comply with ec
Jun 1, 2023 · Penalty $800
Resolve - Class - 2
Observed in the kitchen commercial gas flex on oven that in not on casters. as per 411.1.1 commercial cooking appliances. commercial cooking appliances installed on casters and appliances that are moved for cle
Jun 1, 2023 · Penalty $625
Resolve - Class - 2
Exit door not selfclosing.observed:fireproof selfclosing door@1fl,corridor smoke door near main entrance,smoke door next to daily linen supply rm&smoke door near shift super rm dont selfclose properly due overl
Mar 17, 2022 · Penalty $625
Resolve - Class - 2
Rotted water lines at boiler. repair pipes
Jan 7, 2021 · Penalty $625
Resolve - Class - 2
Main electrical room and boiler room fire stop not done, also sections of the walls are missing for fire rated construction for the rooms., provide/maintain fire stopping
Aug 2, 2019
Resolve - Class - 2
Gas piping to commercial cooking equipment incorrectly installed. , repair and/or replace
Aug 2, 2019
Resolve - Class - 2
Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. noted: observed at cellar's gas meter room. pipe penetrating into adjacent rooms and areas with no fire stopping
Feb 11, 2019
Resolve - Class - 2
70o2,2b7,81y10,68b7. 70o2-dirty pit clean; 2b7-outside comm not connected to current maintenance company, provide. 81y10-piston leaking oilrepair; 68b7-maintenance log not current, provide monthly tags.
Feb 6, 2019
Resolve - Class - 2
B254, 15, 32(a), 50. found(weilelain) model #bl-788 btus 2,049,000 hotwater heating system, as per class 2 (b254) 28.301.1 failure to maintian, (15) openings in walls, (32)a, exposed wiring,(50)missing spill
Feb 6, 2019
Active - Class - 2
11d6,15m7,46l10. 11d6-car station not secured; 15m7-missing certificate or location in car; 46l10-ambient temperature control not working.
Sep 5, 2018
Resolve - Class - 2
Altered/changed building occupied without a valid certificate of occupancy as per 28-118.3.1-28-118.3.2-noted:observed.2 story building altered under job application #300155533 and fully occupied as a shelter w
Jul 20, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner.no fire stopping per bc 712.3,27-345 noted:observed throughout cellars-boiler room, gas meter room, ac room pipes and conduits penetrating into adjacent roo
Jul 20, 2018
Resolve - Class - 1
Unlawful act. failure to comply w/an order of the commissioner. records indicate no application filed to remove,certify & correct violation contained in summons#35313005y;#35289684h. remedy: comply w/comm's ord
May 25, 2018
Resolve - Class - 1
Failure to comply with the commissioner's order contained in summons 35274494p and 35289684h issued on 12/29/17 and to file a certificate of correction pursuant to 28-204.4; 28-201.1; 1rcny 102.01
Mar 19, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. noted: observed at cellar, a lack of fire stopping and fire proofing within the boiler room, gas meter room, ac roo
Jan 30, 2018
Resolve - Class - 2
Failure to comply with commissioner's order contained in summons/violation #35290737k issued on 11/26/17 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. failure to maintain bldg
Jan 10, 2018
Resolve - Class - 1
Unlawful act, failure to comply w/ an order of the commissioner. records indicate no application filed to certify, correct, & remove violation contained in summons #35289684h. rem: comply w/ commissioner's orde
Dec 29, 2017
Resolve - Class - 1
Failure to maintian bldg in code compliant manner. observed on 11/26/17 at above commericial cooling equipment not hard piped. remedy:repairand /or replace.
Nov 26, 2017
Resolve - Class - 2
11j1'39o2;42b6;40o2:car station has a gap between the apanel and the strike side-close gap;car top dirty-clean;exposed wiring on controller,properly secure;machine rm dirty-clean
Oct 26, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. observed on 8/10/17@ above address no sprinkler gauge on upper most floor. remedy: repair&/or replace.
Aug 10, 2017
Resolve - Class - 2
Failure to maintain building in code-compliant manner: no fire stopping as per bc712.3;27-345. noted: at cellar, in gas meter room, water meter room and electrical meter room sheet rock missing at walls in vari
Aug 10, 2017
Resolve - Class - 1
Unapproved, unsafe, unsuitable electrical equipment, apparatus, devices, materials, appliances or wiring in use. observed above front entrance door (inside): the use of extension cords to supply electrical powe
Aug 10, 2017
Resolve - Class - 1
Failure to maintain bldg in code compliant manner. observed on 8/10/17@ above address commercial cooling equipment not hand piped. photo taken. remedy: repair &/or replace.
Aug 10, 2017
Resolve - Class - 1
97x17-the only elevator in section of building out of service. upon inspection the device is found to be out of service creating a hazardouscondition as per 1rcny 11-02 restore to service immediately and notify
May 31, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. observed on 3/1/17 @ above address inspectors test gauge not installed on the upper most floor. photos taken. rem: repair &/or replace.
Mar 1, 2017
Resolve - Class - 1
Sec: fgc 411.1. residential gas flex used on commercial equipment. observed on 3/1/17 @ above address residential gas flex used on commercial cooking equipment. must be hand piped. photos taken. rem: comply w/
Mar 1, 2017
Resolve - Class - 2
Altered/changed building occupied w/o a valid certificate of occupancyper 28-118.3.2; 28-118.3.1. noted: building altered under job#300155533 alt i and fully occupied as a homeless shelter with no certificate o
Jul 22, 2016
Resolve - Class - 2
Failure to maintain bldg in code complaint manner. strainer installed on sprinkler system in meter room-water service locations. photo's taken. remedy: remove/replace.
Sep 5, 2015
Resolve - Class - 2
/16b11/48bb05/99m05/10h11/17h11/70y13/39x10/34q03/ (16b) provide designated lobby braille tags. (48bb,99m) cat one. (10h,17h) where needed. (70y) piston. (39x) car top inspection. (34q) ventilation screen.
Jun 17, 2015
Resolve - Class - 2
Failure to maintain building in code-complaint manner defect is at rear of building. metal chain link fence is in disrepair & collapsed ontoroof area. remedy: repair & or replace make all necessary repairs.
Jul 15, 2011
Resolve
Complaints
- Heating
Heat related
Dec 27, 2005 · Apt 2FL
Close - Heating
Heat related
Dec 2, 2005 · Apt 1FL
Close - Heating
Heat related
Feb 23, 2005 · Apt NA
Close - Heating
Heat related
Feb 7, 2005 · Apt 1
Close - Heating
Heat related
Jan 21, 2005 · Apt 2FL
Close - General
Windows
Jan 21, 2005 · Apt 2FL
Close - Heating
Heat related
Dec 2, 2004 · Apt 2FL
Close - Heating
Heat related
Dec 2, 2004 · Apt 2FL
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Hospital / health (I5)
- Year built
- 1965
- Floors
- 2
- Residential units
- —
- Building area
- 17,000 ft²
- Lot area
- 10,000 ft²
- Zoning
- R6B
- Community board
- 303
- Council district
- 36
- Block / lot
- 1967 / 68
- Assessed value
- $1,361,250
- Landmark / historic district
- No
Questions about 83 Lexington Avenue
Who owns 83 Lexington Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Homeless Services.
Does 83 Lexington Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 83 Lexington Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 83 Lexington Avenue built?
City records list 1965 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.