182 Hopkins Street

Brooklyn, NY 11206BBL 3-01726-0014Map

Owner of record: NYC Department Of Education

182 Hopkins Street is a school building built in 1906 in Brooklyn, 11206. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
12
ECB violations
45
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 12

  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
Show 2 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed

ECB violations · 45

  • Class - 2

    Reissue #35677418j date of issue: 04-18-2024. exit door not self-closing properly at the time of inspection observed and noted at main entrance 2 exit(1st floor) door is not self-closing properly, at 1st. fl. a

    May 19, 2025 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35677420z date of issue: 04-18-2024. failure to maintain building in code-compliant manner at the time of inspection i observed andnoted at 3rd fl stairwell j. one smoke well coming properly and also a

    May 19, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue #35677419l date of issue: 04-18-2024. failure to maintain building in code-compliant manner. illumination for exits, exit dischargesand public corridors per bc 1006.1, 27-381. at the time of inspection

    May 19, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35671789l exit door not self-closing.at time of my inspection i observed at exit 7.2 door not self-closing at exit 8 2 door also not closing at exit 2 door not working properly when they closing need to

    Apr 18, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35671788j failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at time of my inspection i observed the emergency exit li

    Apr 18, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35671787h failure to maintain building in code-compliant manner.at time of my inspection i observed at the 3rd floor stair wall c and g smoke not working properly also at bulkhead door is not working wh

    Apr 18, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:doors do not close properly at 3rd fl stairwell "c",stair "g" & rooftop bulkhead door.remedy:repair/replace

    Feb 9, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing.noted:exit door not self-closing,one door at exit 7, 2 doors at exit 8, 2 doors at exit 3, 2 doors at exit 6.remedy:repair/replace door

    Feb 9, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue# 35655099y.failure to maintain building in code-compliant manner.noted;at roof top bulkhead water penetration damaging bulkhead roof.remedy:repair/replace.make necessary repairs.

    Feb 9, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted:emergency exit lighting found inoperative when tested at cafeteria 2 li

    Feb 9, 2023 · Penalty $625

    Resolve
Show 35 more ↓
  • Class - 2

    Reissue:35557633x(4/19/2021)failure to maintain building in code-compliant manner at bulkhead deteriorated condition from water infuration on steps & walls.rem:repair & or replace.

    Apr 27, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: step @ bulkhead is in disrepair from water damage. remedy: re¢air &/or replace.

    Apr 19, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue 35325101m failure to maintain building in code compliant man ner at bulkhead staircase ceiling damage due to water penetration fromroof. rmdy: repair replace.

    Apr 9, 2019

    Resolve
  • Class - 2

    Reissue 35325100k failure to maintain building in code compliant man ner at 2nd and 3rd floor rooms 308, 314, 323 closers not working doorsnot self close or close. rmdy: replace doors.

    Apr 9, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.noted:at bulkhead staircase(d)water damage to ceiling due to water penetration through roof.rem:comply w/code/repair the ceiling.

    Mar 15, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:lack of emergency lighting for exits,exit discharges and public corridors pe bc 1006.1;27-542.noted:at auditorium area,inoperative emergency lights w/battery ba

    Mar 15, 2018

    Resolve
  • Class - 2

    Failure to maintian bldg in code compliant manner.noted:at 2nd and 3rdfl,the doors have defect in top hinge and not close completely at rm #221,308,314,323.rem:comply w/code/repair or replace.

    Mar 15, 2018

    Resolve
  • Class - 2

    27-371(b)reissue #35095070h.plexi vision panels.plexi vision panels(thermoplastic)installed @ various rooms previously noted on 2nd & 3rd fl.rem:provide code compliant vision panels.

    Feb 19, 2015

    Resolve
  • Class - 2

    Reissue #35095069k.exit doors not self closing.1j,1e,exit9,2a.doors are racked to frame & not closing properly.rem:repair if feasible or replace doors.

    Feb 19, 2015

    Resolve
  • Class - 2

    Defective emergency lighting.@ cellar auditorium,approx 50% of emergency lighting is inoperative.rem:repair &/or replace em.lights.

    Feb 19, 2015

    Resolve
  • Class - 2

    Reissue 35015651n.failure to maintain exteior.spalling decorative stone parapet level throughout.spalling concrete wall @ areaway cellar level @ ellery st.rem:maintain exterior bldg wall.

    Jun 16, 2014

    Resolve
  • Class - 3

    Reissue 35015653r.failure to maintain exterior water penetration into wal adjacent to exit 12.rem:seal penetration.

    Jun 16, 2014

    Resolve
  • Class - 2

    Exit doors not self closing.following doors do not close properly:stair j 1st fl.exit 9 1st fl ,stair"a" 2nd & 3rd fl ,stair 1 1st fl,exit e1st fl.rem:repair or replace doors.

    Jun 16, 2014

    Resolve
  • Class - 2

    27-371(b)vision panels.use of prohibited plexiglass in the following doors:room 208,217a,217b,227,311,308,stair"d"3rd fl.303b,303a,stair"c"3rd fl,stair h @ cellar.rem:provide required glass panels.

    Jun 16, 2014

    Resolve
  • Class - 3

    Water penetration into wall adjacent to exit 12. rmdy: seal penetration.

    Mar 26, 2013

    Resolve
  • Class - 2

    Defective doors 3 fl stair a,b,c,; exit2(stair a); exit vestibule doorstair e, basement stair c. doors not closing properly,splitting doors.rmdy: repair/replace doors.

    Mar 26, 2013

    Resolve
  • Class - 2

    Spalling decorative stone parapet level throughout also mortar joints missing throughout exterior building walls. remedy: make safe! repair wall.

    Mar 26, 2013

    Resolve
  • Class - 2

    Illegal hardware noted on exit vestibule door (e) key cylinder in place. remedy: remove hardware.

    Mar 26, 2013

    Resolve
  • Class - 2

    Interior stone / brick wall is missing mortar located @ the ash hoist @ cellar level. remedy: replace missing mortar

    Mar 4, 2010

    Resolve
  • Class - 2

    Work w/o a permit expired permit sidewalk shed permit expired #30255416201 rem: renew permit

    Jan 8, 2009 · Penalty $400

    Resolve
  • Class - 2

    Reissue: 34435158y failure to maintain building in code compliant manner defect noted: plaster is spalling the entire staircase of "f" 1st through 4th flr & room 227 on the 2nd flr. remedy: repair and/or replac

    Jul 11, 2008

    Resolve
  • Class - 2

    Failure to maintain building walls or appurtenances. noted: foundationbrick wall has missing mortar adjacent to the boilers on cellar level.remedy: maintain exterior building wall.

    Jul 11, 2008

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. defects noted: the interior wall is cracked at staircase "k" between 2nd and 3rd level. remedy: repair and/or replace crack in wall.

    Jul 11, 2008

    Resolve
  • Non-hazardous

    Failure to maintain defects are water penetrating through north and east sides mortar joints remedy:repair mortar joints.

    Apr 21, 2004

    Resolve
  • Non-hazardous

    Failure to maintain defects are loose and bulging plaster walls locations are :(1)stair case # 6 between first floor and basement (2)stair case "g" in basement east wall(3)room # 227 remedy:repair walls

    Apr 21, 2004

    Resolve
  • Hazardous

    Failure to maintain. defects are. basement north side corridor storagerooms door frames and auditorium north and south door frames are rotten loose and sagging with sharp edges. remedy : replace door frames

    Apr 8, 2003

    Resolve
  • Non-hazardous

    Panic hardware in operative : note. auditorium main entrance ( west side ) panic hardware are broken and defective. remedy : repair and / orreplace panic hardware

    Apr 8, 2003

    Resolve
  • Non-hazardous

    Work without a permit work noted contruction and renovation of the entire interior of the 4th floor without a pemit remedy obtain a permit as required

    Apr 24, 2001

    Resolve
  • Non-hazardous

    Exit door not self closing note exit door in caferteria leading to playyard is not self closing exit door opposite room 320 is also not self closing remedy repair / replace door

    Apr 24, 2001

    Resolve
  • Non-hazardous

    Failure to maintain building defects are crack and damaged ceiling in room 21 and 303a remedy damaged / cracked walls

    Apr 24, 2001

    Resolve
  • Non-hazardous

    Failure to maintain building defect is water damaged wall in room 227 remedy rapir damaged wall

    Apr 24, 2001

    Resolve
  • Non-hazardous

    Failur eto fiel areport of compliance with local law 16/84 certiying to the isntallation of required fire protection system remedy file reprot

    Jul 21, 1999

    Resolve
  • Non-hazardous

    Failur eto provide 3 stair letter id signs at staircase all fls remedyprovide signage as per ll16/84

    Jul 21, 1999

    Resolve
  • Non-hazardous

    Failur eto prove emergency lights in ocorridors and stairs all fls failur eto provide emergency power to exit lights in stairs and coridors all fls remedy provide emergency power exit light and to exit directio

    Jul 21, 1999

    Resolve
  • Hazardous

    Failure to maintain building interior and exterior.noted wrought iron dence hazardous ripped open at no side of school. interior doors jammed in position, hazardous. concrete court yard nerds repair. facade rep

    Apr 23, 1999

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1906
Floors
4
Residential units
—
Building area
120,000 ft²
Lot area
30,000 ft²
Zoning
R6B
Community board
303
Council district
36
Block / lot
1726 / 14
Assessed value
$6,507,900
Landmark / historic district
No

Questions about 182 Hopkins Street

Who owns 182 Hopkins Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 182 Hopkins Street have violations?

NYC HPD has no housing violations on record for this property.

Is 182 Hopkins Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 182 Hopkins Street built?

City records list 1906 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.