1424 Herkimer Street
Brooklyn, NY 11233BBL 3-01572-0018Map
Owner of record: 1424 Herkimer Street Development LLC
1424 Herkimer Street is a care facility built in 1926 in Brooklyn, 11233. The owner of record is 1424 Herkimer Street Development LLC. HPD has recorded 16 housing violations here, most recently on March 22, 2026. 1 of the 16 most recent violations are still open.
- HPD violations
- 16
- DOB violations
- 41
- ECB violations
- 57
- HPD complaints
- 109
What to know
Immediately hazardous issues among recent violations are still open.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 16
- CImmediately hazardous
Provide hot water at all hot water fixtures in the water closet compartment located at b-room 301, 3rd story, 1st b-room from west at north
Mar 22, 2026 · Apt 301
Closed — Violation closed - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective hinges in the entrance located at apt 205, 2nd story, 1st apartment from north at east
Mar 22, 2026 · Apt 205
Closed — Violation closed - CImmediately hazardous
Abate the infestation consisting of mice in the 1st room from east located at b-room 205, 2nd story, 1st b-room from north at east
Mar 22, 2026 · Apt 205
Open — Defect letter issued - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective door at entrance located at b-room 23, 2nd story, 2nd b-room from east at south
Feb 25, 2026 · Apt 23
Closed — Violation closed - BHazardous
Properly repair or replace the broken or defective latch set at entrance door located at b-room 37, 3rd story, 1st b-room from south at west
Feb 25, 2026 · Apt 37
Closed — Violation closed - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective door at cafeteria entrance , 1st story
Feb 25, 2026
Closed — Violation closed - CImmediately hazardous
Properly repair or replace the broken or defective latching mechanism at fire stairs exit to hallway (stair a) , 1st story
Feb 25, 2026
Closed — Violation closed - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective latch set at entrance located at b-room 51, 4th story, 1st b-room from south at west
Feb 25, 2026 · Apt 51
Closed — Violation closed - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective latch set at entrance located at b-room 37, 3rd story, 1st b-room from south at west
Feb 25, 2026 · Apt 37
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures in the entire apartment located at apt 102, 1st story, 1st apartment from west at north
Dec 30, 2024 · Apt 102
Closed — Violation closed
Show 6 more ↓
- CImmediately hazardous
Provide ready access to buildings heating system locked door at boiler room
Dec 30, 2024
Closed — Violation closed - CImmediately hazardous
M/d law abate the nuisance consisting of hot water exceeding the maximun allowable temperature of 130 degrees at community bathroom, 2nd story
Feb 22, 2022
Closed — Violation closed - CImmediately hazardous
Provide an adequate supply of heat for the apartment in the 1st room from east located at b-room 401, 4th story, 1st b-room from south at west
Feb 15, 2022 · Apt 401
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures in the 1st room from east located at b-room 401, 4th story, 1st b-room from south at west
Feb 15, 2022 · Apt 401
Closed — Violation closed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 9, 2021
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Oct 9, 2015
Closed — Violation dismissed
DOB building violations · 41
- Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 22, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 22, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 22, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Feb 21, 2024
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 4, 2023
Dob violation - dismissed - Construction other optional
Emergency work order due to defective masonry facade. spalled stone work,loose/rusted metal cornice, cracked bricks damaged mortar joints, damaged window sills on exp 1 and 2 north and east elevations remedy:immed take required measures to secure public safety and install public protection at exp 1 and 2. maked immed repairs
Aug 29, 2022
Dob violation - dismissed - Construction other optional
Ftm building in a code compliant manner. building has spalled stones exp 1 and 2, damaged briacks exp 1,2,3 and roof, damaged window sills, step cracking damaged metal cornice exp1, bulging briacks exp3 remedy: comply with code, provide sidewalk shed on all steet exposures
Jun 3, 2022
Dob violation - dismissed - Construction other optional
Ftm building in code compliant manner. observed at exp 1(north)cracked /spalling stone at 1st floor window lintel. expsosure #3(south)cracked masonry, damaged mortar joints, bulging masonry. remedy: repair and replace
Jun 26, 2021
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 27, 2019
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 27, 2019
Dob violation - dismissed
Show 31 more ↓
- Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 9, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 13, 2018
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 31, 2018
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Feb 8, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 22, 2015
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 11, 2012
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2010 inspection report
Dec 13, 2011
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2010 inspection/test
Dec 13, 2011
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 22, 2011
Vw*-violation - work w/o permit dismissed - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 19, 2010
Dob violation - resolved - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 17, 2009
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 27, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 10, 2007
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 24, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 12, 2005
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 1, 2004
Dob violation - resolved - Elevator elevatorrequired
3f4078
Apr 2, 2002
Dob violation - resolved - Elevator elevatorrequired
3f4078
Mar 28, 2000
Dob violation - resolved - Elevator elevatorrequired
3f4078..cease use
Dec 1, 1998
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 10, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 16, 1993
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 1, 1993
Dob violation - dismissed - Elevator elevatorrequired
(18)provide cover on interlocks and secure interlock bracket
Nov 30, 1989
Dob violation - resolved
ECB violations · 57
- Class - 2
Failure to comply with the commissioner's order to file a certificate of correction with the dept. of buildings for violation # 39130015l, file a certificate of correction
Apr 23, 2026 · Penalty $625
Resolve - Class - 2
Failure to comply with the commissioner's order to file certificate of correction with the dept. of buildings for violation #39130017p, file a certificate of correction
Apr 23, 2026 · Penalty $625
Resolve - Class - 2
Failure to file certificate of correction with the dept. of buildings for violation # 339130014j, file a certificate of correction
Apr 23, 2026 · Penalty $1,250
Resolve - Class - 2
1) in-car communication inoperative. 2) secure hand rail to back wall inside of elevator. 3) top of car door hanger/door operator worn. 4) cleaning of oil leak in elevator mr. 5) elevator not running as-per cod
Mar 27, 2026
Resolve - Class - 1
Cease use items: 1) both zone lock restrictors inoperative. 2)unsecure cab hitch plates. class 2 items: cab missing device number. mialinged cab mirror. unguarded cab lighting. replace worn gibs where needed. s
Mar 16, 2026 · Penalty $6,250
Active - Class - 1
Class 1 rts continued: failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the device is found to be out of service, creating a hazardous
Aug 1, 2025 · Penalty $1,250
Resolve - Class - 1
Class 1 rts: failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the device is found to be out of service, creating a hazardous condition
Jul 22, 2025 · Penalty $1,250
Resolve - Class - 1
Rts class 1: failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the device is found to be out of service, creating a hazardous condition
Jul 17, 2025 · Penalty $1,250
Resolve - Class - 1
Failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the only device in the section of the building is found to be out of service, creatin
Feb 7, 2025 · Penalty $1,250
Resolve - Class - 2
I observed with the installation of a partition wall, new door and hardware the path of egress from the electrical room made improper with the door blocking the path of egress by being installed to swing into t
Nov 12, 2024
Resolve
Show 40 more ↓
- Class - 1
Failure to maintain building in code-compliant manner: use of prohibited door and/or hardware per bc 1008.1 (2014 code); 27-371; bc 1008.1.9 (2014 code); bc 1010.1.8 (2022 code); bc 1010.1.9 (2022 code). observ
Nov 12, 2024 · Penalty $1,250
Resolve - Class - 1
Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed hole penetration ine the gas meter room. in case of emergency this can b
Nov 12, 2024 · Penalty $2,500
Resolve - Class - 1
Unsafe storage of combustible material and equipment. observed storage underneath staircases a&b. at basement level. staircase a has ats switch under stairs and room is not fire rated. b side has wood and debri
Nov 12, 2024 · Penalty $1,250
Resolve - Class - 2
Exit door not self-closing. observed non self closing doors in basement adjacent to electrical room. in case of emergency potential fire or smoke hazard., repair/replace door
Nov 12, 2024 · Penalty $3,125
Active - Class - 1
Failure to comply with the commissioners order contained in summons/violation# 39086998x issued on 5/17/23 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. (27-misc, 28-misc, bc -m
Feb 2, 2024
Resolve - Class - 2
I observed in dob records the failure to submit documentation for the correction of ecb# 39086998x issued on 05/17/2023., file a certificate of correction; submit c of c
Nov 29, 2023
Resolve - Class - 1
I observed at the entrance of the main electrical room the installation of the generator transfer switch and the emergency power panel. as per bc 2702.1.7 the main electrical system shall not be located in the
Nov 29, 2023
Resolve - Class - 2
Observed in the hvac room located on the main floor excessive combustible storage ( file cabinets, brooms and paint). no storage shall be kept in the hvac room., repair and/or replace
Nov 29, 2023 · Penalty $1,562
Resolve - Class - 2
Improper and unsafe storage underneath stairs located at staircase b cellar level., repair and/or replace
Nov 29, 2023 · Penalty $312
Resolve - Class - 1
I observed at the entrance of the main electrical room the installation of the generator transfer switch and the emergency power panel. as per bc 2702.1.7 the a.t.s. and power feeders shall not be located in th
May 17, 2023
Resolve - Class - 1
Failure to comply w/the commissioner's order.note:ecb violation #35647107p issued on 06/03/2022 & dob violation #060322ll1601jc issued on 06/03/2022 to provide safety measures at required exposures & maintain
Aug 5, 2022 · Penalty $2,500
Resolve - Class - 1
Failure to provide sidewalk shed where required. as noted building have defective masonry on exposure 1 and 2 and only have a partial shed on exposure 2 sackman st. conditions include spalled bricks/stones,crac
Jun 3, 2022 · Penalty $10,000
Resolve - Class - 1
Door zone restrictor's front and rear door not working tampered with disabled(cu).
Jan 21, 2022 · Penalty $3,125
Resolve - Class - 2
In car phone not working. hydraulic valve needs to be adjusted hard start and stop. device fail drift test move 3 inches and call for re-leveling after the main line is put back in. device does not open at the
Nov 4, 2021 · Penalty $312
Resolve - Class - 2
Bc 3314.8.2 debris netting. at time of my inspection on inactive site i observed supported scaffold erected on sws. i review the scaffold system and observed the debris netting not adequately maintained on site
Mar 11, 2021 · Penalty $625
Resolve - Class - 2
Failure to inspect for a periodic inspection mandated by nycdob (last inspection conducted in 2018)
Oct 2, 2020 · Penalty $1,562
Resolve - Class - 2
1) hoistway access switches not working 2) top of car stop switch is too far from the hoistway door. provide additional stop switch 3) elevator start and stops with a jerking motion.
Mar 2, 2020
Resolve - Class - 1
Electronic edge not working.main lobby door unable to open wires off the controller. hydraulic valve overshooting the floors jumping up and down. provide weights for retest.
Feb 4, 2020 · Penalty $1,250
Resolve - Class - 2
Bc33141-failure to maintain supported scaffold.note:at time of my inspectionof a 4 story building no work in progress.i observed a blue tarboutin hanging loosed in danger of falling.this condition can creat a h
Feb 3, 2020
Resolve - Class - 2
42t7: (42,t,7) missing (2014 nycbc) tag. tag to show dlm compliance
Jan 17, 2020 · Penalty $310
Resolve - Class - 1
Cease use items: 1) front zone lock restrictor inoperative 2) excessive drifting with minimum load while main line is out. full load drift test required for re-inspection. class 2 items: replace worn hoistway d
Dec 10, 2019 · Penalty $3,125
Resolve - Class - 1
5-a-10,6-l-10,8-v-10,98-m-7=(5,a,10)front door restructor not owring this is a safety device to ensure passengers safety (6,l10) front door opening inoperative do not open off the controller (8,v,10)device not
Sep 4, 2019 · Penalty $1,250
Resolve - Class - 1
I observed on the roof and in the third floor mechanical room the improper installation of temporary wiring for a rooftop circuit breaker panel. the cabling supplying power is run over the parapet wall without
Aug 28, 2019 · Penalty $1,600
Resolve - Class - 1
I observed in the 4th floor mechanical room a temporary cable supplying power to a roof top circuit breaker panel laying across the metal ductwork of a hvac system. temp wire shall not come in contact with buil
Aug 28, 2019
Resolve - Class - 2
6.b.10,8.v.10,6.b.10,42.b.10,46.b.10,31.b.1,70.o.2=(6,b,10)restored service to front door opening (8,v,10)device struggle to make it to the top floor.(6,b,10)front door opening was still able to open without ca
Dec 11, 2018 · Penalty $310
Resolve - Class - 1
Cu05a10,05x10. 05a10-cease use item. door zone restrictor has been rendered inoperative. this is a safety device to ensure the elevator passengers safety. repair restrictor and contact ncdob at eir@buildign
Oct 16, 2018 · Penalty $1,250
Resolve - Class - 2
Electrical w/o a permit. observed on roof,the installation of all required branch circuit & power feeders for a backup power generator priorto obtaining & electrical permit. generator serial #2343284,3 phase 80
Aug 27, 2018 · Penalty $800
Resolve - Class - 2
Work does not conform to approved construction documents and/or approved amendments for alt ii job #321765880 loc folder. at time of inspection found: (1)canopy structural steel members dimensions are smaller t
Aug 23, 2018 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in a code compliant manner. observed on the 1st fl(joist)left of the elevator. 2 water closets in a bathroom covered & taped up w/black bags & advised by shelter(stay)that the water
Jul 19, 2018 · Penalty $312
Resolve - Class - 1
97x10,15d6. (97x)entire device is inoperative,repair. (15d)certificate frame is not secure,secure.
Jul 17, 2018 · Penalty $1,250
Resolve - Class - 1
97x17)the only elevator in building is out of service. upon inspection the device is found to be out-of-service creating a hazardous condition as per 1rcny 11-02. restore to service immediately and notify nycdo
Apr 24, 2018 · Penalty $1,250
Resolve - Class - 2
Work w/o a permit. noted: observed on the 3rd fl roof,the installationof 2 storage sheds approx 7ft x 8ft,& the installing of an awning approx 20ft in length supported by 3 4"x4" vertical posts,all work perform
Jan 24, 2018 · Penalty $800
Resolve - Class - 2
21m7,70o2,75m7,45i10,8j1. (21m)missing interlock cover on 4th flr,provide. (70o)pit dirty,clean. (75m)butter spring missing from left side,provide. (45i)governor switch green field is broken @ the connector,rep
Nov 1, 2017
Resolve - Class - 1
Cease use. 7l10,5e1,10h11,29j1,8v1,68m7. (7l)door reopening device defective, this is a safety device to ensure elevator passengers safety. repair electronic edge & contact nyc dob @ [email protected] & 212-
Aug 31, 2017 · Penalty $1,000
Resolve - Class - 2
17h11;6h11;40o2;5h11;39o2;70y2;70o2:1st fl front door;replace roller for car door gate contact(switch)rear door has electrical tape on it;replace clutch rollr(rear)
Jun 13, 2017
Resolve - Class - 2
Sign. observed sidewalk shed is in place. sidewalk shed information panel is not provided. rmdy: comply with code.
Apr 17, 2017 · Penalty $400
Resolve - Class - 2
Failure to paint dedicated sprinkler piping/valves in accordance with section.at the time of my inspection 11:30am i observed in the cellar dedicated sprinkler piping not painted.rem:paint dedicated sprinkler
Mar 3, 2017 · Penalty $800
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.lack of emergency lighting for exist,exit discharges and public corridors per bc1006.1;27-542.cellar level cafeteria 3 emergency light not working.rem:comply wi
Mar 3, 2017 · Penalty $800
Resolve - Class - 2
5x10 rear car door zone restrictor is inoperative.
Feb 1, 2017
Resolve - Class - 2
05x10,14o02,42r11,42r10,70o02. 05x10-both door zone restrictor are not working; 14o02-mirror is not clear; 42r11-6amp fuse in a 3amp circuit; 42r10-wire connected with wire nut, run wires to the terminal block
Dec 7, 2016
Resolve
Complaints
- Unsanitary condition
Mold
Mar 28, 2026 · Apt 23
Close - Heat/hot water
Entire building
Mar 20, 2026 · Apt BLDG
Close - Unsanitary condition
Pests
Jan 18, 2026 · Apt 2045
Close - Unsanitary condition
Pests
Jan 1, 2026 · Apt 205
Close - Door/window
Door
Jan 1, 2026 · Apt 205
Close - Heat/hot water
Entire building
Dec 18, 2025 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 10, 2025 · Apt 204
Close - Heat/hot water
Entire building
Feb 22, 2025 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 16, 2025 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 29, 2024 · Apt 102
Close
Show 40 more ↓
- Heat/hot water
Entire building
Dec 3, 2024 · Apt 303
Close - Heat/hot water
Apartment only
Dec 2, 2024 · Apt 303
Close - Electric
Power outage
Nov 13, 2024 · Apt 1-020
Close - Heat/hot water
Entire building
Nov 12, 2024 · Apt 206
Close - Heat/hot water
Entire building
Jul 30, 2024 · Apt 201
Close - Electric
Power outage
Mar 6, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 1, 2024 · Apt 303
Close - Heat/hot water
Entire building
Oct 9, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Jul 20, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Jun 26, 2023 · Apt 401
Close - Heat/hot water
Entire building
Feb 4, 2023 · Apt 304
Close - Heat/hot water
Entire building
Dec 26, 2022 · Apt 2044
Close - Safety
Fire escape
Dec 23, 2022 · Apt BLDG
Close - Electric
Power outage
Dec 23, 2022 · Apt BLDG
Close - Heat/hot water
Apartment only
Dec 2, 2022 · Apt 4023
Close - Heat/hot water
Entire building
Nov 26, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 2, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 21, 2022 · Apt 205
Close - Heat/hot water
Entire building
Feb 15, 2022 · Apt BLDG
Close - Electric
Power outage
Jan 29, 2022 · Apt 205
Close - Heat/hot water
Entire building
Jan 17, 2022 · Apt 203
Close - Heat/hot water
Entire building
Jan 9, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 24, 2021 · Apt 302
Close - Heat/hot water
Entire building
Dec 22, 2021 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 21, 2021 · Apt ROOM 1
Close - Heat/hot water
Entire building
Dec 15, 2021 · Apt 305
Close - Heat/hot water
Entire building
Dec 12, 2021 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 30, 2021 · Apt BLDG
Close - Heat/hot water
Entire building
May 14, 2020 · Apt 401
Close - Heat/hot water
Entire building
Apr 1, 2020 · Apt 301
Close - Paint/plaster
Ceiling
Jan 10, 2020 · Apt 101
Close - Plumbing
Bathtub/shower
Jan 10, 2020 · Apt 101
Close - Plumbing
Basin/sink
Jan 10, 2020 · Apt 101
Close - Unsanitary condition
Mold
Jan 10, 2020 · Apt 101
Close - Safety
Carbon monoxide detector
Jan 10, 2020 · Apt 101
Close - Heat/hot water
Apartment only
Jan 10, 2020 · Apt 101
Close - Flooring/stairs
Floor
Jan 10, 2020 · Apt 101
Close - Heat/hot water
Entire building
Dec 31, 2019 · Apt 2
Close - Heat/hot water
Entire building
Dec 28, 2019 · Apt 401
Close - Heat/hot water
Apartment only
Dec 20, 2019 · Apt 102
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Care facility (N2)
- Year built
- 1926
- Floors
- 4
- Residential units
- —
- Building area
- 31,650 ft²
- Lot area
- 9,604 ft²
- Zoning
- R6B
- Community board
- 316
- Council district
- 37
- Block / lot
- 1572 / 18
- Assessed value
- $1,023,750
- Landmark / historic district
- No
HPD registration #385629, last renewed Jul 24, 2025.
Questions about 1424 Herkimer Street
Who owns 1424 Herkimer Street?
The owner of record in NYC Department of City Planning PLUTO data is 1424 Herkimer Street Development LLC.
Does 1424 Herkimer Street have violations?
Yes. NYC HPD has recorded 16 housing violations at this property.
Is 1424 Herkimer Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1424 Herkimer Street built?
City records list 1926 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.