roofy

1958 Fulton Street

Brooklyn, NY 11233BBL 3-01548-0019Map

Owner of record: NYC Human Resources Administration

1958 Fulton Street is a school building built in 1912 in Brooklyn, 11233. The owner of record is NYC Human Resources Administration. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
54
ECB violations
72
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 54

  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 26, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 26, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 8, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 11, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - active
Show 40 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 8, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 1, 2014

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2010 inspection report

    Sep 28, 2012

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2010 inspection report

    Sep 28, 2012

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2010 inspection report

    Sep 28, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 10, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 24, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 27, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 24, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 12, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 27, 2004

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 23, 2003

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Dec 24, 2001

    Dob violation - dismissed
  • Construction other optional

    Haz

    Jun 6, 2001

    Dob violation - dismissed
  • Construction other optional

    Second offense

    Jun 6, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Oct 27, 1993

    Vp*-violation unserved ecb- dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed

ECB violations · 72

  • Class - 2

    Failure to maintain building in code compliant manner.school playground retaining wall along fulton stree side cracks and falling apart multiple places.remedy:

    Apr 6, 2022 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code compliant manner cellar level electrical room electrical panels are busted out deteriorating one to water penetration from streets.remedy:repair and/or replace

    Apr 6, 2022 · Penalty $625

    Active
  • Class - 2

    Reissue#35415494l failure to maintain in building in code-compliant manner.observed:at cellar level electrical room.electrical panels are busted and deteriorating due to water penetration from the street.rem:re

    Oct 8, 2021 · Penalty $1,562

    Active
  • Class - 2

    Found eastcoast mobile boiler- model 4c-175 7000000 btus active and operating with defects. smoking on start up. emergency shut off not accessible. permit expired not posted. no protection around bottom of trai

    Nov 25, 2019 · Penalty $625

    Resolve
  • Class - 2

    Failure to comply with the commissioners order contained in summons/violation#35415494l issued on 05/07/19 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102.1.rem:comply with commission

    Sep 12, 2019

    Resolve
  • Class - 1

    Reissue #35386511y failure to maintain building in code compliant manner electrical panels in electrical room are rusted and deterioting repair and/or replace

    May 7, 2019

    Active
  • Class - 1

    Failure to maintain building in code compliant manner. at the time of inspection and observed at cellar level electrical foom, water penetration through foundation wall caused electrical panels rusted and corro

    Apr 8, 2019

    Active
  • Class - 2

    Reissue 35235322r failure to maintain building walls or appurtenancesat the time of inspection and observed at exp3 and exp4 retaining walls facing streets herkimer st and howard av school yard cracks and dete

    Apr 8, 2019

    Active
  • Class - 2

    Operation of a place of assembly w/o a current certificate of operation at the time of inspection and observed at 1st floor cafeteria capacity of 200 people (persons) with no certificate of place of assembly

    Apr 8, 2019

    Active
  • Class - 2

    Reissue 35324882j failure to maintain building walls or appurtenancesat the time of inspection and observed water penetration through foundation walls, caused damaged in electrical room, boiler room and bulkhe

    Apr 8, 2019

    Active
Show 40 more ↓
  • Class - 1

    Failure to maintain building in code compliant manner: at the time of inspection and observed at cellar level at electrical room electrical panels is rusted and in deteriorated conditions. numerous location of

    Feb 27, 2019

    Active
  • Class - 2

    Failure to comply with the commissioner's order contained in summons/violation #35372733m issued 11/26/18 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. note: no document file fo

    Jan 4, 2019 · Penalty $3,125

    Resolve
  • Class - 1

    Failure to maintain bldg in code compliant manner.noted:observed at cellar level the electrical panel is rusted and in disrepair.rem:repair and/or replace

    Nov 26, 2018

    Active
  • Class - 1

    Failure to maintain building in code compliant manner.note:at electrical room in cellar the electrical panel are rusted and in disrepair.rem:repair and or replace

    Aug 31, 2018

    Active
  • Class - 1

    Failure to maintain building in code compliant manner:noted reissue#353294104 issued on 05/16/2018 observed at cellar level at electric meterroom ceiling is deteriorated and water penetration through (panel) an

    Jul 12, 2018

    Resolve
  • Class - 1

    Reissue #35324885p failure to maintain building in code compliant manner. noted: electric meter room at cellar level has water penetration and waer leakage, water is pouring out of an electric enclosure into

    May 16, 2018

    Active
  • Class - 1

    No conductors or equipment shall be located in damp or wet locations. noted: at cellar electric room, electric meter service equipment fire pump and other related electric enclosures re subjected to water. cor

    May 16, 2018

    Active
  • Class - 2

    Failure to maintain bldg in code complaint manner. noted: the doors have defective in the top hinge & not operate properly at interior foyer doors main entrance & room#304,501,502,300,women bathroom next to rm#

    Mar 13, 2018

    Resolve
  • Class - 2

    Operation of a place of assembly w/o a current c of o. noted: at 1st fl cafeteria area,no place of assembly certificate w/occupancy sign posted for 200 persons. remedy: comply w/code/obtain a place of assembly

    Mar 13, 2018

    Active
  • Class - 2

    Reissue#35235322r failure to maintain bldg walls or appurtenanves. noted: water damaged to walls due to water penetration through walls at multiple places at boiler room area & at bulkhead stair'f' & 'g'.

    Mar 13, 2018

    Active
  • Class - 1

    Failure to maintain bldg in code complaint manner. noted: at cellar level,in electrical rooms,penetration water through retaining wall making electric panels rusted & corroded water in danger of contact w/elect

    Mar 13, 2018

    Active
  • Class - 2

    Reissue# 35216184y. failure to maintain bldg wall(s) or appurtenances @ exp#4 left of the school playyard 1 returning wall along side fulton st side crack & falling apart in multiple places. rem: maintain exter

    Apr 20, 2017

    Active
  • Class - 2

    100b10 wheelchair lift makes loud noise in both directions.

    Oct 26, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner exterior; retaining wall running length of the school yard are cracked and falling apart. rmdy: maintain exterior building walls.

    Sep 14, 2016

    Active
  • Class - 2

    Reissue 34934232j failure to maintain blg walls or appurtenances (exterior) exterior foundation wall is porous and allowing water (rain) toenter the cellar causing interior damages. rmdy maintain exterior bldg

    Sep 14, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. maintain issues noted at 5th flr or room 504 they have ceiling leak on 2nd flr room 204 have a leak through wall (exterior) rmdy: repair and/or replace.

    Feb 11, 2015

    Resolve
  • Class - 2

    Falrue to maintain bldg in code compliant manner: provide required corridor width per bc 1016.2; 27-309. obstruction notd: at first flr west conn door from exit () locker and table obstructing corridor.rmdy

    Feb 11, 2015

    Resolve
  • Class - 2

    27-765 re issue 35003999x fail to maintain.noted illegal wall in placeblocking ventilation into cafeteria.drop ceiling in place w/no mechanical ventilation provided.rem:provide adequate ventilation for place of

    May 21, 2014

    Resolve
  • Class - 2

    Exit door not self-closing/do not open.observ that exit"a"ext doors stick & do not open.also doors to ext behind auditorium stick & doors toexit corridor(@ stage left)do not operate properly.rem:repair/replace

    May 21, 2014

    Resolve
  • Class - 2

    Re issue 35003997m work w/o a permit.illegal work noted @ all lvls.corridor walls installed & not fire rated.wall erected in cafeteria obstructing all windows.rem:obtain permit/restore to prior legal condition.

    May 21, 2014

    Resolve
  • Class - 2

    Re issue 34934232j fail to maintain bldg walls/appurtenances.the ext foundation wall is porous & allowing(rain)water to enter the cellar causing interior damage.rem:maintain exterior bldg wall water proof found

    May 21, 2014

    Active
  • Class - 1

    B101,50a. 50a- no work permit filed w/dob for the electrical connection to bldg at 1958 fulton street bklyn from the mobile boiler on the main street.

    Jun 11, 2013 · Penalty $800

    Resolve
  • Class - 2

    Failure to maintain illumination exit signs over staircase doors 5 floor a,d,4 floor b,c 3 floor b,c, 2 floor b,c. rmdy: provide illuminatedexit signs above staircase doors.

    Mar 19, 2013 · Penalty $2,500

    Resolve
  • Class - 2

    Work w/o permit.illegal work noted at all levels corridor walls installed (non fire rates 2 hr)also wall installed in cafeteria obstruction all windows.also corridor walls on all levels have been modified and

    Mar 19, 2013 · Penalty $4,000

    Active
  • Class - 2

    Failure to maintain illegal hardware noted at staircase exit doors,corridor doors,key cylinder/bolt locks in place. rmdy: remove hardware.

    Mar 19, 2013 · Penalty $2,500

    Resolve
  • Class - 2

    27-765.failure to maintain noted illegal wall in place blocking natural ventilation into cafeteria.also drop ceiling in place with no mechanical ventilation,large p.a. space with questionable ventilation.rmdy:

    Mar 19, 2013 · Penalty $4,000

    Active
  • Class - 2

    The plaster is spalling off the walls located in room 501. remedy: repair and/or replace plaster.

    Jan 25, 2012

    Resolve
  • Class - 2

    The exterior foundation wall is porous & allowing water (rain) to enter the cellar causing interior damages. remedy: water proof exterior foundation wall.

    Jan 25, 2012

    Resolve
  • Class - 1

    1st floor. auditorium skylight defective various sections of individual glass lites broken. rem:repair &/or replace.

    Jan 20, 2011

    Resolve
  • Class - 2

    The plastic on the wall & ceiling is spalling & cracked located in thecafeteria (1st floor),main office (2nd floor) & room 505 (5th floor).remedy:repair and/or replace plaster.

    Feb 18, 2010

    Resolve
  • Class - 2

    Failure to maintain building walls or appurtenances. noted: concrete 2'feet high retaining wall is cracked & spalling located on herkimer street adjacent to the public sidewalk on ground level. remedy: maintain

    Jul 8, 2008

    Resolve
  • Class - 2

    Reissue: 34569892m failure to maintain building in code compliant manner. exit lights defective (inoperable) located at exit #3 on the 2nd & 3rd flr level. remedy: repair and/or replace exit lights.

    Jul 8, 2008

    Resolve
  • Non-hazardous

    Re-issue # 34504972p. noted: water is penetrating through walls at cafeteria 1st floor. remedy: stop water penetration & repair wall.

    Mar 21, 2007

    Resolve
  • Non-hazardous

    Exit light defective. noted: at exit 3 stairway 5h. exit light inoper-able. remedy: repair or replace lighting.

    Mar 21, 2007

    Resolve
  • Non-hazardous

    Failure to maintain. noted: at stairways f,g,h,i at every floor window guards 2'x 4' in disrepair. remedy: repair or replace window guards.

    Mar 21, 2007

    Resolve
  • Non-hazardous

    Failure to maintain exterior building wall. noted: water penetration at 3rd floor parapet on herkimer street creating damage to 2nd floor main office. remedy: repair defect at parapet.

    Mar 21, 2007

    Resolve
  • Non-hazardous

    Noted: exit doors are not self closing at 1st floor exit #5. remedy: repair/replace doors.

    Jan 25, 2006

    Resolve
  • Non-hazardous

    Noted: fire stopping is missing at pipes in the electrical room at basement level. remedy: provide fire stopping.

    Jan 25, 2006

    Resolve
  • Non-hazardous

    Noted: water is penetrating through walls at cafeteria 1st floor. remedy: stop water penetration and repair wall.

    Jan 25, 2006

    Resolve
  • Non-hazardous

    Noted: plaster is spalling and falling apart at room #406 and #206. remedy: repair walls and ceiling.

    Jan 25, 2006

    Resolve

Complaints

  • Heating

    Heat related

    Dec 20, 2010 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W9)
Year built
1912
Floors
5
Residential units
—
Building area
150,000 ft²
Lot area
50,000 ft²
Zoning
R6B
Community board
303
Council district
41
Block / lot
1548 / 19
Assessed value
$3,292,650
Landmark / historic district
No

Questions about 1958 Fulton Street

Who owns 1958 Fulton Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Human Resources Administration.

Does 1958 Fulton Street have violations?

NYC HPD has no housing violations on record for this property.

Is 1958 Fulton Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1958 Fulton Street built?

City records list 1912 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.