813 Hancock Street
Brooklyn, NY 11233BBL 3-01487-0074Map
Owner of record: Beford Stuyvesant Early Childhood
813 Hancock Street is a school building built in 1905 in Brooklyn, 11233. The owner of record is Beford Stuyvesant Early Childhood. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 20
- ECB violations
- 7
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 20
- Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 25, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 28, 2020
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 16, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 8, 2018
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 11, 2017
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
May 1, 2014
Dob violation - resolved
Show 10 more ↓
- Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2010 inspection/test
Dec 13, 2011
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
May 5, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 24, 2010
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2008
Dob violation - dismissed - Elevator elevatoroptional
Ll10/81-local law 10/81 - elevator elevatoroptional
Mar 21, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 16, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 22, 2006
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed
ECB violations · 7
- Class - 2
Hydrotherm blr>combustion air duct has the inside screen+outside louver 1/2 clogged+elevator room exhaust air ducted into blr room air duct+wires run thru fire damper+open air grate in blr room ceiling+replacem
Oct 30, 2025 · Penalty $1,280
Active - Class - 2
Found hydrotherm gas fired boiler model-mr-1200b with 4 modules active with defects. circulator pump leaking at seal. correct all violating conditions and submit a certificate of correction.
Aug 20, 2024 · Penalty $625
Active - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor
Sep 2, 2020 · Penalty $1,250
Active - Class - 2
B254,50,50a. as per class 2 b254 28.301.1 failure to maintain 50- flue pipe is incorrect gauge for size of pipe 8"pipe is to be 24 gaugeand 12" is to be 22 gauge. 50a-flue pipe to have proper support (band
Jun 19, 2018 · Penalty $1,562
Resolve - Class - 3
Failure to maintain bldg wall or appurtenances. defect noted: at ramp level near entrance have large crack on ramp creating a trip hazardous condition often pedestrian or visitors to bldg. remedy: maintain ext
Feb 4, 2015 · Penalty $250
Resolve - Hazardous
Illegal use in residential district r2-r3. 4 motor vehicles parked on vacant lot. remedy: discontinue illegal use.
Mar 2, 2005
Resolve - Non-hazardous
Failure to maintain building exteriror wall hazardous defect noted: entire east wall is in total disrepair, the 2 chimneyes are out of plumbhas loose and missing bricks and is in danger of collasping onto adjac
Jul 1, 2004 · Penalty $800
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W9)
- Year built
- 1905
- Floors
- 3
- Residential units
- —
- Building area
- 21,210 ft²
- Lot area
- 9,015 ft²
- Zoning
- R6B
- Community board
- 303
- Council district
- 41
- Block / lot
- 1487 / 74
- Assessed value
- $1,318,500
- Landmark / historic district
- No
Questions about 813 Hancock Street
Who owns 813 Hancock Street?
The owner of record in NYC Department of City Planning PLUTO data is Beford Stuyvesant Early Childhood.
Does 813 Hancock Street have violations?
NYC HPD has no housing violations on record for this property.
Is 813 Hancock Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 813 Hancock Street built?
City records list 1905 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.