Owner of record: NYC Department Of Education

1600 Park Place is a school building built in 1925 in Brooklyn, 11233. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
20
ECB violations
61
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 20

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
Show 10 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 27, 1999

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 27, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations · 61

  • Class - 2

    Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:in the gymnasium front lights,exit five on the first floor six lights

    Apr 2, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not self-closing.noted:on the first floor exit 4 two of the doors were not closing properly.rem:repair/replace door.

    Apr 2, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:water penetration from roof causing ceiling damage in rms #407,421a,405 & 401.remedy:repair and/or replace

    Jan 12, 2023 · Penalty $625

    Resolve
  • Class - 2

    Gauge glass protection rods missing.condensate pump leaking. correct violating condition and submit a certificate of correction.

    Apr 15, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35476027l date of issue:3/6/2020 failure to maintain building in code compliant manner. use of prohibited door and/or hardware per bc 1008.1.8;27-371(j). noted at room 426,423,323 smoke doors by the sec

    Mar 11, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits,exit discharges and public corridors per bc 1006.1;27-381. at 1st fl auditorium 2 place each place 3 lights. remedy:repair/replace l

    Mar 11, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing. noted: at the 1st fl smoke by exit 4,auditorium right rear,left rear smoke by exit 3,cafeteria entrance by 113,smoke by exit 5 by 104 & left smoke by the security desk;the ecxit door

    Mar 6, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. use of prohibited door &/or hardware per bc 1008.1;27-371(j). noted: at rooms 426,423,323smoke doors by the security desk room 101 & the main entrance to the

    Mar 6, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: the door at room 120 is not working properly. remedy: repair &/or replace.

    Mar 6, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at exp#1 on the left side;the main entrance metal fencing to the parking lot is broken defective. remedy: repair &/or replace.

    Mar 6, 2020 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code compliant manner at 2nd floor classrooms 216 + 217 door not working properly not closing, uneven. remedy: replace

    Mar 18, 2019

    Resolve
  • Class - 2

    Reissued 35252618k. failure to maintain building in code-compliant manner. lack of emergency lighting for exit, exit discharge and public corridors per bc1006.1; 27-381. note: at gym on 3rd floor 2 corridors pe

    Feb 27, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. note: at basement level in boiler room ejector pit floor cover door not secure possible of falling into pit. rem: repair and/or replace.

    Feb 27, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:lack of emergency lighting for exits per bc1006.1'27-542.noted:at cafeteria one emergency lighting inoperative.rem:repair and or replace lighting.

    Apr 24, 2017

    Resolve
  • Class - 2

    Reissue #35207754m;failure to maintain building in code compliant manner.noted:spalling plaster @ stairway b @ 5th floor.rem:comply with notice of violation.

    Apr 24, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner (interior). noted @ time of insp spalling plaster in stairway b on the 5th flr & @ rear of auditorium exit 2 ceiling. rem: repair &/or replace.

    Sep 9, 2016

    Resolve
  • Class - 2

    Failure to maintain in code compliant manner: no fire stopping per bc712.3; 27-345. noted @ time of insp, insufficient fire stopping in electrical room in basement. conduit penetration @ ceiling. rem: provide/m

    Sep 9, 2016

    Resolve
  • Class - 2

    27-371(b) reissue # 35018942r plexi vision panels @ 3rd floor classrooms, thermoplastic vision panels installed. remedy: replace w/ code compliant vision

    Jul 15, 2014

    Resolve
  • Class - 2

    Reissue # 35018943z cracked brick walls at 5th floor bulkhead fan roomseveral brick wall w/ hotizontal and vertical cracks. remedy: repair brick masonry

    Jul 15, 2014

    Resolve
  • Class - 2

    27-371(b) plexi vision panels. at 3rd flr classrooms,thermoplastic vision panels installed. rmdy: replace w/code compliant vision.

    Jun 18, 2013

    Resolve
  • Class - 2

    Cracked brick interior walls. at 5th floor bulkhead fan room, several brick wall with horizontal and vertical cracks. rmdy: repair brick masonry.

    Jun 18, 2013

    Resolve
  • Class - 2

    Excessive combustible material throughout entire school at all floors on corridor walls & ceilings as well as light fixture in classrooms,consisting of banners art work & school projects. remedy: remove any &

    Apr 4, 2011 · Penalty $2,500

    Resolve
  • Class - 2

    (r-191) doors @ dining room (p.a. 300970 171 (occupancy load 164) are not self closing. rem:repair/replace door closers.

    Aug 5, 2010

    Resolve
  • Class - 2

    Failure to maintain hazardous at gym defective panic bar gym double doors to rest of bldg won't unlock easily also rear gym door closer doesn't operatr door remains open remedy:repair replace hardware immediate

    May 29, 2009

    Resolve
  • Class - 3

    Reissue 34692291k vertical cracks appr. 12' long in guarded brick two gym walls remedy:repair cracks

    May 29, 2009

    Resolve
  • Class - 1

    Use of prohibited door hardware exterior door located front left of gym chained and padlocked shut while school open remedy:remove illegal hardware

    May 29, 2009

    Resolve
  • Class - 2

    Failure to maintain egress clear and unobstructed on fls 4.3.2 desks chairs book cases dsiplay tables located in corridors reducing width up to 60% remedy:remove obstruction immediately

    May 29, 2009

    Resolve
  • Class - 3

    Vertical crack in glazed brick on both sides of gym approx 12'long. remedy; repair crack.

    Aug 14, 2008

    Resolve
  • Hazardous

    Plaster is cracked on the ceiling located in the gym on the 3rd level.remedy:repair ceiling.

    May 3, 2007

    Resolve
  • Hazardous

    Reissue:34502017h exterior bldg wall has become porous and allowing rain water to enter the bldg causing damages in room 301 on the 3rd level.remedy: water proof exterior wall.

    May 3, 2007

    Resolve
  • Non-hazardous

    Failure to maintain exterior bldg. wall- noted: water penetration through exterior wall at 3rd fl directly through classroom #301. remedy: repair exterior wall of rm #301

    Jan 20, 2006

    Resolve
  • Non-hazardous

    Plaster cracked,missing,spallingon ceiling ofbulkhead # 7. remedy: repair plaster.

    Mar 11, 2005

    Resolve
  • Non-hazardous

    Water penetration through roof of blulkhead at stairway # 7. remedy: repair roof of bulkhead # 7.

    Mar 11, 2005

    Resolve
  • Non-hazardous

    Failure to maintain building - defect is :crack in ceiling and wall i n room 418 & 221 remedy : maintain building - make all necessary repairs

    Mar 8, 2004

    Resolve
  • Non-hazardous

    Failure to maintain building - defect is :unhibited access to roof, n o gates at stair 4/5 & 2/3. remedy : maintain building - make all necessary repairs

    Mar 8, 2004

    Resolve
  • Non-hazardous

    Failure to maintain bldg. defect is: unlimited access to roof, no gates @ stair 4/5 & 2/3 remedy: maintain building- make all necessary repairs.

    Jan 22, 2004

    Resolve
  • Hazardous

    Fialure to maintain hazardous defect is rotten and defective metal door with sharp edges in east wall of boys bath room on 3 floor. remedy; replace door.

    Jan 29, 2003

    Resolve
  • Non-hazardous

    Failure to maintain defects are 4 floor men bathroom and 1 floor boys bath room door locks are missing. remedy; replace door locks.

    Jan 29, 2003 · Penalty $2,500

    Resolve
  • Non-hazardous

    Reissue. failure to maintain. defects are: cracked plaster ceiling. location: rms 221,418 gym, 322,321,317,313,304,201,202,216. remedy: do repairs.

    Jan 16, 2002

    Resolve
  • Non-hazardous

    Reissue> failure to maintain. defect are: water damaged deiling. location: 301,301,222,front gym adjacent to office door. remedy: do repairs.

    Jan 16, 2002

    Resolve
  • Non-hazardous

    Reissue. failure to maintain. defects ate: cracked masonary walls. location: basement locker rooms, emergency sxit sadder on opposite upper wall basement.

    Jan 16, 2002

    Resolve
  • Hazardous

    Failure to maitain. hazadous. defects is: exit door at exit 4+5 not poening properly. panic hardware inoperativ. location: exit 4 + 5 to plaz yard. remedy: do repairs.

    Jan 16, 2002

    Resolve
  • Non-hazardous

    Reissue. failure to maintain. defect are: apalling masory foundation wall. location: basement, locker room. remedy: d0 repairs.

    Jan 16, 2002

    Resolve
  • Hazardous

    Reissue. failure to maintain. defect are: exterior plan yard / parking are patholes and sekin various sections thru out yard. tripping hazard. location: plaz yard/parking area rear of building. remedy: do repai

    Jan 16, 2002

    Resolve
  • Hazardous

    Reissue. failure to maintain. defect are: cracked concrete ceiling beams. location: rms 221,202 +201. remedy: do repairs.

    Jan 16, 2002

    Resolve
  • Non-hazardous

    Failure to maintain defects damaged flooring tiles

    Jun 13, 2001

    Resolve
  • Hazardous

    Failure to maintain defects cracked concrete ceiling beams

    Jun 13, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defects spalling concrete foundation wall

    Jun 13, 2001

    Resolve
  • Hazardous

    Failure to maintain defects extrior playground parking area potholes sinking in rooms section and trip hazards

    Jun 13, 2001

    Resolve
  • Hazardous

    Failure to maintain defects erroded rusted damaged support structure steel lintel's

    Jun 13, 2001

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1925
Floors
4
Residential units
—
Building area
77,741 ft²
Lot area
46,958 ft²
Zoning
R6
Community board
308
Council district
41
Block / lot
1375 / 12
Assessed value
$4,410,900
Landmark / historic district
No

Questions about 1600 Park Place

Who owns 1600 Park Place?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 1600 Park Place have violations?

NYC HPD has no housing violations on record for this property.

Is 1600 Park Place rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1600 Park Place built?

City records list 1925 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.