HPD violations
8
DOB violations
16
ECB violations
28
HPD complaints
3

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
Last violation May 8, 2026

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 8

  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    May 8, 2026

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Jun 13, 2025

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 17, 2024

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 31, 2023

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 9, 2022

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 10, 2022

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 20, 2021

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 6, 2019

    Closed — Violation dismissed

DOB building violations · 16

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 28, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 28, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 14, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 14, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 7, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 7, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 12, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 12, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2010

    Dob violation - resolved
Show 6 more ↓
  • Construction other optional

    Work does not conform to approved construction documents in that two 3 " x 6" steel columns installed under steel floor beams between 1st and 2nd floor at corridor cmu walls. three each approx 5 ft. long w12 st eel conenctors installed betw w12 fl beams above lobby remedy: amend plans and/or conform to plans

    Aug 5, 2009

    Dob violation - dismissed
  • Construction other optional

    Misc. vios. scaffold has not been erected & maintained in a safe mann er so as not to endanger public & property from falling material, tool s, debris or collapse of scaffold remedy: stop all work. comply with nou. erect & maintain scaffold i n a safe manner

    Jul 30, 2009

    Dob violation - dismissed
  • Construction other optional

    Stop work,make safe

    Jan 14, 2009

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Oct 6, 2000

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Aug 10, 1995

    Vpw*-violation unserved ecb-work without permit-dismissed
  • Construction other optional

    C-construction other optional

    Sep 22, 1989

    Dob violation - dismissed

ECB violations · 28

  • Class - 2

    Class 2: elevator top emergency exit (escape hatch) is not properly secured. it has no locking device and could be easily opened from inside the car, allowing unauthirized access to the top of the elevator car

    Jan 29, 2026

    Resolve
  • Class - 2

    Class 2: elevator top emergency exit (escape hatch) is not properly secured. it has no locking device and could be easily opened from inside the car, allowing unauthirized access to the top of the elevator car

    Jan 29, 2026

    Resolve
  • Class - 1

    Observed sprinkler heads spray pattern being obstructed on roof storage room, third floor linen closet and in the basement garbage disposal room. in basement stair case door is hitting sprinkler line, open wast

    Jan 29, 2026 · Penalty $2,500

    Active
  • Class - 1

    Observed in basement hot water heater vent exhausted is not sealed properly. also not having the up dated test for back flow device which is contrary to code sections fgc 503.3 and pc 102.3, repair and/replace

    Jan 22, 2026 · Penalty $6,250

    Resolve
  • Class - 2

    I observed on the roof level an open junction box at the generator with exposed energized wires, also noted the wiring for the lights exposed. this an major shock hazard for persons., comply with ec; repair/ re

    Oct 2, 2024

    Resolve
  • Class - 2

    Excessive storage in the rpz room ( reduce pressure zone room) located at first floor also excessive storage in the water heater room located at cellar level., repair and/or replace

    Oct 2, 2024 · Penalty $312

    Resolve
  • Class - 2

    I observed on all floors the room listed as mechanical room with excessive storage, these rooms are the electrical panel rooms as such no storage is permitted. also noted 5th floor also contains the gas-fired t

    Oct 2, 2024

    Resolve
  • Class - 2

    Observed throughout staircase b sprinkler drain down riser not painted red. as per bc 903.6.1 new buildings. cross connections and risers in new buildings, including buildings constructed pursuant to section 28

    Oct 2, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    I observed the improper raceway installed for the rooftop lights, lfnc is not permitted to be used in lengths greater than 6 ft. and where subject to ambient temperatures greater than allowed. also noted the ra

    Oct 2, 2024 · Penalty $500

    Resolve
  • Class - 1

    Unsafe storage of combustible material and equipment. observed combustible material located underneath stairway leading to cellar level., maintain storage in compliance with fire code

    Oct 2, 2024 · Penalty $2,500

    Resolve
Show 18 more ↓
  • Class - 1

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed hole penetrations located in utility, mechanical rooms throughout buildi

    Oct 2, 2024 · Penalty $625

    Resolve
  • Class - 1

    I observed on all floors the failure to provide tamper-resistant outlets as required in ll 39/2015 for all hallways and common areas accessible to children. photos taken., comply with ec; provide tamper-resista

    Oct 2, 2024

    Resolve
  • Class - 1

    I observed on the 5th floor and the cellar level the failure to provide a remote shut- down as required in mc 1006.8.1 at the point of egress. this is an immediate hazard as it safeguards persons from entering

    Oct 2, 2024 · Penalty $625

    Resolve
  • Class - 2

    Work without permit. noted: at the right side, installed 3 area flood lights at 5th floor. no permit or application on file. lights illuminate adjacent graded lot. remedy: obtain permit if feasible.

    Mar 2, 2017 · Penalty $400

    Resolve
  • Class - 2

    Work does not conform to aproved construction documents &/or approved amendments for altii appl#310298095 of which applicant is requesting aletter of completion:non conforming work noted:1-@ roof area the inst

    May 27, 2010

    Resolve
  • Class - 2

    Fail to safeguard all persons/property affected by const operations. recent smoking refuse observed in violation of nyc fire code 1404.1. smoking refuse observed in electrical panel room,sprinkler room, 1st f

    Aug 5, 2009 · Penalty $1,200

    Resolve
  • Class - 2

    Failure to maintain bldg wall or appurtenances. at time of inspection observed excessive debris accumulated at exterior of bldg. remedy: stop all work maintain exterior remove all debris immediately.

    Jul 30, 2009

    Resolve
  • Class - 2

    Misc violations failure to provide 3ft 6 inch guardrail or equivalent around all flr and perimeter openings. at time of inspection observed openings at elevator shaft bulkhead missing required guardrail. remedy

    Jul 30, 2009

    Resolve
  • Class - 2

    Sec. ac 27-157 28-104.7.1 plans fail to comply with building code. plans for job #310110572 a new building application filed on or about 4/9/08 under professional certification & to create a 5 story hotel,fail

    Feb 5, 2009 · Penalty $800

    Resolve
  • Class - 2

    Sec. ac 27-157 28-104.7.1 plans fail to comply with building code. plans for job #310110572 a new building application filed on or about 4/9/08 under professional certification & to create a 5 story hotel,fail

    Feb 5, 2009 · Penalty $800

    Resolve
  • Non-hazardous

    Failure to comply with the commissioner order to correct the violatingcondition and file a certificate of correction with the nyc departmen t of buildings for notice of violation # 34573060l remedy:correct the

    Feb 16, 2008 · Penalty $500

    Resolve
  • Non-hazardous

    Filing a false certification with the nyc department of buildings pur suant to section 26-126.3 respondent filed a certifcate of correction for notice of violation #34573060l on june -20-2007.an inspection made

    Feb 16, 2008 · Penalty $2,500

    Resolve
  • Non-hazardous

    Work without a permit.noted:wood canopy erected at rear of building without a permit. remedy:obtain a permit.

    Feb 16, 2008 · Penalty $800

    Resolve
  • Non-hazardous

    Altered bldg occupied w/o a valid c of o. noted: permit # 300553238 issued 01/23/97 for the use of poultry & rabbit killing establishment on1st flr has not been signed off & 1st flr is occupied prior to obtanin

    Jun 20, 2007 · Penalty $350

    Resolve
  • Non-hazardous

    Failure to maintain. defects noted: missing fire proofing & exposed loosed electric wiring, poor ventilation at 1 fl poultry establishment. remedy: repair defect noted.

    Jun 20, 2007 · Penalty $800

    Resolve
  • Non-hazardous

    Failure to maintain. defect noted: defective wood enclosure at front of premises is loose & leaning thru-out. also at rear yard of premises wood canopy structure has partially collapsed & rear yard has debris

    Jun 20, 2007 · Penalty $800

    Resolve
  • Non-hazardous

    Work w/o a permit. noted: wood canopy erected at rear of bldg w/o a permit. remedy: obtain a permit.

    Jun 20, 2007 · Penalty $800

    Resolve
  • Non-hazardous

    Altered building occupied without a valid c of o job#300553238.rem:obtain a valid c of o forthwith.

    Oct 6, 2000 · Penalty $350

    Resolve

Complaints

  • Safety

    Window guard broken/missing

    Jan 3, 2024 · Apt 306

    Close
  • Unsanitary condition

    Pests

    Dec 30, 2016 · Apt 504

    Close
  • Unsanitary condition

    Pests

    Dec 19, 2015 · Apt 406

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hotel (H3)
Year built
2008
Floors
5
Residential units
—
Building area
19,950 ft²
Lot area
10,000 ft²
Zoning
C8-2
Community board
308
Council district
36
Block / lot
1201 / 12
Assessed value
$3,385,800
Landmark / historic district
No

HPD registration #388345, last renewed Oct 14, 2025.

Questions about 1324 Atlantic Avenue

Who owns 1324 Atlantic Avenue?

The owner of record in NYC Department of City Planning PLUTO data is Nageshwar LLC.

Does 1324 Atlantic Avenue have violations?

Yes. NYC HPD has recorded 8 housing violations at this property.

Is 1324 Atlantic Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1324 Atlantic Avenue built?

City records list 2008 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.