358 Warren Street
Brooklyn, NY 11201BBL 3-00397-0011Map
Owner of record: NYC Department Of Education
358 Warren Street is a school building built in 1923 in Brooklyn, 11201. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 21
- ECB violations
- 46
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 21
- Elevator elevatorrequired
E-elevator elevatorrequired
Dec 15, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 8, 2019
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Construction other optional
C-construction other optional
Apr 29, 1999
Dob violation - active - Construction other optional
Hazardous
Apr 29, 1999
Dob violation - dismissed
Show 11 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations · 46
- Class - 2
Failure to maintain building in code-compliant manner. broken glass @ custodian office. remedy: comply with code.
Apr 6, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing exit doors. at exits #1, 2, 3, 8, not self-closing at time of inspection. remedy: comply with code.
Apr 6, 2026 · Penalty $625
Active - Class - 2
At the time of inspection, a sidewalk shed was observed in place, but no shed parapet information panel was provided as required by the building code. this condition creates a hazardous condition by causing a d
Mar 5, 2026 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:on 1rst fl exit #1 one of the door on the left is not closing properly.on 1st fl exit #2 doors not closing properly.remedy:repair and/or replace.
Feb 15, 2023 · Penalty $625
Resolve - Class - 2
Re-issue #35561030z(5/10/21)failure to maintain building in code compliant manner.at 4th floor science lab plaster spalling near windows.remedy:repair and/or replace.
Apr 26, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued #35500758m failure to maintain bldg in code compliant manner:lack of emergency lighting for exits,exit discharges & public corridors per bc 1006.1;27-542. noted: observed at 2nd fl stairway 2d&2b,exist
May 10, 2021 · Penalty $3,125
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: observed at 4th fl science lab,spalling plaster near window due to water penetration. remedy: repair &/or replace.
May 10, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits,exit discharges & public corridors per bc 1006.1;27-542. noted: observed in staircase b & d between 2nd & 3rd fl the emerg
Jul 23, 2020 · Penalty $1,250
Resolve - Class - 2
Reissue#35434103z failure to maintain bldg in code compliant manner: noted: observed bon the 1st fl exit #1 & 2 the doors are not opening & closing properly,also in the basement tje auditorium exit h the doors
Jul 23, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted: at 4th floor stair f,e 3rd fl stair a 1st floor exit 1,2 cafeteria basement gym, and auditorium doors are in disrepair /racked.
Jun 3, 2019
Resolve
Show 36 more ↓
- Class - 2
Failure to maintain building in code compliant manner.noted: at 1st floor public hallway/egress passageway near exit 5 obstruction by multiple desk approx. 20. remedy: remove obstruction
Jun 3, 2019
Resolve - Class - 2
Exit door not self closing noted: at 1st floor exit 1c stair h door cracks are in disrepair /non operational. remedy: repair/replace door
Jun 3, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted: at 4th floor staircases a,c,g,h ceilings/walls cracked /holes with missing/ falling plaster.remedy: repair and or replace
Jun 3, 2019
Resolve - Class - 2
Exit door not self closing:re-issue#35253594j at exit 4f,3a,bsmt,a.rem:repair/replace door
Apr 23, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: illumination for exits, exit discharges & public corridors per bc 1006.1; 27-381. existing emergency light are not operational when tested. cafeteria students
Apr 28, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. lack of emergency lightings for exits,exit discharges & public corridors per bc 1006.1;27-542. lighting is out in center of boiler room 4 units are not working
Apr 28, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: @ time of insp on roof 2 flashing is loose on north/west, 2 flashing is on the roof ground @ s/e location, 2 flashing is loose on s/w locations. rem: repair &/
Apr 28, 2017
Resolve - Class - 2
Exit done not self closing, bsmt door 'a', b15,4f, & exit 3 'a' is notself closing. rem: repair/replace door.
Apr 28, 2017
Resolve - Class - 2
Sec: 28-301.1. unlawful placement of furnishings, decorations or otherobjects @ exits that obstruct access to egress from one visibility there of per fdny 2008 code; fc 1027.4. roof bulkhead stairway# f materia
Apr 28, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner lack of emergency lighting for exitws, exits discharges and public corridors.emergency lighting is out in center of boiler room 4 unis are not working when t
Sep 30, 2016
Resolve - Class - 2
Use of prohibited door hardware.door stops @ the following doors:rm 207,300,301,302,307,310,311,312,313,401,402,403,410,418 & also main cafeteria entry doors.rem:remove prohibited hardware.
Jul 16, 2014
Resolve - Class - 2
Reissue 35018125r fail to maintain:defective roof flashing @ roof,loose,hanging & missing roof flashing @ warren/smith area & baltic/smith area.rem:repair & replace metal roof flashing.
Jul 16, 2014
Resolve - Class - 2
27-371(b)vision panels use of prohibited plexiglass in the following doors:stair 1f,stair f 4th fl,room 202,217 & 314.rem:provide required glass panels.
Jul 16, 2014
Resolve - Class - 3
Defective roof flashing at roof,loose,hanging & missing roof flashing.remedy: repair & replace metal roof flashing.
May 10, 2013
Resolve - Class - 2
Work does not conform to approved construction documents noted: sidewalk shed at exposure #1 missing (horizontal) braces. plans checked at side. pictures dates. remedy: conlform to approved plans.
Nov 25, 2011
Resolve - Class - 2
Missing fire stop at gas meter room, 2' x 3' masonry hole covered withplywood and 5" pipe hole at door. @ new elect5ric room, ceiling right side open to concealed space. remedy : provide fire stop as required
Aug 25, 2011
Resolve - Class - 2
Spalling concrete adjacent to hoist area over water main spalling, cracked and separating concrete ceiling exposing steel beam. remedy : remedy : repair concealed ceiling masonry
Aug 25, 2011
Resolve - Hazardous
Hazardous. exit passageway total obstructed noted on 1st flr left siderear staircase obstructed with flr buffers,snow blower,a/c and 8' highgate also noted no stairways are numbered or lettered.remedy: remove a
Jun 16, 2008
Resolve - Hazardous
Re-issue:34509892h,34441913j,34284201p. loose & hanging metal wires, loose bricks, rotten wood in the auditorium located on the 1st floor. remedy: repair auditorium.
Feb 28, 2007
Resolve - Hazardous
Re-issue vio #34283950m. noted: bathrooms need to be upgraded broken stalls & doors in locker (gym) rooms, auditorium bathrooms. remedy: make all necessary repairs, install new bathrooms
Feb 17, 2006
Resolve - Hazardous
Reissue vio #34441913j. noted; auditorium is totally unusable with loose and hanging metal ceiling and cables, missing bricks, rotten wood and holes in walls at various locations. auditorium is being use as a s
Feb 17, 2006
Resolve - Hazardous
Noted: exit door not self-closing. inoperative near stair "e" at 1st flr. remedy: repair/replace door.
Feb 17, 2006
Resolve - Non-hazardous
"reissue" (34387067p) failure to maintain.defect is gym locker room bathroom is unusable and sealed off with plywood.bathroom is defective.remedy:repair bathroom
Jul 8, 2004
Resolve - Non-hazardous
Failure to maintain.defect is:auditorium is totally unusable with loose and hanging metal ceiling and cables,missing bricks,rotten wood and holes in walls at various locations.auditrium is being use as a work
Jul 8, 2004
Resolve - Hazardous
Failure to maintain building defect is water penetration exterior facase 1st & 2nd elevation at n/s sides causing spalling plaster at stairwwll and classrooms.remedy:maintian building make all necessary repairs
Feb 27, 2004
Resolve - Non-hazardous
Failure to maintian building defect is bathrooms need to be upgraded no fresh air intakes remedy:maintian building do all the necessary repairs.
Feb 27, 2004
Resolve - Hazardous
Failure to maintain bldg interior & exterior noted facade needs reporting overall.remedy:maintain building
Jan 9, 2004
Resolve - Hazardous
Failure to maintain building interior & exterior noted:sky lights leaking water into classrooms remedy:maintain building make all necessary repairs eliminate hazardous.
Jan 9, 2004
Resolve - Non-hazardous
Failure to maintian. noted : roof leak- location - auditorium - noted : buckets needed to catch water remedy : repair roof leak
Mar 21, 2003
Resolve - Hazardous
Failure to maintain. noted : locker room bathroos. unusable - blocked off from access * bathrooms in locker rooms need to be renovated * remedy : renovate bathrooms
Mar 21, 2003
Resolve - Hazardous
Failure to maintain building hazardous defect note 1 sidewalk cracked open holes at north and south side of building 2 open mortor joints throughout remedy maintain building make repairs
Apr 11, 2002
Resolve - Non-hazardous
Failure to maintain building noted defects auditiorium has been gutted and abendoned renovatin is required. remedy: maintain building make repairs.
Apr 7, 2001
Resolve - Non-hazardous
Failure to maintain building- noted defects water penetration from exterior facade, causing spallind of plaster in stairwells & class rooms
Apr 4, 2001
Resolve - Hazardous
Failure to maintain builidng noted defects bathrooms need to be up graded broken stalls & doors. remedy. maintain building make repairs
Apr 4, 2001
Resolve - Hazardous
Failure to maintain defects are:(hazardous)(1)water penetration exterior facade 1st and 2nd elevations at north and south sides causing spalling plaster at stairwell and classrooms.(2)repair all tile work at st
Jun 20, 2000
Resolve - Hazardous
Failure to maintain exterior & exterior noted #1 emergency lighting throughout school exception boiler are 2 entrance steps and retaining walls & saeling need full repair 3 peremetr fence needs upgrade 4
Apr 29, 1999
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1923
- Floors
- 4
- Residential units
- —
- Building area
- 51,000 ft²
- Lot area
- 30,000 ft²
- Zoning
- R6B
- Community board
- 306
- Council district
- 39
- Block / lot
- 397 / 11
- Assessed value
- $4,333,500
- Landmark / historic district
- No
Questions about 358 Warren Street
Who owns 358 Warren Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 358 Warren Street have violations?
NYC HPD has no housing violations on record for this property.
Is 358 Warren Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 358 Warren Street built?
City records list 1923 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.