roofy

175 Remsen Street

Brooklyn, NY 11201BBL 3-00250-0007Map

Owner of record: 175 Remsen Owner Tic 1 LLC

175 Remsen Street is an office building built in 1962 in Brooklyn, 11201. The owner of record is 175 Remsen Owner Tic 1 LLC. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
75
ECB violations
51
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 75

  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    May 29, 2024

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Apr 3, 2024

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 6, 2024

    Dob violation - dismissed
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Dec 1, 2023

    Dob violation - active
  • Failure to correct swarmp conditions (facade) facade required

    Failure to correct swarmp conditions

    Nov 1, 2023

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 4, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Hazardous condition (facade) facade required

    Cycle 9b unsafe report filed

    Feb 21, 2023

    Dob violation - dismissed
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Dec 1, 2022

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 28, 2021

    Dob violation - resolved
Show 40 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 28, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 28, 2021

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 2, 2020

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 29, 2020

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 13, 2020

    Dob violation - active
  • Construction other optional

    C-construction other optional

    Mar 18, 2020

    Dob violation - dismissed
  • Sprinkler none

    Failed to file final sprinkler report by july 1, 2019

    Sep 3, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 13, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 13, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 13, 2019

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 10, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 10, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 10, 2017

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 21, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 2, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 2, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 2, 2016

    Dob violation - resolved
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Nov 2, 2015

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Aug 2, 2015

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 2, 2015

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 14, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 14, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 14, 2015

    Dob violation - resolved
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 1, 2014

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 7b technical report by 08/21/2012

    Aug 30, 2013

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 4, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 4, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 4, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 21, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 21, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 21, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 28, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 28, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 4, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 4, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 18, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 18, 2009

    Dob violation - resolved

ECB violations · 51

  • Class - 2

    Replace worn gibs where needed. secure gibs where needed. adjust bottom landing hoistway door access hole. eliminate gaps between brake pads and drum. car does not hold bottom landing call. seal hoist amchine l

    Apr 22, 2025 · Penalty $1,562

    Resolve
  • Class - 2

    Replace worn gibs where needed. secure gibs where needed. adjust bottom landing hoistway door access hole. eliminate gaps between brake pads and drum.

    Apr 22, 2025 · Penalty $1,562

    Resolve
  • Class - 3

    Federal plw-100 boiler=body drain pipes missing at safety valves+defective sail switch at fresh air fan+both building water pressure pumps are leaking into boiler room;correct violation+submit certificate of co

    Sep 16, 2024 · Penalty $500

    Active
  • Class - 2

    Failure to file acceptable cycle 9b report indicating correction of unsafe conditions described in initial facades report required by 28-302.5 for control #909128. remedy: file acceptable report.

    Jan 16, 2024 · Penalty $625

    Resolve
  • Class - 1

    Class 1 item: 2 fuses in dispatch controller have the incorrect fuse rating. elevator main gear case is leaking oil and needs repair. class 2 items: lower elevator cab railing is missing.

    Dec 26, 2023 · Penalty $1,250

    Resolve
  • Class - 1

    Class 1 item: 2 fuses in dispatch controller have the incorrect fuse rating. class 2 items: elevator main gear case is leaking oil and needs repair.

    Dec 26, 2023 · Penalty $1,250

    Resolve
  • Class - 1

    Class 1 item: 2 fuses in dispatch controller have the incorrect fuse rating. class 2 items:elevator main gear case is leaking oil and needs repair.

    Dec 26, 2023 · Penalty $1,250

    Active
  • Class - 2

    Removal of public protection from unsafe facade without approval from the department. -at time of inspection i observed the sidewalk shed protection removed from site. the owner did not obtain department approv

    Dec 11, 2023 · Penalty $1,250

    Active
  • Class - 1

    Failure to comply with commissioner's order.note:violation#35670855x states failure to provide safety measures where to required dated 03/16/2023.as of today 04/18/2023 still no safety measures in place.rem:com

    Apr 16, 2023

    Resolve
  • Class - 1

    Failure to take and provide adequate safety measures such as sidewalk shed fence ect where require to protect and secure public safety from documented unsafe facade as per 1rcny 103.04.facade technical report f

    Mar 16, 2023

    Resolve
Show 40 more ↓
  • Class - 2

    Pedestrian protection does not meet code specification.note:at time ofmy inspection of a 12 storys bldg 1 observed by 5:20am a sidewalk shedat expo#1 of the bldg w/out lighting to generate illuminations.failure

    Nov 10, 2020 · Penalty $2,430

    Resolve
  • Class - 1

    Class 1 cease use item..... gap observed between brake drum and pad. perform brake maintenance and provide date on tag and record in log book. weights required (125% of rated load) for re-inspection to lift cea

    Mar 2, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Bc27-929.1/a.c 27-929.1 failure to complete the installation of full sytem of automatic sprinkler and file a final sprinkler report preparedby a registered design professional by july 1,2019,in an office buildi

    Nov 15, 2019 · Penalty $1,250

    Resolve
  • Class - 2

    Repair and restore device to service.

    Oct 24, 2019

    Resolve
  • Class - 2

    3m7,15m7,92k2,56y2,56y10,39x2. 3m7-misisng city id tag in cab and capacity plate; 15m7-provide location for certificate in elevator missing52k2-rusted hoist rope on machine; 56y2-clean machine oil leak; 56y10-

    Mar 9, 2018

    Resolve
  • Class - 2

    Pedestrian protection does not met code spec.3307.6.5.3 sidewalk shed shall be maintained and used by gc and where there is no gc or active work the bldg owner.noted:at time of inspection shed on exp#1 has brok

    Oct 27, 2017 · Penalty $2,400

    Resolve
  • Class - 1

    05n10 repair bypassed door zone lock and render operative.

    Jun 27, 2016 · Penalty $1,000

    Resolve
  • Class - 2

    59u15,70o02. 59u15-brake maintenance tag; 70o02-pit is dirty.

    Jan 12, 2016 · Penalty $500

    Resolve
  • Class - 2

    59u15,70o02. 59u15-brake maintenance tag; 70o02-pit is dirty.

    Jan 12, 2016 · Penalty $250

    Resolve
  • Class - 2

    50u15,70o02,05x10. 59u15-brake maintenance tag; 70o02-pit is dirty; 05x10-door zone restrictor is not working.

    Jan 12, 2016 · Penalty $500

    Resolve
  • Class - 2

    Partial *swo* licensed rigger designated an unqualified foreman on site.noted:1 worker doing facade repairs w/o licensed rigger or designated foreman on site to supervise workers.rem:stop all work.conform to bl

    Jun 11, 2013 · Penalty $400

    Resolve
  • Class - 2

    Partial *swo* fail notify dept prior to use/inst off c-hooks.note:licensed rigger called in notification for c-hooks,on site the rigger was using a sling set-up.sling req a set of drawings by engineer & app by

    Jun 11, 2013 · Penalty $400

    Resolve
  • Class - 2

    52k11,44h02,56y13,56o02,42o02,42g11,43l11,17h11,17d06,16b11,70o02,12x10-52k-lube or replace,44h-regroove,56y-seal leaks,56o-clean,42o-clean 42g-unreadable fuses,43l-led indicater,17h,d-replace/secure where need

    Nov 29, 2011 · Penalty $250

    Resolve
  • Class - 2

    42g11,42n09,56y13,42o02,56q03,17m11,16b11,17d06,52o02,70o02,42g-unreadable fuses,42n-fmi fuse,56y-seal leaks,42o-clean,56q-splice box,17h,d-replace/secure where needed,52o-clean for proper inspection,70o-clean.

    Nov 29, 2011

    Resolve
  • Class - 2

    17m11,17o06,01b10,02b10,16b11,40b09,56y13,56o02,56q03,42g11,42n09,42o02,76m07,39o02,52m07,70o02-17md-replace/secure where needed,01,02b-muted bell,16b-provide"designated lobby"braille tags,40b-remove debris fro

    Nov 29, 2011

    Resolve
  • Class - 2

    Failure to file an architect/engineer report certifying exit/directional signs are connected to emergency power source/storage battery equipment.rem:file architect/engineer report

    Jan 27, 2010 · Penalty $800

    Resolve
  • Class - 1

    Fail maintain bldg in compliant manner:lack of automatic sprinklers where required per bc 903.2;37-954 observe cell business school space no sprinkler system installed as per requirements 27-954 (j) & 27-954

    Nov 29, 2008 · Penalty $1,000

    Resolve
  • Non-hazardous

    84l10 84-10 car communications.

    Feb 10, 2005

    Resolve
  • Non-hazardous

    15m07/17h11 17-h, lobby

    Jan 29, 2004

    Resolve
  • Non-hazardous

    15m07/17m07/17h11/21h11 17-m,12fl,l, and 11.17-h lobby,21-h locker roller, l,6,7,10 and 11

    Jan 29, 2004

    Resolve
  • Non-hazardous

    17h11 17-h, lobby gibs

    Jan 29, 2004

    Resolve
  • Hazardous

    4a,19b 36 4a hazardous 36 lochinare hot water boiler model rbn 045

    Nov 19, 2003 · Penalty $800

    Resolve
  • Non-hazardous

    17m07/ (17) main fl - basement - 2 - fl - - 7fl

    Feb 7, 2003 · Penalty $180

    Resolve
  • Non-hazardous

    79x11/ 17m07/ (79) restore to service so a full inspection can be made (17) front

    Feb 7, 2003 · Penalty $180

    Resolve
  • Non-hazardous

    70b07/ 17m07/ 16b01/ (17) main rear - (6) rear (7fl) rear (8fl) front (9fl) front (11fl) front (12) front (16) adjust main fl door top

    Feb 7, 2003 · Penalty $180

    Resolve
  • Non-hazardous

    28l12,52h12. -28 replace guide roller, -52 reline brake shoes, call for reinspection before return to service

    Mar 11, 1999 · Penalty $2,500

    Resolve
  • Non-hazardous

    52h12. -52 replace brake shoes, call for reinspection before return toservice

    Mar 11, 1999 · Penalty $2,500

    Resolve
  • Non-hazardous

    41b7-provide up trip switch.

    Feb 5, 1998

    Resolve
  • Non-hazardous

    41b7-provide up trip switch on gov.

    Feb 5, 1998

    Resolve
  • Non-hazardous

    35o,46o,50o,40o,41m,14m,41-m-07 provide up trip switch on governor

    Feb 3, 1998

    Resolve
  • Non-hazardous

    Failure to provide emergency power exit light on floors 8+7.failure to provide emergency power to exit-directional sign on floor exit:8+7. remedy:provide emergency power exit light and to exit-directional sig

    Jun 4, 1996 · Penalty $800

    Resolve
  • Non-hazardous

    52h,74m, (74) nyc designated elevator no (amend rule 208.10)

    Jun 3, 1994

    Resolve
  • Non-hazardous

    52h,74m

    Jun 3, 1994

    Resolve
  • Non-hazardous

    37g,21l, 21. lobby dir.indic.

    Oct 27, 1992

    Resolve
  • Non-hazardous

    37g,

    Oct 27, 1992

    Resolve
  • Non-hazardous

    02i,08v,21l, 21. bobby ind., lights.

    Oct 27, 1992

    Resolve
  • Non-hazardous

    73#;57o;03o; 73. perform five year test properly tag device and file elev. 3 form. 03. top of car.

    Mar 4, 1992 · Penalty $75

    Resolve
  • Non-hazardous

    73#;57o;030; 73. perform 5 year test and properly tag device and file #3.form. 03. top of car.

    Mar 4, 1992 · Penalty $75

    Resolve
  • Non-hazardous

    Stair "re-entry" signs missing 10 c stairs not posted "no re-entry" 10b stairs,same, 6fl c stairs not posted no "re-entry" 6fl b stairs same2nd fl b stairs not posted "no re-entry". remedy provide signs as per

    Mar 14, 1991 · Penalty $500

    Resolve
  • Non-hazardous

    Stair and or elevator sign missing at basement level in "c" stairs c stairway letter missing. remedy provide sign as per code and ll 5/73

    Mar 14, 1991 · Penalty $500

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Office building (O6)
Year built
1962
Floors
12
Residential units
—
Building area
129,520 ft²
Lot area
10,650 ft²
Zoning
C5-2A
Community board
302
Council district
33
Block / lot
250 / 7
Assessed value
$13,057,200
Landmark / historic district
Borough Hall Skyscraper Historic District

Questions about 175 Remsen Street

Who owns 175 Remsen Street?

The owner of record in NYC Department of City Planning PLUTO data is 175 Remsen Owner Tic 1 LLC.

Does 175 Remsen Street have violations?

NYC HPD has no housing violations on record for this property.

Is 175 Remsen Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 175 Remsen Street built?

City records list 1962 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.