roofy

1007 Evergreen Avenue

Bronx, NY 10472BBL 2-03711-0001Map

Owner of record: NYC Department Of Education

1007 Evergreen Avenue is a school building built in 1975 in Bronx, 10472. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
36
ECB violations
73
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 36

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 5, 2019

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2016 inspection/test

    Sep 15, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 29, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 7, 2016

    Dob violation - resolved
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 1, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 29, 2014

    Dob violation - resolved
Show 26 more ↓
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 12, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 7, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 24, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 3, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 13, 2008

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 20, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 7, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 25, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed

ECB violations · 73

  • Class - 2

    Reissue on ecb #35720957j. failure to maintain building in code-compliant manner. noted: due to defective roofing material causing penetration to travel to classroom 302c 3rd floor, teachers lounge 1st floor an

    May 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue on ecb #356688782j. failure to maintain building walls or appurtenances. noted: various step and vertical cracks with missing mortarat all exposures 1, 2, 3, 4, of the occupied building with sidewalk sh

    May 5, 2026 · Penalty $6,250

    Active
  • Class - 2

    Reissue on ecb #35688781h. failure to maintain building walls or appurtenances. noted: foundation wall at basement boiler room has become porous allowing water penetration at various locations observed upon ins

    May 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue on ecb #35720958l. failure to maintain building in code-compliant manner. noted: fire rated classrooms and smoke doors not self-closing due to binding, missing, and on faulty hardware on classrooms, 302

    May 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue on ecb #35688780k. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridosr per bc 1006,1; 27-381. noted: emergency illuminated discharge exit

    May 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Exit door not self-closing. noted: emergency exterior exit door not self-closing due to binding missing and/or faulty hardware on exterior exit door at exit 7 1st fl and exit 10 1st fl observed upon inspection.

    May 5, 2026 · Penalty $625

    Active
  • Class - 2

    28-301.1 reissue#35688783l failure to maintain building in code-compliant manner.ceiling leak at 3rd floor class 302c, 1st floor cafeteria and teachers change all these room have water damage.rem:comply with co

    Jul 16, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35688785p failure to maitain building in code compliant manner3rd floor story at 2nd floor rm 213 next to 202.all have broken door closer.rem:comply with code.

    Jul 16, 2025 · Penalty $6,250

    Active
  • Class - 2

    Reissue#35672273p failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at gym 2 emergency exit lighting,at cafeteria 3 lig

    Sep 24, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35672270j. failure to maintain building in code-compliant manner. noted: ceiling leak at 3rd floor class room #302c, first floor cafeteria, and teacher lounge area due to defective roof. remedy: make n

    Sep 24, 2024 · Penalty $1,562

    Active
Show 40 more ↓
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. noted: at cafeteria and auditorium roof top parapet is not in 42" height as required.remedy: provide parapet/protective railing.

    Sep 24, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35672272n failure to maintain building wall(s)or appurtenancesnoted:at cellar foundation walls has become porous allowing the water into the boiler room at various locations.rem:maintain exterior wall.

    Sep 24, 2024 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35672271l failure to maintain building wall(s)or appurtenancesnoted:at exp#1 brick facade with vertical crack at the corner by main entrance and flag pole,step crack under first floor window by exit#1,m

    Sep 24, 2024 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: ar 3rd floor, stair "a" with broken door closer, second floor corridor door next to room #213, and next to room #202, all has broken door closers. r

    Sep 24, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue #35663149nfailure to maintain building in code compliant manner. noted:observed at roof level of the occupied school building, roofing materialhas become porous allowing water to penetrate down into 3 f

    May 16, 2023 · Penalty $1,562

    Active
  • Class - 2

    Stair and/or floor identification signs missing and/or defective. note: observed at various staircase landings and/or corridor throughout the occupied school building. the location id signs are not provided ide

    May 16, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35663148l failure to maintain building in code compliant manner. noted: observed at various locations throughout the occupied school building, numerous fpsc doors on 1st, 2nd, and 3rd floors used for ex

    May 16, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35663146h failure to maintain building wall(s) or appurtenances. note: observed at cellar level, boiler room foundation walls have become porous and allowing water to penetrate at various locations into

    May 16, 2023 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35665350yfailure to maintain building in code compliant manner note:observed at 3rd fl classroom #302c and at 1st fl cafeteria, and teachers lounge, ceiling in state of disrepair due to water penetratio

    May 16, 2023 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35663147j failure to maintain building wall (s) or appurtenances. note: observed at various locations throughout all 4 exposures of the occupied school building, numerous step cracks, missing mortar be

    May 16, 2023 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35663145x failure to maintain building in code compliant manner: illumination for exits, exit discharges, and public corridors per bc 1006.1; 27-381. noted: observed at various locations of the 1st fl

    May 16, 2023 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35663144y exit door not self closing. note: observed at various locations of the occupied school building, 1st fl exterior exit-discharge doors located at exits2,4,6 and 8 are in state of disrepair and

    May 16, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35577424h exit door not self-closing.noted:observed exterior exit doors at exit#2,4,6 and 9,roof exit door at stair d are not self closing.rem:repair/replace door.

    Jul 1, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35577422y failure to maintain building wall(s)or appurtenances:noted observed foundation walls have become porous allowing water topenetrate into the boiler room area at various locations.rem:maintain

    Jul 1, 2022 · Penalty $3,125

    Active
  • Class - 2

    Reissued#35502400r failure to maintain building in code-compliant manner:noted:observed fpsc doors at various locations throughout floors 1,2 and 3 stairs and classrooms doors are packed and not closing properl

    Jul 1, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:noted:observed, roofing material has become porous allowing water to enter the building into classroom#302c.rem:repair and/or replace.

    Jul 1, 2022 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner:noted:observed at 3rd floor,room 302c,ceilings plaster is damaged due to water penetration,water being caught in a waste bin.rem:repair and/or replace.

    Jul 1, 2022 · Penalty $625

    Active
  • Class - 2

    Reissued#35577423x failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed existing emergency lights labeled#16,by r

    Jul 1, 2022 · Penalty $1,562

    Active
  • Class - 2

    Reissued#35502401z failure to maintain building wall(s)or appurtenances:noted:observed at exposure#1,at exit#1,spalling cement at entrance door overhang,diagonal cracks by exit#1 right side under 1st flr window

    Jul 1, 2022 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35501060p failure to maintain bldg in code compliant manner. noted: during inspection observed the following fpsc doors are missing the automatic door closers &/or are racked. at rm#301c,#303i,double do

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35501059h failure to maintain bldg walls or appurtenances. noted: during inspection observed at exp#1-limestone over main entrance exit#1 has cracks between slab joints due to missing sealent,diagonal

    Jul 21, 2021 · Penalty $3,125

    Active
  • Class - 2

    Re-issue#35501063k failure to maintain bldg walls or appurtenances. boted: during inspection observed at cellar level-boiler room foundationwall has started to become porous at several locations allowing water

    Jul 21, 2021 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35501062z failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridor per bc1006.1;27-381. noted: during inspection observed existing emergency lights at

    Jul 21, 2021 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35501061r exit door not self closing. noted: during inspectionobserved observed at roof level-stair d,t 1st fl-exit#2,at 1st fl-exit#4 & 1st fl-exit#9 are not closing properly when tested. remedy: repai

    Jul 21, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances noted observed at exposure 1, brick retaining wall has vertical cracks at the corners by main entrance and flag pole fragonal cracks under first floor windo

    Jun 30, 2020 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self closing noted observed exterior exit doors at exit 2, exit 4 and exit 9 do not self close doors remain in an open position when opened repair or and replace door

    Jun 30, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits, exit discharges and public corridor per bc 1006.1;27-381 noted observed existing emergency lighst at stair"a" exit 9 at exit 8 , exi

    Jun 30, 2020 · Penalty $625

    Active
  • Class - 2

    Failure to maintain buidling wall(s) or appurtenances noted foundation walls have become porous allowing water to enter into the boiler room area maintin extrrio building wall

    Jun 30, 2020 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner noted observed fireproof self closing door at 2nd floor stair "a" not closing properly due to missing door cloaser 1st floor stair "d" doors are racked and

    Jun 30, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to comply w/the comm's order contained in summons/vio#35373071r issued on 01-11-19 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. no compliance recorded. remedy: comply w/comm's order &/or file

    Mar 8, 2019

    Resolve
  • Class - 1

    Failure to institute/maintain safety equipment measures or temporary construction no toe boards.observed in indoors yard between exit 11and12 high side unprotected.pipe scaffold no toe boards no scaffoling

    Jan 11, 2019

    Resolve
  • Class - 2

    Reissue 35148055x. failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8; 27-371. exit doors on the 3rd flr not self closing, next to girls toilet on 2nd flr, e

    Jun 28, 2017

    Resolve
  • Class - 2

    Fail to maintain bldg in code-compliant manner: use prob door/hardwareall exit doors on 3rd fl not self-closing;doors next to girls toilet on 2nd fl, not self-closing;exit door on 1st fl exit 7,exit d, exit 11

    Sep 30, 2015

    Resolve
  • Class - 2

    Reissue nov # 35017057j failure to maintain building in code-compliantmanner.note:cross corridor doors do not fully close at rooms 311,211,101 rem:repair and/or replace.

    Sep 30, 2015

    Resolve
  • Class - 2

    /05x10/48y13/70z02/70y02/71x10/71q03/ 05x10-repair car door restrictor (zone lock). 48y13-replace seal in hydraulic jack to stop oil leak. 70z02-clean water from pit. 70y02-clean oil fron pit.

    Apr 8, 2015

    Resolve
  • Class - 3

    Reissue - 34957754z. cracked masonry block wall at oil tank room wall adjoining public corridor. remedy: repair block wall.

    May 3, 2013

    Resolve
  • Class - 2

    Mechanical rooms used for storage: boxes, wood chairs, metal box, cardboard boxes. domestic water room: cardboard boxes, 2" x 4" elec eq rm.tall fans, desk, chair. telephone rm - cardboard boxes, wood, plastic

    May 3, 2013

    Resolve
  • Class - 2

    Exterior exit doors and frames rotted out and/or not fully operational. courtyard exteriors doors. 1- exit doors near room 101. 2- exit doors opposite exit 6. remedy: repair/replace according to code.

    May 3, 2013

    Resolve
  • Class - 2

    Cross corridor do not fully close door near room. room 311, 211, 101. remedy: repair/replace doors.

    May 3, 2013

    Resolve
  • Class - 3

    Left-rear near grass area - exterior vertical joint metal cover rustedand rotted out. remedy: repair/replace metal cover over sealant.

    May 3, 2013

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1975
Floors
3
Residential units
—
Building area
92,509 ft²
Lot area
52,028 ft²
Zoning
R6
Community board
209
Council district
17
Block / lot
3711 / 1
Assessed value
$11,370,150
Landmark / historic district
No

Questions about 1007 Evergreen Avenue

Who owns 1007 Evergreen Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 1007 Evergreen Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 1007 Evergreen Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1007 Evergreen Avenue built?

City records list 1975 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.