3540 Kings College Place
Bronx, NY 10467BBL 2-03356-0036Map
Owner of record: NYC Department Of Education
3540 Kings College Place is a school building built in 1928 in Bronx, 10467. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 59
- ECB violations
- 51
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 59
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 21, 2019
Dob violation - resolved - Elevator elevatorrequired
Cease use
Apr 9, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 9, 2018
Dob violation - resolved - Elevator elevatorrequired
Cease use
Apr 9, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed
Show 40 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 5, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 5, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 5, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 29, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 29, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 29, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 8, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 8, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 8, 2015
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2014 inspection/test
Jun 10, 2015
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2014 inspection/test
Jun 10, 2015
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2014 inspection/test
Jun 10, 2015
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 19, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 19, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 12, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 16, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 16, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 16, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 4, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 4, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 4, 2011
Dob violation - resolved - Construction other optional
Stop work failure to safeguard all persons and property affected by co nstruction operations noted: at time of inspection an active site foun dation walls in place ps 94x along exp2 chain link fence open and ungu arded accessible to school job#201011261nb remedy: stop all work along exp2 safeguard public and property call excavation unit 212 442-1698
Feb 2, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed
ECB violations · 51
- Class - 2
Reissue#35721018x failure to maintain building in code-compliant manner.noted:fpsc doors do not self-close properly at 4th flr-staircase e 3rd flr-gym near staircase b.1st flr-staircase f.classroom doors do not
Jun 30, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at the time of inspection,observed at staircase f on 1st,2nd and 3rd flr glass panels were missing 3 in total.at 3rd flr staircase c 2 panels were mis
Jun 30, 2026 · Penalty $1,250
Active - Class - 2
Re-issue #35689010y failure to maintain building in code-compliant manner. noted: at exit 5 by audi. door broken hardware need to be fixed so door works. interior smoke doors near 402m staircase*b) 3rd flr, gym
Jul 28, 2025 · Penalty $3,125
Active - Class - 2
Re-issue #35676245x failure to maintain building wall(s) or appurtenances. noted: at cellar level foundation wall has become porous allowingrain water into the cleaning supply room and adjacent room one of padd
Jul 28, 2025 · Penalty $6,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner: lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. noted: emergency lights did not turn on when being tested
Jul 28, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: 1st flr(exit 8) exit light was not operational when tested. reme
Jul 28, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner. at exit 5 by aud., door broken hardware need to be fixed so door works. remedy: repair and/or replace.
Oct 17, 2024 · Penalty $625
Active - Class - 2
Failure to provide power to emergency exit lighting. at exit 6 emg. light unit. no pwer to unit red light not on unit not working, also light on ceiling not working. in gym 2 lights ripped of top of emg. light
Oct 17, 2024 · Penalty $1,250
Active - Class - 2
Failure to maintain building wall(s) or appurtenances. noted: at cellar level, foundation wall has become porous allowing the rain water into the cleaing supply room and adjacent room. one puddle of water obser
Jul 21, 2023 · Penalty $1,250
Resolve - Class - 2
Excessive oil leaking in the pit, make all the necessary repairs to eliminate the leak & clean the pit. motor room communication inoperative, repair. non-essential equipment in the motor room (empty oil buckets
Apr 20, 2023 · Penalty $625
Active
Show 40 more ↓
- Class - 2
Excessive oil leaking in the pit, make all the necessary repairs to eliminate the leak & clean the pit.
Apr 20, 2023 · Penalty $625
Active - Class - 2
Emergency signs at elevator call station missing defective or non compliant with section requirements note the elvator at 1st floor and basement not having emergency call signs install and or repair signs
Jul 26, 2021 · Penalty $625
Resolve - Class - 1
81y11,81y11,39y02,70y02,67x10,40o09,71x10. 81-replace packing on right and left cylinders; 39-clean oil of car top; 70-clean oil in pit; 67-repair in car phone; 40-clean machine room; 71-repair pit light
May 14, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner;lack of emergency lighting for exits,exit discharges & public corridors per bc 1006.1;27-542. noted: in basement,cafeteria emergency light packs are not working
Oct 31, 2016
Resolve - Class - 2
Occupancy contrary to that allowed by the c of o or bldg dept records. noted: in the school yard/playground,premises is being occupied as a parking lot,observed 19 motor vehicles in the play yard at the time of
Oct 31, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: provide required corridor width per bc1016.2;27-369(partial obstruction). noted: on the 3rd,2nd & 1st floors corridors in front of stair b are partially obstru
Oct 31, 2016
Resolve - Class - 2
Defective exterior pavement adjacent to exit 3, sunken and uneven paver stones creatin a trip condition at stair edge. remedy: reset exterior paver stones
Jul 23, 2014
Resolve - Class - 2
Exit door not self closing properly at multi room 102, door is rack toframe w. hinge popped. remedy: repair door
Jul 23, 2014
Resolve - Class - 2
No fire stop. at cellar level electric room w/grate over doors. remedy: maintain fire stop, seal opening.
Jun 1, 2011
Resolve - Class - 2
Defective doors. at 2nd flr, the smoke door has broken hinges and do not operate. remedy: replace as required.
Jun 1, 2011
Resolve - Class - 2
Reissue : 34761974x exterior brick facade & foundation wall has becomeporous and allowing rain into the auditorium 1st fl & boiler room ( west side ) causing interior damages at cellar level. remedy: water proo
Jun 2, 2010
Resolve - Class - 2
Interior corridor hallway is being partially obstructed by chairs, tables & cabinets located on the 2nd fl level by the main office. remedy: remove obstruction
Jun 2, 2010
Resolve - Class - 2
The mortar is missing between bricks located in room 422 on the 4th flloor level right above the windows. remedy: replace missing mortar between bricks
Jun 2, 2010
Resolve - Class - 2
Sec. bc1017 27-369 exit passageway & corridor obstructed noted on 4th flr,1st flr tables,chairs filing cabinets stored (1l) corridor,also noted at auditorium boxes partial obstruction exit passageway also at ex
Mar 12, 2009
Resolve - Class - 2
Re 34646980z,34646979l exterior brick wall allowing water to enter at auditorium on 1st flr around multiple windows also water penetration at north side foundation wall basement level. remedy: seal all penetrat
Mar 12, 2009
Resolve - Class - 1
Sec. bc100.1.3 stop work misc violations failure to maintain egress clear & unobstructed at time of inspection,foundation walls in place. construction fence compromises school (ps94x) egress. auditorium & lunch
Feb 2, 2009
Resolve - Class - 2
Provision of law 27-195 miscellaneous violation failure to notify dob with 24-48 hours of start of excavation. rem: comply with notice of violation officially notify dob by calling 212-227-4416 and obtian confi
Dec 29, 2008 · Penalty $4,000
Resolve - Class - 2
Provison of law 27-1032b miscellaneous violations failure to provide 3ft 6in guardrails or solid enclosure around open and accessible sides of excavation no guardrails around open excavation. rem: comply with n
Dec 29, 2008 · Penalty $800
Resolve - Hazardous
Reissue: 34592497h roof has become porous and allowing rain water below in room 454 causing interior damages on the 4th flr level. remedy: waterproof roof above room 454.
May 6, 2008
Resolve - Non-hazardous
Reissue: 34592496x exterior brick facade has become porous and allowing rain water to enter bldg causing interior damage in the auditorium on the 1st flr. remedy: waterproof brick facade.
May 6, 2008
Resolve - Non-hazardous
Reissue: 34592495y foundation wall has become porous and allowing rai n water to enter the bldg causing interior damages on cellar level. remedy : waterproof foundation wall.
May 6, 2008
Resolve - Hazardous
Reissue: 34592494m brick parapet is bulging at roof level on the north/east corner. remedy: repair brick parapet wall.
May 6, 2008
Resolve - Hazardous
Water penetration through roof into room # 454 remedy: stop water penetration / make all necessary repairs
Aug 24, 2007
Resolve - Hazardous
Reissue 34519234p water penetration through exterior brick wall into 1st floor auditorium, left side near window and right side near window by stage, room # 219. remedy: stop water penetration / make all necess
Aug 24, 2007
Resolve - Hazardous
Water penetration through exterior foundation wall into cellar boiler room @ north / west area. remedy : stop water penetration / make all necessary repairs
Aug 24, 2007
Resolve - Hazardous
Brick parapet has bulging brick & missing, cracked bulging mortar @ east & n/e sides @ interior ( roof side ) and @ west side. brick facade has cracked brick @ water way from roof @ west side, south waterway
Aug 24, 2007
Resolve - Non-hazardous
Reissue:34466829h.exterior brick facade has become porous & allowing rain water to enter the bldg & causing damage to the interior finish ofthe auditorium by the windows above adj to stairway b & rear window
Apr 21, 2006
Resolve - Hazardous
Failure to maintain building. defects noted: 1st floor auditorium, left side only at rear & front near stair b has water coming in above windows. remedy: maintain building. make all necessary repairs.
Feb 10, 2005
Resolve - Non-hazardous
Failure to maintain building. defects noted: bulkhead stair c water coming in over roof door. also noted: classroom 461 has a leak from roof running down vertical pipe. remedy: maintain roof. make all nec
Feb 10, 2005
Resolve - Non-hazardous
Failure to maintain:defect active leaks from roof eroding ceiling tile& ceiling tile grid location :roof leaking at center joint eroding corridor interior .remedy:make all necessary repairs.
Jan 8, 2004
Resolve - Non-hazardous
Failure to provide panic hardware where required by law.location;cafeteria 360 people occupancy
Mar 10, 2003
Resolve - Hazardous
Failure to maintain;defects are;rear concrete platform buldging & deteriating & causing fire exit doors to become inoperable.location;rear exit
Mar 10, 2003
Resolve - Non-hazardous
Failure to provide panic hardware where required by law at the gymnasium and auditorium. remedy; provide panic hardware.
Feb 27, 2002
Resolve - Non-hazardous
Failure to maintain defect is: spalling, deteriorating plaster at ceilings and walls stairwell #9 vestbule #4 and #5 rooms #423,420,403 and cage area 4 fl. remedy; repair spalling plaster area entire school.
Mar 14, 2001
Resolve - Non-hazardous
Failure to maintain defects is roof leaks at 4 th floor cage area roof leaks at sky lights vestibule area exit # 4 and # 5 remedy repair roof and replace broken skylights
Mar 14, 2001
Resolve - Hazardous
Failure to maintain defect is paved surfaces at rear of premises are sinking have cracks and trip hazards recently boiler upgrade excavated area not yet repaved water accumulation at various areas remedy mainta
Mar 14, 2001
Resolve - Hazardous
Failure to maintain exterior bldg wall defect id at rear of premises masonary entrance steps 4 have deteriorated risers and treads are spalling and have major trip hazards retaining walls have long open vertica
Mar 14, 2001
Resolve - Non-hazardous
Failure to maintian.defects is defective hvac system at school.thermosstats defective,inability of custodial staff to provide fresh air at childrens classroom during winter.rem:maintain bldg,repair defective hv
Mar 14, 2001
Resolve - Non-hazardous
Failure to maintain defect is floor at cage room 4th fl has rotten with open holes some areas are buckling remedy repair floor at cage are in cafeteria
Mar 14, 2001
Resolve - Non-hazardous
Failuer to maitnain exterior defect is no draining for minischool glass rm no drains in playground area remedy provide drinage
Apr 8, 1999
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1928
- Floors
- 4
- Residential units
- —
- Building area
- 139,464 ft²
- Lot area
- 49,387 ft²
- Zoning
- R7-1
- Community board
- 207
- Council district
- 11
- Block / lot
- 3356 / 36
- Assessed value
- $9,693,900
- Landmark / historic district
- No
Questions about 3540 Kings College Place
Who owns 3540 Kings College Place?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 3540 Kings College Place have violations?
NYC HPD has no housing violations on record for this property.
Is 3540 Kings College Place rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 3540 Kings College Place built?
City records list 1928 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.