341 East 207 Street

Bronx, NY 10467BBL 2-03351-0001Map

Owner of record: NYC Department Of Education

341 East 207 Street is a school building built in 1914 in Bronx, 10467. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
34
ECB violations
59
HPD complaints
5

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 34

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 19, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 19, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 24, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 24, 2020

    Dob violation - resolved
Show 24 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 24, 2020

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 20, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 29, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 29, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 4, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 4, 2017

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Feb 10, 1993

    Vp*-violation unserved ecb- dismissed

ECB violations · 59

  • Class - 2

    Reissue ecb#35721412y failure to maintain building in code-compliant manner.noted backup generator on the roof not working.rem:repair and/orreplace.

    Jun 30, 2026 · Penalty $3,125

    Active
  • Class - 2

    Exit door not self closing.noted exit doors#5 and #6 not self closing.rem:repair/replace door.

    Jun 30, 2026 · Penalty $625

    Active
  • Class - 2

    Reissue: 35689026p-failure to maintain building in code-compliant manner: back up generator on roof for emergency lights not working. emergency was tested and working properly. remedy: comply with code.

    Jul 28, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35689015n-failure to maintain building in code-compliant manner: temp c ofo exp: 4/23/24. no c of o on file up to date. remedy: comply with code.

    Jul 28, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: 2nd floor corridor door missing closer: exit #6 corridor door not self-closing properly. remedy: comply with code.

    Jul 28, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: use of prohibited door and/or hardware per 1016.2; 27-369: exit #5 at kitchen area has turn knob. remedy: comply with code.

    Jul 28, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue ecb#35721413x altered/changed building occupied without a valid certificate of occupancy as per 28-118.3.1;28-118.3.2.noted cofo#2018457-0000004 expired 4/23/2023.rem:obtain valid cofo or discontinue il

    Jun 30, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. backup gen on roof not working which is needed under pa for rooms no emg installed only gen for full building. last oil done 2017 listed on filter. remedy:

    Oct 15, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. temp c of o exp4/23/2024 no new c of o on file for school. remedy: repair and/or replace.

    Oct 15, 2024 · Penalty $625

    Active
  • Class - 2

    Reissued#35582578r failure to maintain building in code-compliant manner.noted:observed at cellar level in electrical room water penetratingthru wall behind electrical panel.rem:replace and/or replace.

    May 26, 2022 · Penalty $1,562

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code compliant manner note at cellar level in electrical room storage of combustible material in room ie (ceiling tiles, cardboard boxes,ladder and other construction materials r

    Jul 23, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner note at cellar level in electrical room water penetration thru floor causing water to paddle in front of electrical switch boxes this is a hazardous conditi

    Jul 23, 2021 · Penalty $625

    Resolve
  • Class - 1

    Fail to notify the dept upon insp as noted @ active demo site,excavators,demo equip,concrete rubble & re-bar on site no notification was given to dept prior to starting demo.rem:notify dept as per code.

    May 31, 2014 · Penalty $1,200

    Resolve
  • Class - 2

    Occupancy contrary to that allowed by the cofo or bldg dept records. reissue 34980841m - cars being illegally parked in children play area.rmdy: discontinue illegal use of amend cofo.

    Jul 26, 2013

    Resolve
  • Class - 2

    Altered/changed building occupied w/o a valid cofo as per 28-118.3.1 28-118.3.2 re-issue ecb #34987201x, issued 7-21-12. nb-98-1987 (zp0003562)rmdy: obtain valid cofo &/or discontinue illegal use.

    Jul 26, 2013

    Resolve
  • Class - 2

    The following exit doors are not self-closing. 1-door to playground; 2-west door; 3-east door. rmdy: repair/replace door.

    Jul 26, 2013

    Resolve
  • Class - 2

    Porous foundation wall responsible for interior damage to electrical room being inundated w/rainwater. reissued. ecb#34980843x (issued 7-12-12). rmdy: maintain exterior walls

    Jul 26, 2013

    Resolve
  • Class - 2

    Reissue 34918847x altered/changed building without a valid cert of occupancy temp cert of occupancy nb2p0003562 temp expired on 1/19/09. nb98/1987. rem:obtain a valid cert of occupancy.

    Jul 21, 2012

    Resolve
  • Class - 2

    The foundation wall has become porous & allowing rain water into the electrical room causing interior damages. remedy: water proof foundation wall.

    Jul 12, 2012

    Resolve
  • Class - 2

    Reissue: 34918845m occupancy contrary. noted: p.s.56 school staff members are parking their vehicles in the children play yard. approx 12 vehicles are parked in the children play yard. remedy: discontinue illeg

    Jul 12, 2012

    Resolve
  • Class - 2

    Reissue: 34918844k the electrical room is lacking fire stopping aroundthe pipe pentration at the cellar level. remedy: provide/maintain firestopping.

    Jul 12, 2012

    Resolve
  • Class - 2

    Rear auditorium is partially obstructed by desk,chairs on the 1st floor main entrance. noted: rear auditorium is being as a office. an public assembly permit #200470560 for 330 permit. remedy: provide free and

    Jul 12, 2012

    Resolve
  • Class - 2

    Defective doors. at mini school center entrance, the exterior exit doors are racked and jam in frame w/one door seized closed and frame eroded and loose at bottom. remedy: replace doors and frame.

    Jun 1, 2011

    Resolve
  • Class - 2

    Defective doors. at mini school, the fire proof self-closing doors - smoke - are racked w/bent hinges and not self-closing. remedy: repair doors to properly open and self-close.

    Jun 1, 2011

    Resolve
  • Class - 2

    Reissue #34855794x. bldg occupied w/o valid c/o. mini school occupied under nb 98/87. 200003562 temporary c/o expired. remedy: obtain c/o.

    Jun 1, 2011

    Resolve
  • Class - 2

    Reissue #34855795h. partial obstruction. at mini school main corridor,partial corridor obstruction w/tables, chairs, computer hooked up, being used as mini classroom w/student instruction at time of nspection.

    Jun 1, 2011

    Resolve
  • Class - 2

    Missing fire stop. at cellar level electric, conduit penetrations at ceiling and wall w/no fire stop. remedy: provide fire stopping.

    Jun 1, 2011

    Resolve
  • Class - 2

    Partial corridor obstruction. 1st,2nd,3rd flr corridors partially obstructedw/rolling carts, tv, computers w/power hook up, tables and chairs, boxes. remedy: remove all items, maintain corridor width clear.

    Jun 1, 2011

    Resolve
  • Class - 2

    Water penetration. exterior foundation wall has become porous allowingrain water penetrate into electric room w/standing water present. aidsroom w/bubbling paint. remedy: water proof exterior foundation walls.

    Jun 1, 2011

    Resolve
  • Class - 2

    Reissue #34855791k. missing door checks. at various classroom doors throughout (too numerous to list) missing door checks, doors are not self-closing. remedy: provide door checks so doors properly self-close.

    Jun 1, 2011

    Resolve
  • Class - 2

    Occupancy contrary. vehicle parked in school yard playground as parking lot. remedy: discontinue illegal use.

    Jun 1, 2011

    Resolve
  • Class - 2

    The plaster on the walls is spalling off located in room no # 2, # 4 ( cafeteria ) & class room 16 remedy: repair and / or replace plaster on wall

    Jun 3, 2010

    Resolve
  • Class - 2

    Corridor width is partially obstructed on hallway by tables & chairs while being used as mini - class room sessions. remove obstuction

    Jun 3, 2010

    Resolve
  • Class - 2

    Reissue : 34770468h certificate of occupancy has expired on 1/19/09 & bldg is still being occupied as a school. remedy: obtain valid certificate of occupancy and / or discontinue illegal occupancy

    Jun 3, 2010

    Resolve
  • Class - 2

    The plaster is spalling off the wall located in the gymnasium ( multi purpose ) & the aids room at the basement level. remedy: repair and / or replace plaster on wall

    Jun 3, 2010

    Resolve
  • Class - 2

    Reissue : 34761971k interior corridor width is partially obstructed onthe 1st & 3rd fl level w/ tables & chairs noted: mini class rooms are being held within the hallways. remedy: remove obstruction forthwith

    Jun 3, 2010

    Resolve
  • Class - 2

    Reissue : 34761972m interior classroom doors is missing door checks throughout the school : remedy: install missing door checks

    Jun 3, 2010

    Resolve
  • Class - 3

    Re 34646968x multiple classroom doors are missing door checks throughout school. remedy: install door checks.

    Mar 12, 2009

    Resolve
  • Class - 2

    Sec. bc1017 27-369 re 34646967y corridor width obstructed with tables,chair 3rd flr,1st flr,also noted front & rear of auditorium being occupied as offices obstructing exit passageway (1st flr) basement level

    Mar 12, 2009

    Resolve
  • Class - 1

    New bldg occupied w/o a valid c of o. noted: mini school bldg nb 398/87 2000035362t005 expired 1-19-09. remedy: obtain valid c of o.

    Mar 12, 2009

    Resolve
  • Class - 2

    New bldg occupied w/o a valid c of o noted school bldg nb#98/87 2pooo3562t005 expired 1-19-09. remedy: obtain valid c of o.

    Mar 12, 2009

    Resolve
  • Hazardous

    Roof has become porous & allowing rain to enter the bldg causing interior damages below in classrm # 1 remedy:water-proof

    May 2, 2008

    Resolve
  • Non-hazardous

    Various classrm doors are missing door checks thru-out the school on every fl remedy:replace missing door checks

    May 2, 2008

    Resolve
  • Hazardous

    Rear exit door is partially blocked with a file cabinet & security desk in the auditorium on the 1st fl level remedy:remove obstruction

    May 2, 2008

    Resolve
  • Hazardous

    Interior classrm door is missing located at rm 202 on the 2nd fl remedy:replace missing door

    May 2, 2008

    Resolve
  • Hazardous

    Auditorium door across from room # 104 opens only half way due to bottom hitting floor. remedy: repair / adjust door

    Aug 23, 2007

    Resolve
  • Non-hazardous

    Reissue:34466481x.roofing is not water tight and allowing rain water to enter the bldg and causing damage to the interior finish above rooms#9,12 and 16.remedy:repair roof.

    Apr 20, 2006

    Resolve
  • Non-hazardous

    Failure to maintain building. defect noted: classroom 9 bathroom ceil-ing has a roof leak. remedy: maintain building. make all necessary repairs.

    Feb 8, 2005

    Resolve
  • Non-hazardous

    New building occupied wihtout a valid cofo(mini school)temp cofo#2p0003562 exp sep 17 2003 remedy:obtain a valid c of o

    May 12, 2004

    Resolve
  • Non-hazardous

    Failure to maintain. defect is door inoperable dragging comming loose from hinges. location mini school bathrooms all. make necessary repairs.

    Feb 28, 2003

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Jan 21, 2019 · Apt BLDG

    Close
  • Heating

    Heat related

    Nov 14, 2013 · Apt 3C

    Close
  • Heating

    Heat related

    Jan 26, 2007 · Apt 2

    Close
  • Heating

    Heat related

    Dec 14, 2006 · Apt 2

    Close
  • Nonconst

    Vermin

    Dec 14, 2006 · Apt 2

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1914
Floors
4
Residential units
—
Building area
83,077 ft²
Lot area
45,652 ft²
Zoning
R5B
Community board
207
Council district
11
Block / lot
3351 / 1
Assessed value
$6,232,501
Landmark / historic district
No

Questions about 341 East 207 Street

Who owns 341 East 207 Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 341 East 207 Street have violations?

NYC HPD has no housing violations on record for this property.

Is 341 East 207 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 341 East 207 Street built?

City records list 1914 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.