3961 Hillman Avenue

Bronx, NY 10463BBL 2-03252-0182Map

Owner of record: NYC Department Of Education

3961 Hillman Avenue is a school building built in 1932 in Bronx, 10463. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
62
ECB violations
40
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 62

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
Show 40 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 9, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 9, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 17, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 17, 2017

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 11, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 11, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 15, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 15, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 1, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 1, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 24, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 24, 2013

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 14, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 14, 2011

    Dob violation - resolved
  • Construction other optional

    C-construction other optional

    May 13, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed

ECB violations · 40

  • Class - 2

    Failure to maintain building in code-compliant manner. noted: step crack on retaining reb brick wall, seperating from base foundation at exposure 1 and 4 corner. remedy: repair and/or replace.

    Mar 19, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: fire rated classroom doors and smoke doors not self-closing due to missing and/or defective hardware or binding on classrooms, 421, 413, 410, 409, 4

    Mar 19, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted: emergency exit exterior door not self-closing due to binding missing hardware or faulty hardware on 1st floor exit 8 stair 3 1st floor and exterior door cellar level. remedy:

    Mar 19, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: exit discharge illumination box 11, 12, 19, 18, 17, 1st floor, b

    Mar 19, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: window cracked on door at exit 9 exterior 1st floor and window at exposure 3 playground and door 8 at cellar level, including missing panels(wire me

    Mar 19, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35644598p failure to maintain building in code compliant manner.playground has cracks on ground causing tripping hazards.rem:comply with code.

    Apr 2, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35663221z: park area for kids has multiple cracks throughout.remedy: comply with code.

    Apr 11, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35644598p failure to maintain building in code-compliant manner.at time of inspection observed at playground fl scab has several cracks at various locations show from aprox 1 1/2 " to 1" inch width & v

    Feb 27, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.note playground floor slab has several cracks at various locations that vary from approx 1/2''to 1'' inch width and various lengths.remedy:repair and/or rep

    Mar 22, 2022 · Penalty $625

    Resolve
  • Class - 1

    Bc3314.4.8 maintenance. scaffolds. all components of and attachments to the scaffold shall be maintained in a good condition. noted: at time of inspection, i observed supported scaffold installed on exp #3 with

    Jan 19, 2019

    Resolve
Show 30 more ↓
  • Class - 2

    Failure to maintain bldg in code-compliant manner. noted: in room #2014 at 2nd story (aks electrical closet) observed over 30 folding chairsbeing stored.

    Jan 22, 2018

    Resolve
  • Class - 2

    Exit door not self closing. noted at 3rd story stairway "f" door not self closing. door is out of plumbing and draggig on floor. rmdy: repair/replace door.

    Jan 22, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at cellar in room labeled "ats/electrical room" water penetrating into room w/electrical panels and has standing water. leak coming from "vacuum

    Jan 22, 2018

    Resolve
  • Class - 2

    Reissue #35146806z exit door not self-closing. exit door(s) not self- closing. exit door(s) not slef-closing and 4th story stair f and 3rd story stair h. remedy: repair and or replace doors noted. comply with

    Mar 18, 2016

    Resolve
  • Class - 2

    Exit door(s) not self-closing.@4th story stair f & 3rd story stair h.rem:repair &/or replace doors noted.

    Jul 13, 2015

    Resolve
  • Class - 2

    Broken glass @ basement entrance to apart.exit door bottom glass panel is broken,repair glass with sheet metal or aluminum to prevent future breaks.rem:replace glass panel on door

    Jul 10, 2014

    Resolve
  • Class - 2

    Reissue #34981186j. vertical separation cracks in brickwork of facades.locations:4 to roof above 1st dorrway left of new bldg. 4 to roof hillman facade @sedgwick.4 to roof sedgwick facade @hillman.rem:maintain

    Apr 3, 2013

    Resolve
  • Class - 2

    Leaking water from vacuum pump causing ponding of water on floors.location:boiler room/generator room/electric panel room. remedy: maintain bldg as per code.

    Apr 3, 2013

    Resolve
  • Class - 2

    Excessive combustible art work at 1st & 2nd flr corridors combustible art work hanging from ceiling wall to wall & protruding paper art workfrom walls. rem:remove all excessive combustible art work.

    Jun 20, 2012

    Resolve
  • Class - 2

    Partial obstructions. at 4th flr gym rear stairway with sports equipment. new wing 1st,2nd flrs with various tables & art work. rem:remove all items maintain corridor width clear.

    Jun 20, 2012

    Resolve
  • Class - 2

    Cracked brick facade at corner of hillman & sedgwick avenue 4th flr 10vertical crack with minor seperation of brick masonry. rem:repair exterior brick masonry.

    Jun 20, 2012

    Resolve
  • Class - 2

    Expired tco temporary cert of occupancy 201023123 too4 expired 6/17/12rem:obtain valid c/o or discontinue illegal use.

    Jun 20, 2012

    Resolve
  • Class - 1

    Use of rigging equipment w/o a rigger lic noted: no rigger on site hoisting ( ) to 5th fl roof. cw #3744 exp 12-18-10 national crane/model 9103a ser #293253 boom truck set up & working operator dragon

    Sep 1, 2010

    Resolve
  • Class - 2

    Roof access gate locked w/ chain & padlock remedy: remove illegal hardware

    Jun 29, 2010

    Resolve
  • Class - 2

    4th fl stwy "g" door locked stwy "c" not closing 3rd fl stwy "c" door not closing 2nd fl stwy "i&h" doors locked remedy: repair / replace doors

    Jun 29, 2010

    Resolve
  • Class - 2

    The electrical room is lacking fire stopping at cellar level. remedy: provide/maintain fire stopping.

    Mar 13, 2009

    Resolve
  • Class - 2

    Reissue: 34646985h classroom doors is missing door closers on the 1st & 2nd flr level. remedy: replace missing door closers.

    Mar 13, 2009

    Resolve
  • Class - 2

    Failure to safeguard all persons & property affected by construction operations. observed workers smoking within construction site in violation of nyc fire code 1404.1. 2) men smoking cigarrete & 1 man a cigar

    Nov 17, 2008 · Penalty $1,200

    Resolve
  • Class - 2

    Failure to provide/post signs at jobsite pursuant to subsection. no contractor's sign posted @ time of inspection. job # 201023123-01-al. remedy: provide contractor's sign

    Nov 17, 2008 · Penalty $400

    Resolve
  • Hazardous

    Exterior facade is porous & allowing rain water into the bldg causing interior damages by exit no# 8 & 9 leading to the rear playgroung on basement level.remedy water-proof exterior wall

    Aug 24, 2007

    Resolve
  • Non-hazardous

    Reissue:failure to maintian defect noted water penetratons at various areas of roofs upper roof & lower effecting interior location:upper roof north side of build lower roof north side above lower north bulkhea

    Jan 6, 2004

    Resolve
  • Hazardous

    Reissue:failure to maintain defect noted plaster building cracking:2 x2 piece of ceiling has collapsed all due to water leak locatons:bulkh ead # 6 * 7 stairwells # 3 & 4 4th flr ent to gym rm 408 bulkhead lowe

    Jan 6, 2004

    Resolve
  • Hazardous

    Reissue:failure to maintain exterior stairs defect noted 10'thick by 40' long blue ston straps are loose & hav shifted causing serve trip hazardous.location south west exit sedge week ave side.remedy:make all

    Jan 6, 2004

    Resolve
  • Non-hazardous

    Failure to maintain: defects noted: water penetrations thru various areas of roofs-causing plaster to buldge cracks & become loose to the point of collapse. locations: bulkhead 6&7, stairwell 3&4, 4th fl.exit t

    May 6, 2003 · Penalty $2,500

    Resolve
  • Hazardous

    Failure to maintain steps: defect noted: slate steps missing mortar & seperating shifting & too much movement causing trip hazards. location: east stairwell- on van court lanch are. remedy: make all necessary r

    May 6, 2003 · Penalty $2,500

    Resolve
  • Hazardous

    Exit door total obstruction noted class room #214 exit door blocked by cabidet remedy remove obstruction

    Feb 14, 2002

    Resolve
  • Non-hazardous

    Exit door required width decreased by obstruction noted at stairwell #3 & 4 2nd and 3rd fl exit door blocked by deskand chairs remedy remove obstruction

    Feb 14, 2002

    Resolve
  • Non-hazardous

    Fialure to maintain defect is roof leaks at various locations rooms # 456 #408 stairwell 3 & 4 and service wing adjacentto 4th fl gym skylight at room # 456 defective remedy repair roof stop leaks / replace def

    Apr 19, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defect is deteriorating flaking spalling plaster room # 456 # 408 service wing 4 th fl stairwell # 3 & 4 ceiling areas remedy maintain bldg repair deteriorating ceiling

    Apr 19, 2001

    Resolve
  • Non-hazardous

    Failure to maintain exterior. defects are: 1) exterior vestibule exitsmasonry mortar is missing. location: playground exits. 2) two horizon-tal steel and concrete supports. from school wall to retaining wall

    Jun 3, 1999

    Resolve

Complaints

  • Heat/hot water

    Entire building

    May 24, 2024 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1932
Floors
4
Residential units
—
Building area
171,920 ft²
Lot area
77,365 ft²
Zoning
R7-1
Community board
208
Council district
11
Block / lot
3252 / 182
Assessed value
$13,303,800
Landmark / historic district
No

Questions about 3961 Hillman Avenue

Who owns 3961 Hillman Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 3961 Hillman Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 3961 Hillman Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 3961 Hillman Avenue built?

City records list 1932 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.