560 East 179 Street
Bronx, NY 10457BBL 2-03061-0055Map
Owner of record: Uptown Storage Co.,inc.
560 East 179 Street is a school building built in 1914 in Bronx, 10457. The owner of record is Uptown Storage Co.,inc.. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 46
- ECB violations
- 67
- HPD complaints
- 2
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 46
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 22, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 22, 2017
Dob violation - resolved
Show 36 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Dec 16, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 16, 2016
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 1, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 1, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 17, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 17, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 14, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 14, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 8, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 8, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 25, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 19, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 30, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 30, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 11, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 11, 2006
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatorrequired
2p110
Feb 26, 2002
Dob violation - resolved - Elevator elevatorrequired
2f18
Feb 26, 2002
Dob violation - resolved - Construction other optional
C-construction other optional
Aug 26, 2001
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Elevator elevatorrequired
2p110
Mar 2, 2001
Dob violation - resolved - Elevator elevatorrequired
2f18
Mar 2, 2001
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 10, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 20, 1994
Vp*-violation unserved ecb- dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Elevator elevatoroptional
2
Apr 25, 1991
Dob violation - dismissed
ECB violations · 67
- Class - 2
Reissue#35721124j failure to maintain building in code-compliant manner.noted:on 2nd floor at exp#1 there is vertical cracks in window,also on 1st flr exp#4 cafeteria has vertical cracks.rem:repair and/or repla
Jul 2, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35721123h failure to maintain building wall(s)or appurtenancesnoted:on the roof level,the chimney has vertical cracks and top layer is broken up.rem:maintain exterior building wall.
Jul 2, 2026 · Penalty $6,250
Active - Class - 2
Reissue#35721122x failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency lights on 3rd flr,2nd and all but 2 light
Jul 2, 2026 · Penalty $3,125
Active - Class - 2
Reissue#3572121y failure to maintain building in code-compliant mannernoted:staircase a 4th flr has cracks on ceiling and walls due to waterpenetrations,3rd flr staircase a also has water damage in ceiling and
Jul 2, 2026 · Penalty $3,125
Active - Class - 2
I found a federal ast2-100 boiler leaking from inside/backflow missing/oil tank room not fire rated/chimney clean out on the floor/correct all violating condition/submit certificate of correction
Aug 21, 2025 · Penalty $1,250
Active - Class - 2
Reissue #35692327j. failure to maintain building in code-compliant manner. noted spalling and cracking plaster on walls and ceilings at stairwell a on 4th, and 3rd fl. also at stairwell b bulkhead level due to
Jul 24, 2025 · Penalty $1,250
Active - Class - 2
Reissue #35692328l. failure to maintain building walls or appurtenances. noted at roof level, chimney has crack at all elevations along the top, with masonry starting is seperate and missing chunk of stone. add
Jul 24, 2025 · Penalty $2,500
Active - Class - 2
Failure to maintain building in code-compliant manner. noted cracked window glass panels at exp #1, 2nd fl.rm #213 and at exp #4, 1st fl. multipurpose cafeteria(3) broken glass panels. remedy: repair and/or rep
Jul 24, 2025 · Penalty $1,250
Active - Class - 2
Reissue #35692326h. failure to maintain building in code-compliant manner. noted broken wire mesh glass in door at room #105. main entrance smoke doors were not properly self-closing when tested. remedy: repair
Jul 24, 2025 · Penalty $1,250
Resolve - Class - 2
Reissue #35692329n. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381/ noted approx. 95% of emergency lights with battery
Jul 24, 2025 · Penalty $1,250
Active
Show 40 more ↓
- Class - 2
Failure to maintain building in code-compliant manner. noted at cellarlevel oil tank room, corroded girder and heavily rusted steel beams with missing fireproofing. numerous cracks in concrete cosing fr horizon
Jul 24, 2025 · Penalty $1,250
Resolve - Class - 1
Failure to maintain building in code-compliant manner. noted automaticfire sprinkler system was inoperative throughout school building. due to penthouse level water storage tank having leak which caused entire
Jul 24, 2025 · Penalty $2,500
Resolve - Class - 2
Exit door not self-closing. noted exterior doors at exit #1 and 2 not opening or closing properly due to defective saddles. remedy: repair and/or replace door.
Jul 24, 2025 · Penalty $625
Resolve - Class - 2
Reissue #35677143j. date of issue: 07/11/2023. failure to maintain building in code-compliant manner. neer cafeteria has a door broken glass(at room-105) repair or replace broken glass. remedy: repair or replac
Oct 21, 2024 · Penalty $1,562
Active - Class - 2
Reissue #35677141x. date of issue: 07/11/2023. failure to maintain building wall(s) or appurtenances. at the time of inspection at exposure 2 west side chimney in center of roof in disrepair at top has cracks.
Oct 21, 2024 · Penalty $3,125
Active - Class - 2
Reissue #35663471l. date of issue: 07/11/2023. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspectio
Oct 21, 2024 · Penalty $1,562
Active - Class - 2
Reissue #35677144l. date of issue: 07/11/2023. failure to maintain building in code-compliant manner at 1st floor main entrance hole in saddle in doorway tripping hazard and 1st floor cafeteria 4 exit doors are
Oct 21, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue #35677142h. date of issue: 07/11/2023. failure to maintain building in code-compliant manner spalling at windows stair "b" at floors2, 3, 4 and skylight leaking, cellar drains puddles and water causing
Oct 21, 2024 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code-compliant manner. spalling at windows stair b at floors 2, 3, 4 and skylight leaking. cellar drains puddles and water causing flooding. remedy: repair and/or replace.
Jul 11, 2023 · Penalty $625
Active - Class - 2
Reissue #356547712. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per 1006.7; 27-381. noted at 1, 2, 3, 4 floors most of the emergency light
Jul 11, 2023 · Penalty $1,562
Active - Class - 2
Reissue #35578258x. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc1006.1; 27-381. noted exit signs 5fl stair b, 4fl stair b, 3fl emerg
Jul 11, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building wall(s) or appurtenances. exposure 2 westside chimney missing brick and mortar parapet cracks, chimney in center of roof in disrepair at top has cracks. remedy: maintain exterior bu
Jul 11, 2023 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. cafeteria has adoor with a broken glass. remedy: repair and/or replace.
Jul 11, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. 1 floor main entrance hole in saddle in door way tripping hazard. remedy: repair and/or replace.
Jul 11, 2023 · Penalty $625
Resolve - Class - 2
Exit door not self-closing. noted at exit doors 1 and 2 doors are rubbing causing it to not work properly. remedy: repair/replace door.
Jul 11, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted 4th floor1500 gallon tank for fire suppression is leaking from piping coming out of tanks. remedy: repair and/or replace.
Jul 11, 2023 · Penalty $625
Resolve - Class - 2
Reissue35578154l lack of emergency lighting for exit,exit discharges&public corridors per bc1006.1;27-542,most emergency lights not working in school.repair &or replace lighting
May 20, 2022 · Penalty $3,125
Resolve - Class - 2
Reissue35473280l failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:thruout bldg,most of emergency lights werent working when test
Jun 1, 2021 · Penalty $1,562
Active - Class - 2
Exit door not self closing.noted 2nd,3rd floor exit door by hallway not self closing.rem:repair or replace.
May 28, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.lack of emergency lighting for exits.exit discharges and public corridors per bc 1006.1 27-542.noted:1st and 2nd floor emergency light at hallway not workin
May 28, 2020 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at 4 floorrm 413,412 along with 179th street water leak,water penetration visible of celling and around windows.rem:repair or replace.
May 28, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bld.in code compliant manner.at 4th fl.rooms 415,402,403 water penetration visible at ceiling from roof above.rem:complywith code.
Jul 9, 2019
Resolve - Class - 2
Reissue viol #35261013m. exit door not self-closing. noted: defectivetop hinge and not self closing door at 3rd floor. rmdy: repair and/or replace door.
Apr 24, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: several water penetration through retaining walls crackes on east and north wall in the cellar level. rmdy: repair and/or replace
Apr 24, 2018
Resolve - Class - 2
Reissue viol #35261012k. failure to maintain building in code-compliant manner. noted: defective emergency lighting observed throughout entire building. rmdy: repair/replace lighting.
Apr 24, 2018
Resolve - Class - 2
Failure to maintain building in code-compliantmanner: lack of emergen cy lighting for exit discharges and public corridors per bc 1006.1; 27542. noted: at 1st flr, multipurpose room and at various places in 1st
Jun 2, 2017
Resolve - Class - 2
Exit door not self-closing. noted: the doors have defetive in the top hinge and not close properly at the following places: at 3rd floor, boy's bathroom, girl's bathroom, exit stair (a, b, and at the 2nd floor
Jun 2, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at water main room,also aka oil tank room at cellar level,vertical cracks at walls. vertical cracks are approx 3'to 6'feet long. cracks are also on foun
Oct 11, 2016
Resolve - Class - 2
Failure to provide power for emergency exit lighting. noted: no power to any emergency exit lights at all stairways & corridors throughout entire school at all stories. remedy: provide adequate power for emerge
Oct 11, 2016
Resolve - Class - 2
Reissue 35018351p defective exit door @ exit 3 along e 179 st.exteriorexit door has loose & corroding frame.rem replace door & frame
Jul 14, 2015
Resolve - Class - 2
Reissue 35101711r failure to maintain bldg in code compliant manner.use of door stops @ rooms 201 through 211,entry doors & smoke corridor doors on 1st fl.rem remove door steps.
Jul 14, 2015
Resolve - Class - 2
Exit door not self closing.re-issue #35101710p following doors are missing door closures:3a,1a,door adjacent to 301.remedy:repair/replace door.
Jul 14, 2015
Resolve - Class - 2
Re-issue # 35018351p. defective exit door. at exit 3 along east 179 street, the exterior exit door has loose & corroding frame. remedy: replace door & frame.
Jun 30, 2014
Resolve - Class - 2
Exit doors not self closing. at 3a,1a, adjacent 301, missing door closers. remedy: replace door closers.
Jun 30, 2014
Resolve - Class - 2
Kick stops installed on exit doors. at 2nd,3rd,4th floors, at various doors throughout. remedy: remove kick stops.
Jun 30, 2014
Resolve - Class - 2
Failure to maintain building noted spalling/loose capping stone (slate) flaking throughout,also corner stone at northwest corner appears to be loose. rmdy: make safe.
May 29, 2013 · Penalty $250
Active - Class - 2
Defective rooms 4fl corridor doors next to 403 (bathroom);3fl corridordoors next to 301,3flr stair (a)1 fc exit 3 frame rotten/loose. rmdy: repair/replace doors/frames.
May 29, 2013
Resolve - Class - 2
Doors not closing. at 3rd story b side corridor door near elevator. rem:repair &/or replace door.
Jul 26, 2012
Resolve - Class - 3
Out of service chimney not capped. at roof chimney not capped. remedy:cap chimney.
Sep 2, 2011
Resolve - Class - 2
Water penetration thru foundation wall. at cellar level east wall below sidewalk water penetrates thru foundation wall at intersection w/footing. remedy: provide/maintain water proof integrity of foundation
Sep 2, 2011
Resolve
Complaints
- Heat/hot water
Entire building
Jan 4, 2016 · Apt 1E
Close - Heating
Heat related
Feb 6, 2011 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1914
- Floors
- 4
- Residential units
- —
- Building area
- 45,000 ft²
- Lot area
- 22,552 ft²
- Zoning
- R7-1
- Community board
- 206
- Council district
- 15
- Block / lot
- 3061 / 55
- Assessed value
- $1,089,000
- Landmark / historic district
- No
Questions about 560 East 179 Street
Who owns 560 East 179 Street?
The owner of record in NYC Department of City Planning PLUTO data is Uptown Storage Co.,inc..
Does 560 East 179 Street have violations?
NYC HPD has no housing violations on record for this property.
Is 560 East 179 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 560 East 179 Street built?
City records list 1914 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.