Owner of record: NYC Department Of Education

743 Fairmount Place is a school building built in 1974 in Bronx, 10457. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
42
ECB violations
76
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 42

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
Show 32 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 9, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 25, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    Nyc department of transportation

    Jun 26, 2014

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 28, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 17, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 15, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 19, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 14, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    2p4887

    Apr 22, 2003

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - active
  • Elevator elevatorrequired

    74 renew main seal on jack

    Sep 28, 1990

    Dob violation - resolved
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - active
  • Elevator elevatoroptional

    Ll10/81-local law 10/81 - elevator elevatoroptional

    Apr 25, 1975

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll10/81-local law 10/81 - elevator elevatoroptional

    —

    Dob violation - dismissed

ECB violations · 76

  • Class - 2

    Re-issue #35721568k. failure to maintain building in code-compliant. no fire-stopping per bc 712.3; 27-345. noted: in electric meter room, fire-stopping was missing around pipes that go thru cmu block in multip

    May 7, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35721567z. failure to maintain building in code-compliant manner. noted: on the roof gravel is in state of disrepair with exposed/missing insulation in various areas. remedy: repair and/or replace.

    May 7, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue 35721564n. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: emergency light not working when tested insi

    May 7, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35721563l. failure to maintain building in code-compliant manner. noted: fpsc doors do not self-close properly at 4th flr-staircase "c", "d". 3rd flr-staircase "a", smoke door #303 and 301. 2nd flr-st

    May 7, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: classroom rm #s-402 and 402c have kick-stops installed on bottom of doors. remedy

    May 7, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self closing exterior doors at exit 5d & 9g not self closing properly when tested.rem:repair/replace doors.

    Aug 1, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at roof level step cracks vertical cracks & deteriorating mortar joints in parapet walls & exterior walls of mechanical rooms and decorally properly c

    Aug 1, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted exp #3 rear yard was heavily overgrown by tree, weeds and bushes, protruding post the property fence onto public sidewalk. remedy: repair/replace/mai

    Aug 1, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. exp #3 rear 7' retaining wall was leaning approx. 6 inches with failed expansion joints and pulling away from building facade by exit door. remedy: repair

    Aug 1, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted illegal kickdown door stops or classroom doors #203a, 203b, 203c, 203d and 2nd fl

    Aug 1, 2025 · Penalty $1,250

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code compliant manner.interior fpsc doors not closing properly at:4th fl stair c,d & 401.3rd fl stair a & 301 2nd fl stair c & d 201,203,202 & corridor smoke by 210 1st fl stair

    Aug 1, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.emergency lights not working when tested at:2nd fl gym 4 by stair e 1st fl c

    Aug 1, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted gravel roof in state of disrepair with exposed/missing areas of installation. vegitation growing throughout roof surface and inside roof drains. reme

    Aug 1, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: no firestoppingper bc 712.3; 27-345. at electric meter room an approx. 8"x16" hole incmu wall. no fire stopping provided. remedy: provide/maintain fire sto

    Aug 1, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain bldg in codecompliant manner:provide required corridor width per bc1016.2;27-369.noted:observed@cellar level-aprx50% of common corridor obstructed by school furniture eg desks,chairs shelves

    May 23, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner no firestopping per bc712.3;27-345.noted:observed in gas meter rm 16"x8" opening in cmu block wall w/pipe penetrating into adj area&valve in middle of opening co

    May 23, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006-1;27-381.noted:observed existing emergency lights w/battery backup power labeled 3d,3e,3c,2e,2

    May 23, 2022 · Penalty $625

    Resolve
  • Class - 1

    Class 1 violation issued no dlm installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc remedy; file application install dlm, class 2 violation issued, in car nyc# device tag number

    Mar 15, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue ecb#35423138p issued 06-24-2019 ecb#35329547 issued 04-27-2018exit door not self closing noted;exit door not self closing room 413 on 3rd floor exit 2 & 4,room 301, 2nd floor and 1st floor.door on 4th f

    May 28, 2020 · Penalty $1,562

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor

    Feb 27, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue #3532954n failure to maintain building in code compliant manner various doors throughout 1,2,3,4 have broken closeres + hangers on classroom exit & corridor doors repair & or replace

    Jun 24, 2019

    Resolve
  • Class - 2

    Exit door not sel fclosing room 413 on 3rd floor exit 2,4 rm 301 , 2nd floor exit 2& 1st floor repair & or replace

    Jun 24, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.note:@ kitchen storage room windows with shelves and storage goods.remedy:repair or removeobstruction.

    Apr 27, 2018

    Resolve
  • Class - 2

    Reissued 35270880p.failure to maintain bldg in code compliant manner.nnote:@2nd fl girls student bathroom across from gym stalls broken(1st stall walls beat,3rd stall door bent and cannot lock 4th stall door ha

    Apr 27, 2018

    Resolve
  • Class - 2

    Reissued 35270879h.failure to maintain bldg walls & appurtenances:notebroken windows @main entrance exit #2,2nd floor and exit 6&7 between 2nd and 3rd floor.rem:maintain exterior bldg walls

    Apr 27, 2018

    Resolve
  • Class - 2

    Reissue 35270877y failure to maintain bldg in code compliant manner.lack of emergency lighting for exit discharges & public corridors per bc1006.1.note:@ various locations on all floors emergency lights not wor

    Apr 27, 2018

    Resolve
  • Class - 2

    Reissue 35270878x failure to maintain bldg in code compliant manner. note:various doors throughout 1,2,3 & 4 floors have broken closures & hinges on classroom,exit and corridor doors.rem:repair &/or replace

    Apr 27, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.note:@ roof level roof level roof leaks in various ara causing water damage to ceilings below.rem:repair and/or replace.

    Apr 27, 2018

    Resolve
  • Class - 2

    28-301.1 failure to provide natural or mechanical ventilation to occupied spaces per mc401.2.note:@ basement level storage of gas machines &gas can.remedy:comply w/notice of violation and remove machine & gas c

    Apr 27, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.use of prohibited door &/or hardware per bc1008.1.8.note:in corridors on all floors corridor door have (icey)locks.rem:provide legal hardware.

    Apr 27, 2018

    Resolve
  • Class - 2

    Exit door not self-closing:note on various floors.exit doors to stairways not closing (door on 4th fl exit 2,7,5)corridor door 401 both sides 403 & room 413 on 3rd fl exit 2&7 room 301 & 2nd fl exit 2 & 1st fl

    Apr 27, 2018

    Resolve
  • Class - 2

    Reissue#35213760j.failure to maintain bldg in code compliant manner.lack of emergency lighting for exits &exit discharges and public corridors per bc 1006 lack of emergency lights and exit discharge throughout

    Jun 14, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.various doors through9out 1,2,3,4 floors broken hinges and closers exit classroom,and corridors not working.rem:repair/replace

    Jun 14, 2017

    Resolve
  • Class - 2

    Failure to maintain building walls and appurtenances window broken at main entrance exit 2 and 2 and exit 6 and 7 between 2nd and 3rd floor landing. rmdy: maintain exterior building walls.

    Jun 14, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner: at 2nd floor girls student bathroom across from gym rear stalls busted not working. rmdy: repair or replace.

    Jun 14, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s)or appurtences.noted:@exp#1 on both sides of main entrance, retaining walls cracked and crumbling.(concrete retaining walls).rem:maintain ext5erior noted.

    Sep 27, 2016

    Resolve
  • Class - 2

    Failure to maintain in code-compliant manner:lack of emergency lighting for exits,exit discharges and public corridors per bc1006.1;27-542 re-issue nov #35128143h issued on 4/14/15 for lack of emergency lightin

    Sep 27, 2016

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. water penetrat ing roof. at 4th story public corridors of complex 401 and complex 403(adjoining rooms 401c and 403b respectively).rmdy: repair defect noted

    Oct 23, 2015

    Resolve
  • Class - 2

    Reissue #35101611j on 6/23/14 failure to maintain bldg in code compliant manner: lack of emergency lighting for exits,exit discharges & public corridors per bc 1006.1;27-542. note: defective emergency lights

    Apr 14, 2015

    Resolve
  • Class - 2

    Reissue 35101615r on 6/23/14 failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3'27-345. note: missing fire stopping at gas meter room & electric meter room. no fire stopping w/pipe

    Apr 14, 2015

    Resolve
  • Class - 2

    Reissue: 35101613n 6/23/14 failure to maintain bldg in code compliant manner. note: combustible hanging banners. numerous banners hanging from conduits throughout 1st fl of school. remedy: comply w/notice of

    Apr 14, 2015

    Resolve
  • Class - 2

    Defective emergency lights. at 2nd floor divided gym-c.s.211 side inoperative emergency lighting with battery back up. remedy: repair or replace emergency lighting.

    Jun 23, 2014

    Resolve
  • Class - 2

    Combustible hanging banners. numerous banners hanging from conduits. remedy: remove banners from conduits.

    Jun 23, 2014

    Resolve
  • Class - 2

    Partial obstruction. at 203 complex, corridor width reduced by bicycles, chairs & carts. remedy: remove all items, maintain corridor width clear.

    Jun 23, 2014

    Resolve
  • Class - 2

    No place of assembly plans available. 2nd floor gym/sports areas under pa # 200545909 is divided & sealed shut with one means of egress on each side, with occupancy for 371 persons. remedy: provide approved p

    Jun 23, 2014

    Resolve
  • Class - 2

    Missing fire stopping. at gas meter room & electric meter room, no fire stopping with pipe penetrations in cmu block walls. remedy: provide/maintain fire stopping.

    Jun 23, 2014

    Resolve
  • Class - 2

    Combustible artwork in fire stairs. at stair "d" 2nd,3rd & 4th floors, large combustible artwork & decorations at floor landings creating a fire condition safety issue. remedy: remove all combustible items.

    Jun 23, 2014

    Resolve
  • Class - 2

    Exit doors not self closing. at 4c bulkhead, adjacent 410,301,2e, gym # 232, broken door closers. remedy: replace door closers.

    Jun 23, 2014

    Resolve
  • Class - 2

    Exit passageway obstructed at 1 floor front of exit 7 large l shape wooden desk in place directly front of doors also 4 floor approx 4 deck in corridor. remedy: remove desk.

    May 22, 2013

    Resolve
  • Class - 2

    Doors not closing at 4th story cross corridor doors #403 & #402 at 3rdstory cross corridor doors #301 & stair e. remedy: repair &/or replacedoors noted.

    Jul 6, 2012

    Resolve

Complaints

  • Electric

    Wiring

    Aug 4, 2016 · Apt 2D

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1974
Floors
4
Residential units
—
Building area
170,000 ft²
Lot area
62,100 ft²
Zoning
R7-1
Community board
206
Council district
15
Block / lot
2951 / 32
Assessed value
$18,723,600
Landmark / historic district
No

Questions about 743 Fairmount Place

Who owns 743 Fairmount Place?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 743 Fairmount Place have violations?

NYC HPD has no housing violations on record for this property.

Is 743 Fairmount Place rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 743 Fairmount Place built?

City records list 1974 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.