3674 3 Avenue
Bronx, NY 10456BBL 2-02925-0029Map
Owner of record: Thirdview LLC
3674 3 Avenue is a hospital / health built in 1920 in Bronx, 10456. The owner of record is Thirdview LLC. HPD has recorded 6 housing violations here, most recently on July 1, 2022. 2 of the 6 most recent violations are still open.
- HPD violations
- 6
- DOB violations
- 32
- ECB violations
- 49
- HPD complaints
- 27
What to know
Immediately hazardous issues among recent violations are still open.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 6
- CImmediately hazardous
Abate the infestation consisting of mice in the entire apartment located at apt 5c, 5th story, 2nd apartment from east at south
Jul 1, 2022 · Apt 5C
Open — Notice of issuance sent to tenant - CImmediately hazardous
Abate the infestation consisting of roaches in the entire apartment located at apt 5c, 5th story, 2nd apartment from east at south
Jul 1, 2022 · Apt 5C
Open — Notice of issuance sent to tenant - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Feb 18, 2022
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 5, 2021
Closed — Violation dismissed - CImmediately hazardous
Provide hot water at all hot water fixtures in the entire apartment located at apt 5a, 5th story, 1st apartment from west at north
Jan 12, 2017 · Apt 5A
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures in the 1st room from east located at apt 4r, 4th story
Feb 14, 2016 · Apt 4R
Closed — Violation closed
DOB building violations · 32
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Feb 7, 2024
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 4, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - active
Show 22 more ↓
- Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jul 21, 2021
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 24, 2021
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Sep 2, 2020
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 27, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 10, 2018
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 19, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 10, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 16, 2012
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 25, 2012
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 9, 2011
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Elevator elevatoroptional
2
Oct 12, 1989
Dob violation - dismissed - Elevator elevatorrequired
(51) remove water from pit
Jan 27, 1989
Dob violation - resolved - Elevator elevatorrequired
11,12 when stop switch engaged alarm must ring
Jan 27, 1989
Dob violation - resolved
ECB violations · 49
- Class - 1
Class 1 rts - immediately hazardous condition: during inspection from top of car with inspection mode engaged, stop switch activated and reset, car unexpectedly accelerated at high speed. condition indicates fa
Apr 29, 2026 · Penalty $1,250
Resolve - Class - 2
Found a laars pwo400 hlw boiler for heat install in 2011 not register/register boiler and submit a certificate of correction
Apr 29, 2026
Resolve - Class - 2
Found a laars pwo400 hlw boiler for heat install in 2011 not register/register boiler and submit a certificate of correction
Apr 29, 2026
Resolve - Class - 1
Failure to maintain building in code-compliant manner. at time of inspection, observed multiple opening cut through office partitions leading to the hallway. these openings are fitted with ventilation covers; h
Dec 9, 2025 · Penalty $6,250
Active - Class - 2
Failure to maintain building in a code-compliant manner. at time of inspection, observed the playground at the rear yard obstructed by a playground bench, restricting required egress with this condition present
Dec 9, 2025
Resolve - Class - 2
Failure to maintain building in a code-compliant manner. at time of inspection, observed the play ground at the rear yard obstructed by a play ground bench, restricting required egress width. the condition pres
Dec 9, 2025 · Penalty $3,125
Active - Class - 1
Failure to maintain building in code-compliant manner. at time of inspection observed multiple opening cut through office partitions leadingto hallway. these openings are fitted with ventilation covers; however
Dec 9, 2025
Resolve - Class - 1
Failure to provide unobstructed exit passageway. obstructed playground passageway obstructed by playground bench. located at rear yard. potential hazard., remove obstruction
May 6, 2025 · Penalty $1,250
Active - Class - 1
Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed office rooms in basement for holes in them. holes are covered with vent
May 6, 2025 · Penalty $2,500
Active - Class - 2
Class 2 items: in-car communication inoperative. repair oil leak and clean hoist machine. replace car door retainers and close gap. provide an updated maintenance log. provide a maintenance program. repair hall
May 5, 2025 · Penalty $625
Active
Show 39 more ↓
- Class - 2
Failure to comply with commissioner's order contained in summons #39093297z issued on 08/24/2023, and failure to file a certificate of correction pursuant to 28.201.1 and 1 rcny 102-01(d)(2). an acceptable cert
Jan 29, 2025 · Penalty $1,250
Active - Class - 2
Failure to comply with commissioner's order contained in summons #39081988j issued on 03/22/2023, and failure to file a certificate of correction pursuant to 28.201.1 and 1 rcny 102-01(d)(2). an acceptable cert
Jan 29, 2025 · Penalty $1,250
Active - Class - 1
Unlawful acts: failure to comply with commissioner's orders stated in ecb# 39093367p issued on 08/24/2023. pursuant to 28-201.1 and 1rcny 102-01., comply with commissioner's order; submit a certificate of corre
Dec 28, 2023 · Penalty $6,250
Resolve - Class - 2
I observed on the 2nd floor roof 5 condenser units disconnect switches with the grounding conductor improperly terminated. there is no attachment to the body of the switch., provide adequate grounding; properly
Aug 24, 2023 · Penalty $1,200
Resolve - Class - 2
I observed the violating conditions as stated in ecb 39082123p still in effect no cert. of correction was issued no the violating conditions corrected by the commissioner's orders., file a certificate of correc
Aug 24, 2023
Resolve - Class - 1
I observed in the electrical closets on all floors the data equipment as stated in the previous ecb 39082123p issued on 03/23/2023. the violating conditions remain in effect. photos taken., comply with ec; remo
Aug 24, 2023
Resolve - Class - 2
Structural vertical cracks found in the sidewalk compartment and walls located in the boiler room, cellar level., repair and/or replace
Aug 24, 2023 · Penalty $312
Resolve - Class - 2
Observed door in the gas meter room not self closing. door sweep installed on the door to the gas meter room is prohibiting it from closing. 102.3 maintenance. installations, both existing and new, and parts th
Aug 24, 2023 · Penalty $625
Resolve - Class - 2
-hole penetration in the walls and ceilings throughout the building., repair and/or replace
Aug 24, 2023 · Penalty $625
Resolve - Class - 2
-exsecessive storage underneath the stair located at staircase (a), repair and/or replace
Aug 24, 2023 · Penalty $312
Resolve - Class - 3
Found rating plate unreadable on boiler , need to replace it .
Aug 24, 2023 · Penalty $250
Active - Class - 2
I observed at the front exterior of the building the use of emt conduits to supply power to the exterior lights. as per the electrical code emt conduits are not permitted to be used outdoors in damp/ wet locati
Mar 23, 2023
Resolve - Class - 1
I observed on all floors the installation of conduits data wiring and termination boxes for the building wifi system. the electrical closet is dedicated toi electrical distribution equipment only. the installat
Mar 23, 2023
Resolve - Class - 2
I observed in the common hallways on all floors the failure to maintain tamper resistant/proof receptacles as required per 2015 ll 39.; ll-39, comply with code
Mar 23, 2023
Resolve - Class - 2
Two laars mt boilers not operating for heat-corrosion on domestic hw piping over storage tanks-heat stress on insulated covering of boiler no. 4 and metal temp. unusually high.
Mar 22, 2023 · Penalty $625
Active - Class - 2
Failure to comply with the commissioner's order contained in summons/violation#35635626z issued on 11/15/2021 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01.filed certificate of c
Mar 9, 2022
Resolve - Class - 2
I observed in dob records the accepted cure for ecb 36635625r. at the time of my inspection the violating conditions remained the exact same as stated on 11/15/2021. (photos taken), file a certificate of correc
Feb 24, 2022
Resolve - Class - 2
I observed on the exterior of the building the unpermitted use of electrical metallic tubing to supply power for wall lights. emt is not permitted for use in outside locations., comply with ec code; provide pro
Feb 24, 2022
Resolve - Class - 2
Failure to protect conductors against overcurrent as per ec.observed in rooftop elevator motor room conductors in elevator disconnect switch imporpely fused the wad side conductors are a #4 awg and are fused at
Nov 15, 2021
Resolve - Class - 2
Failure to comply with commissioner's order to file certificate of correction with dept of buildings.a proper certificate of correction is required for ecb #35294526z issued 16/13/2017.violating conditions of u
Nov 15, 2021
Resolve - Class - 2
Unpermitted use of electrical metal tubing.observed on exterior of building the use of emt raceway to supply power for wall lights.please note use of emt outside is not permitted.remedy:comply with code use pro
Nov 15, 2021
Resolve - Class - 1
Filed certificate of correction or other related materials containing material false statements.observed in dept of buildings record c of c submitted for ecb #35294526z in which respondent stated violating cond
Nov 15, 2021
Resolve - Class - 1
No door lock monitoring installed in this controller as per 3.10.12 of appendix k3 of the 2014 nycbc. remedy; install dlm and perform and file test with nycdob.
Apr 26, 2021 · Penalty $3,125
Resolve - Class - 2
As per one welded, ao smith heat exchanger/storage tank; pressure relief valve not installed; correct all violating conditions, submit a certificate of correction.
Dec 23, 2020 · Penalty $310
Resolve - Class - 1
42m5-no door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc.this is a controller feature which ensures passenger safety.rem:file application.install dlm&per
Jan 6, 2020 · Penalty $1,250
Resolve - Class - 2
Sprinkler head installed to deep into the ceiling., repair and/or replace
Oct 24, 2019
Resolve - Class - 2
56.y.13,05.i.10,16.h.11,26.d.06,52.u.07,53.u.07,39.o.02,59.b.07,68.m.07,40.o.02=(56) seal machine (05) repair gate dw greenfield (16) replace worn door release roller greenfield (16) replace worn door release
Apr 3, 2019
Resolve - Class - 2
Ec430.75.motor disconnect switch has not been provided.observed on roof motor disconnect for exhaust fan has not been provided/installed with six feet of equipment.rem:comply with ec code
Nov 9, 2018 · Penalty $620
Resolve - Class - 1
Unlawful acts. failure to comply w/an order of the commissioner. in 10-13-17;1-22-18. 2 violations was issue to the respondent failed to comply w/nyc electrical code #250.4;28-201.1 ecb's#35294523r;35312637h.
May 2, 2018 · Penalty $2,530
Resolve - Class - 1
An unlawful act. failure to comply w/an order of the commissioner. failure to correct & certify summons#35294525r issued on 10-13-17 for failure to ground the electrical system in the water meter room in the
Jan 22, 2018 · Penalty $800
Resolve - Class - 1
Failure to ground electrical systems observed in water meter room located in the bsmt:main grounding conductor for bldg electrical systems disconnected from water main pipe;floating ground.please know that fail
Oct 13, 2017 · Penalty $4,800
Resolve - Class - 2
Unapproved unsafe unsuitable electrical equipment appartus devices materials appliances or wiring in use.observed above main entrance:unsuitable use of materials to provide power to wall pack light fixtures.
Oct 13, 2017 · Penalty $400
Resolve - Class - 2
Fgc408.2/miscellaneous violations.drips-future connects exist down stream of appliance.observed on 11/7/16 in boiler room future gas connection on elbows that are plugged.rem:comply with notice of violation
Nov 7, 2016 · Penalty $800
Resolve - Class - 1
Cease use. /01/l/10/. repair emergency stop switch in car.
Nov 1, 2011 · Penalty $1,000
Resolve - Class - 2
98bb5
Oct 20, 2009
Resolve - Hazardous
Supervision or use of rigging equipment w/o a special rigger license.refer to swo #15960
Nov 3, 2006 · Penalty $500
Resolve - Hazardous
Work contrary to approved dob plans & application.material hoist not show on drawing.refer to swo #15960
Nov 3, 2006 · Penalty $500
Resolve - Hazardous
Sidewalk shed does not meet building code srecifications 1, no lights 2, side toward building not sealed missing two sheet of plywood 3, bebri left on shed. remedy: conform shed to building code srclifications
Oct 4, 2002
Resolve - Non-hazardous
Work without a permit. work noted: having installed a side walk shed without a permit. remedy: obtain a permit.
Oct 4, 2002
Resolve
Complaints
- Heat/hot water
Entire building
Jun 8, 2026 · Apt 5C
Close - Heat/hot water
Entire building
May 21, 2026 · Apt 5Q
Close - Heat/hot water
Entire building
Jan 15, 2025 · Apt 1J
Close - Heat/hot water
Entire building
Oct 5, 2022 · Apt BLDG
Close - Unsanitary condition
Pests
Jun 28, 2022 · Apt 5C
Close - Unsanitary condition
Pests
Jun 28, 2022 · Apt 5C
Close - Heat/hot water
Entire building
Jun 30, 2021 · Apt 1F
Close - Heat/hot water
Apartment only
Oct 27, 2020 · Apt 2H
Close - Heat/hot water
Entire building
Feb 15, 2020 · Apt 1H
Close - Heat/hot water
Entire building
Oct 20, 2019 · Apt 2R
Close
Show 17 more ↓
- Heat/hot water
Apartment only
Mar 19, 2018 · Apt 3M
Close - Heat/hot water
Entire building
Mar 12, 2018 · Apt 1
Close - Heat/hot water
Entire building
Jan 2, 2018 · Apt 5G
Close - Heat/hot water
Apartment only
Dec 28, 2017 · Apt 1E
Close - Heat/hot water
Entire building
Nov 28, 2017 · Apt 5A
Close - Heat/hot water
Entire building
Jan 9, 2017 · Apt 5A
Close - Heat/hot water
Apartment only
Feb 15, 2016 · Apt 5S
Close - Heat/hot water
Apartment only
Oct 5, 2015 · Apt 3K
Close - Heat/hot water
Entire building
Feb 15, 2015 · Apt 1K
Close - Heat/hot water
Entire building
Feb 5, 2015 · Apt BLDG
Close - Plumbing
Water supply
May 30, 2013 · Apt BLDG
Close - Heating
Heat related
Oct 5, 2011 · Apt 2G
Close - Heating
Heat related
Nov 28, 2010 · Apt 3A
Close - Appliance
Electric/gas range
Feb 26, 2010 · Apt 2E
Close - Heating
Heat related
Feb 19, 2010 · Apt NA
Close - Heating
Heat related
Jan 20, 2009 · Apt 3R
Close - Nonconst
Vermin
Jul 25, 2007 · Apt 3Q
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Hospital / health (I1)
- Year built
- 1920
- Floors
- 5
- Residential units
- —
- Building area
- 39,900 ft²
- Lot area
- 20,963 ft²
- Zoning
- R7-1
- Community board
- 203
- Council district
- 16
- Block / lot
- 2925 / 29
- Assessed value
- $2,359,800
- Landmark / historic district
- No
HPD registration #227288, last renewed Jul 24, 2025.
Questions about 3674 3 Avenue
Who owns 3674 3 Avenue?
The owner of record in NYC Department of City Planning PLUTO data is Thirdview LLC.
Does 3674 3 Avenue have violations?
Yes. NYC HPD has recorded 6 housing violations at this property.
Is 3674 3 Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 3674 3 Avenue built?
City records list 1920 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.