roofy

3674 3 Avenue

Bronx, NY 10456BBL 2-02925-0029Map

Owner of record: Thirdview LLC

3674 3 Avenue is a hospital / health built in 1920 in Bronx, 10456. The owner of record is Thirdview LLC. HPD has recorded 6 housing violations here, most recently on July 1, 2022. 2 of the 6 most recent violations are still open.

HPD violations
6
DOB violations
32
ECB violations
49
HPD complaints
27

What to know

Concern
2 open Class C

Immediately hazardous issues among recent violations are still open.

Good
Last violation Jul 1, 2022

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 6

  • C

    Abate the infestation consisting of mice in the entire apartment located at apt 5c, 5th story, 2nd apartment from east at south

    Jul 1, 2022 · Apt 5C

    Open — Notice of issuance sent to tenant
  • C

    Abate the infestation consisting of roaches in the entire apartment located at apt 5c, 5th story, 2nd apartment from east at south

    Jul 1, 2022 · Apt 5C

    Open — Notice of issuance sent to tenant
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Feb 18, 2022

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 5, 2021

    Closed — Violation dismissed
  • C

    Provide hot water at all hot water fixtures in the entire apartment located at apt 5a, 5th story, 1st apartment from west at north

    Jan 12, 2017 · Apt 5A

    Closed — Violation closed
  • C

    Provide hot water at all hot water fixtures in the 1st room from east located at apt 4r, 4th story

    Feb 14, 2016 · Apt 4R

    Closed — Violation closed

DOB building violations · 32

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Feb 7, 2024

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 4, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
Show 22 more ↓
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jul 21, 2021

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 24, 2021

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 2, 2020

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 27, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 10, 2018

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2016 inspection/test

    Sep 15, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 19, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 10, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 16, 2012

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 25, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 9, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Elevator elevatoroptional

    2

    Oct 12, 1989

    Dob violation - dismissed
  • Elevator elevatorrequired

    (51) remove water from pit

    Jan 27, 1989

    Dob violation - resolved
  • Elevator elevatorrequired

    11,12 when stop switch engaged alarm must ring

    Jan 27, 1989

    Dob violation - resolved

ECB violations · 49

  • Class - 1

    Class 1 rts - immediately hazardous condition: during inspection from top of car with inspection mode engaged, stop switch activated and reset, car unexpectedly accelerated at high speed. condition indicates fa

    Apr 29, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Found a laars pwo400 hlw boiler for heat install in 2011 not register/register boiler and submit a certificate of correction

    Apr 29, 2026

    Resolve
  • Class - 2

    Found a laars pwo400 hlw boiler for heat install in 2011 not register/register boiler and submit a certificate of correction

    Apr 29, 2026

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner. at time of inspection, observed multiple opening cut through office partitions leading to the hallway. these openings are fitted with ventilation covers; h

    Dec 9, 2025 · Penalty $6,250

    Active
  • Class - 2

    Failure to maintain building in a code-compliant manner. at time of inspection, observed the playground at the rear yard obstructed by a playground bench, restricting required egress with this condition present

    Dec 9, 2025

    Resolve
  • Class - 2

    Failure to maintain building in a code-compliant manner. at time of inspection, observed the play ground at the rear yard obstructed by a play ground bench, restricting required egress width. the condition pres

    Dec 9, 2025 · Penalty $3,125

    Active
  • Class - 1

    Failure to maintain building in code-compliant manner. at time of inspection observed multiple opening cut through office partitions leadingto hallway. these openings are fitted with ventilation covers; however

    Dec 9, 2025

    Resolve
  • Class - 1

    Failure to provide unobstructed exit passageway. obstructed playground passageway obstructed by playground bench. located at rear yard. potential hazard., remove obstruction

    May 6, 2025 · Penalty $1,250

    Active
  • Class - 1

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed office rooms in basement for holes in them. holes are covered with vent

    May 6, 2025 · Penalty $2,500

    Active
  • Class - 2

    Class 2 items: in-car communication inoperative. repair oil leak and clean hoist machine. replace car door retainers and close gap. provide an updated maintenance log. provide a maintenance program. repair hall

    May 5, 2025 · Penalty $625

    Active
Show 39 more ↓
  • Class - 2

    Failure to comply with commissioner's order contained in summons #39093297z issued on 08/24/2023, and failure to file a certificate of correction pursuant to 28.201.1 and 1 rcny 102-01(d)(2). an acceptable cert

    Jan 29, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to comply with commissioner's order contained in summons #39081988j issued on 03/22/2023, and failure to file a certificate of correction pursuant to 28.201.1 and 1 rcny 102-01(d)(2). an acceptable cert

    Jan 29, 2025 · Penalty $1,250

    Active
  • Class - 1

    Unlawful acts: failure to comply with commissioner's orders stated in ecb# 39093367p issued on 08/24/2023. pursuant to 28-201.1 and 1rcny 102-01., comply with commissioner's order; submit a certificate of corre

    Dec 28, 2023 · Penalty $6,250

    Resolve
  • Class - 2

    I observed on the 2nd floor roof 5 condenser units disconnect switches with the grounding conductor improperly terminated. there is no attachment to the body of the switch., provide adequate grounding; properly

    Aug 24, 2023 · Penalty $1,200

    Resolve
  • Class - 2

    I observed the violating conditions as stated in ecb 39082123p still in effect no cert. of correction was issued no the violating conditions corrected by the commissioner's orders., file a certificate of correc

    Aug 24, 2023

    Resolve
  • Class - 1

    I observed in the electrical closets on all floors the data equipment as stated in the previous ecb 39082123p issued on 03/23/2023. the violating conditions remain in effect. photos taken., comply with ec; remo

    Aug 24, 2023

    Resolve
  • Class - 2

    Structural vertical cracks found in the sidewalk compartment and walls located in the boiler room, cellar level., repair and/or replace

    Aug 24, 2023 · Penalty $312

    Resolve
  • Class - 2

    Observed door in the gas meter room not self closing. door sweep installed on the door to the gas meter room is prohibiting it from closing. 102.3 maintenance. installations, both existing and new, and parts th

    Aug 24, 2023 · Penalty $625

    Resolve
  • Class - 2

    -hole penetration in the walls and ceilings throughout the building., repair and/or replace

    Aug 24, 2023 · Penalty $625

    Resolve
  • Class - 2

    -exsecessive storage underneath the stair located at staircase (a), repair and/or replace

    Aug 24, 2023 · Penalty $312

    Resolve
  • Class - 3

    Found rating plate unreadable on boiler , need to replace it .

    Aug 24, 2023 · Penalty $250

    Active
  • Class - 2

    I observed at the front exterior of the building the use of emt conduits to supply power to the exterior lights. as per the electrical code emt conduits are not permitted to be used outdoors in damp/ wet locati

    Mar 23, 2023

    Resolve
  • Class - 1

    I observed on all floors the installation of conduits data wiring and termination boxes for the building wifi system. the electrical closet is dedicated toi electrical distribution equipment only. the installat

    Mar 23, 2023

    Resolve
  • Class - 2

    I observed in the common hallways on all floors the failure to maintain tamper resistant/proof receptacles as required per 2015 ll 39.; ll-39, comply with code

    Mar 23, 2023

    Resolve
  • Class - 2

    Two laars mt boilers not operating for heat-corrosion on domestic hw piping over storage tanks-heat stress on insulated covering of boiler no. 4 and metal temp. unusually high.

    Mar 22, 2023 · Penalty $625

    Active
  • Class - 2

    Failure to comply with the commissioner's order contained in summons/violation#35635626z issued on 11/15/2021 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01.filed certificate of c

    Mar 9, 2022

    Resolve
  • Class - 2

    I observed in dob records the accepted cure for ecb 36635625r. at the time of my inspection the violating conditions remained the exact same as stated on 11/15/2021. (photos taken), file a certificate of correc

    Feb 24, 2022

    Resolve
  • Class - 2

    I observed on the exterior of the building the unpermitted use of electrical metallic tubing to supply power for wall lights. emt is not permitted for use in outside locations., comply with ec code; provide pro

    Feb 24, 2022

    Resolve
  • Class - 2

    Failure to protect conductors against overcurrent as per ec.observed in rooftop elevator motor room conductors in elevator disconnect switch imporpely fused the wad side conductors are a #4 awg and are fused at

    Nov 15, 2021

    Resolve
  • Class - 2

    Failure to comply with commissioner's order to file certificate of correction with dept of buildings.a proper certificate of correction is required for ecb #35294526z issued 16/13/2017.violating conditions of u

    Nov 15, 2021

    Resolve
  • Class - 2

    Unpermitted use of electrical metal tubing.observed on exterior of building the use of emt raceway to supply power for wall lights.please note use of emt outside is not permitted.remedy:comply with code use pro

    Nov 15, 2021

    Resolve
  • Class - 1

    Filed certificate of correction or other related materials containing material false statements.observed in dept of buildings record c of c submitted for ecb #35294526z in which respondent stated violating cond

    Nov 15, 2021

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as per 3.10.12 of appendix k3 of the 2014 nycbc. remedy; install dlm and perform and file test with nycdob.

    Apr 26, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    As per one welded, ao smith heat exchanger/storage tank; pressure relief valve not installed; correct all violating conditions, submit a certificate of correction.

    Dec 23, 2020 · Penalty $310

    Resolve
  • Class - 1

    42m5-no door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc.this is a controller feature which ensures passenger safety.rem:file application.install dlm&per

    Jan 6, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Sprinkler head installed to deep into the ceiling., repair and/or replace

    Oct 24, 2019

    Resolve
  • Class - 2

    56.y.13,05.i.10,16.h.11,26.d.06,52.u.07,53.u.07,39.o.02,59.b.07,68.m.07,40.o.02=(56) seal machine (05) repair gate dw greenfield (16) replace worn door release roller greenfield (16) replace worn door release

    Apr 3, 2019

    Resolve
  • Class - 2

    Ec430.75.motor disconnect switch has not been provided.observed on roof motor disconnect for exhaust fan has not been provided/installed with six feet of equipment.rem:comply with ec code

    Nov 9, 2018 · Penalty $620

    Resolve
  • Class - 1

    Unlawful acts. failure to comply w/an order of the commissioner. in 10-13-17;1-22-18. 2 violations was issue to the respondent failed to comply w/nyc electrical code #250.4;28-201.1 ecb's#35294523r;35312637h.

    May 2, 2018 · Penalty $2,530

    Resolve
  • Class - 1

    An unlawful act. failure to comply w/an order of the commissioner. failure to correct & certify summons#35294525r issued on 10-13-17 for failure to ground the electrical system in the water meter room in the

    Jan 22, 2018 · Penalty $800

    Resolve
  • Class - 1

    Failure to ground electrical systems observed in water meter room located in the bsmt:main grounding conductor for bldg electrical systems disconnected from water main pipe;floating ground.please know that fail

    Oct 13, 2017 · Penalty $4,800

    Resolve
  • Class - 2

    Unapproved unsafe unsuitable electrical equipment appartus devices materials appliances or wiring in use.observed above main entrance:unsuitable use of materials to provide power to wall pack light fixtures.

    Oct 13, 2017 · Penalty $400

    Resolve
  • Class - 2

    Fgc408.2/miscellaneous violations.drips-future connects exist down stream of appliance.observed on 11/7/16 in boiler room future gas connection on elbows that are plugged.rem:comply with notice of violation

    Nov 7, 2016 · Penalty $800

    Resolve
  • Class - 1

    Cease use. /01/l/10/. repair emergency stop switch in car.

    Nov 1, 2011 · Penalty $1,000

    Resolve
  • Class - 2

    98bb5

    Oct 20, 2009

    Resolve
  • Hazardous

    Supervision or use of rigging equipment w/o a special rigger license.refer to swo #15960

    Nov 3, 2006 · Penalty $500

    Resolve
  • Hazardous

    Work contrary to approved dob plans & application.material hoist not show on drawing.refer to swo #15960

    Nov 3, 2006 · Penalty $500

    Resolve
  • Hazardous

    Sidewalk shed does not meet building code srecifications 1, no lights 2, side toward building not sealed missing two sheet of plywood 3, bebri left on shed. remedy: conform shed to building code srclifications

    Oct 4, 2002

    Resolve
  • Non-hazardous

    Work without a permit. work noted: having installed a side walk shed without a permit. remedy: obtain a permit.

    Oct 4, 2002

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Jun 8, 2026 · Apt 5C

    Close
  • Heat/hot water

    Entire building

    May 21, 2026 · Apt 5Q

    Close
  • Heat/hot water

    Entire building

    Jan 15, 2025 · Apt 1J

    Close
  • Heat/hot water

    Entire building

    Oct 5, 2022 · Apt BLDG

    Close
  • Unsanitary condition

    Pests

    Jun 28, 2022 · Apt 5C

    Close
  • Unsanitary condition

    Pests

    Jun 28, 2022 · Apt 5C

    Close
  • Heat/hot water

    Entire building

    Jun 30, 2021 · Apt 1F

    Close
  • Heat/hot water

    Apartment only

    Oct 27, 2020 · Apt 2H

    Close
  • Heat/hot water

    Entire building

    Feb 15, 2020 · Apt 1H

    Close
  • Heat/hot water

    Entire building

    Oct 20, 2019 · Apt 2R

    Close
Show 17 more ↓
  • Heat/hot water

    Apartment only

    Mar 19, 2018 · Apt 3M

    Close
  • Heat/hot water

    Entire building

    Mar 12, 2018 · Apt 1

    Close
  • Heat/hot water

    Entire building

    Jan 2, 2018 · Apt 5G

    Close
  • Heat/hot water

    Apartment only

    Dec 28, 2017 · Apt 1E

    Close
  • Heat/hot water

    Entire building

    Nov 28, 2017 · Apt 5A

    Close
  • Heat/hot water

    Entire building

    Jan 9, 2017 · Apt 5A

    Close
  • Heat/hot water

    Apartment only

    Feb 15, 2016 · Apt 5S

    Close
  • Heat/hot water

    Apartment only

    Oct 5, 2015 · Apt 3K

    Close
  • Heat/hot water

    Entire building

    Feb 15, 2015 · Apt 1K

    Close
  • Heat/hot water

    Entire building

    Feb 5, 2015 · Apt BLDG

    Close
  • Plumbing

    Water supply

    May 30, 2013 · Apt BLDG

    Close
  • Heating

    Heat related

    Oct 5, 2011 · Apt 2G

    Close
  • Heating

    Heat related

    Nov 28, 2010 · Apt 3A

    Close
  • Appliance

    Electric/gas range

    Feb 26, 2010 · Apt 2E

    Close
  • Heating

    Heat related

    Feb 19, 2010 · Apt NA

    Close
  • Heating

    Heat related

    Jan 20, 2009 · Apt 3R

    Close
  • Nonconst

    Vermin

    Jul 25, 2007 · Apt 3Q

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hospital / health (I1)
Year built
1920
Floors
5
Residential units
—
Building area
39,900 ft²
Lot area
20,963 ft²
Zoning
R7-1
Community board
203
Council district
16
Block / lot
2925 / 29
Assessed value
$2,359,800
Landmark / historic district
No

HPD registration #227288, last renewed Jul 24, 2025.

Questions about 3674 3 Avenue

Who owns 3674 3 Avenue?

The owner of record in NYC Department of City Planning PLUTO data is Thirdview LLC.

Does 3674 3 Avenue have violations?

Yes. NYC HPD has recorded 6 housing violations at this property.

Is 3674 3 Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 3674 3 Avenue built?

City records list 1920 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.