450 St Pauls Place
Bronx, NY 10456BBL 2-02902-0001Map
Owner of record: NYC Department Of Education
450 St Pauls Place is a school building built in 1916 in Bronx, 10456. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 32
- ECB violations
- 87
- HPD complaints
- 1
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 32
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed
Show 22 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed
ECB violations · 87
- Class - 2
Reissue on ecb#356933356n failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency illuminated discharge exits and e
Jul 10, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb#35693359z exit door not self-closing.noted:emergency exterior exit doors not self closing due to binding,missing and or faulty hardware at exterior exit 11 behind stage exterior exit 4 2 doors ex
Jul 10, 2026 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:fire ratedclassroom and smoke doors not self closing due to binding,missing and or faulty hardware on classrooms 403,407,409,411,418,322,313,320,318,3
Jul 10, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:missing and or cracked stairwell wire mesh glass panels and vision panels on fire rated smoke doors on stair f from 3rd to 4th fl missing,stair f 4 an
Jul 10, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:on retaining wall perimeter at exposure#2 and #3 has missing chunks of concrete on base of wrought iron gate fence observed upon inspection.rem:repair
Jul 10, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb #35677121z. failure to maintain building in code-compliantmanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at(1st fl) cafeteria, auditorium and gym
Aug 21, 2025 · Penalty $1,250
Active - Class - 2
Reissue ecb #35677120r. failure to maintain building in code-compliantmanner. no firestopping per bc 712.3; 27-345. noted: at(cellar) electrical room firestopping missing/none ceiling. remedy: provide/maintain
Aug 21, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: at(6th fl) stair a provided/installed with kick door stopped where not allowed. r
Aug 21, 2025 · Penalty $1,250
Resolve - Class - 2
Exit door not self-closing. noted:: at(1st fl) stair c, b, exit 11, cafeteria, (3rd fl) hallway smoke door near rm 306 stair a/b(4th fl) hallway smoke door near rm 407, stair a/b, e(6th fl) stair a doors are in
Aug 20, 2025 · Penalty $625
Active - Class - 2
Reissue#35672183l date of issue:01.25.2023 failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at the time of inspection observ
Aug 22, 2024 · Penalty $1,562
Active
Show 40 more ↓
- Class - 2
Reissue#35672188k date of issue:01.25.23 failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.at the time of inspection i observed that at cellar level electrical room side
Aug 22, 2024 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code compliant manner.at time of inspection observed fire proof self closing doors not closing properly.at 3rd fl staor c,stair h and double doors by rm 306.at 2nd fl stair h, st
Jan 25, 2023 · Penalty $625
Resolve - Class - 2
28-301.1 unlawful display of artwork in corridors greater than 20% perfdny 20/08 code;fc 803.3.2.at time of inspection throughout floors 1-5observed excessive placement of combustible material(artwork)at corrid
Jan 25, 2023 · Penalty $1,250
Resolve - Class - 2
Unlawful placement of furnishings,decorations or other objects at exits that obstruct access to egress from or visibility thereof per fdny 2008 code;fc 1027.4.at time of inspection observed at basement level ca
Jan 25, 2023 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner:no firestopping per bc 712.3;27-345.at time of inspection observed at cellar level electrical room,penetrations in ceiling along pipes,no firestopping in pl
Jan 25, 2023 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.at time of inspection observed at cellar level electrical room a puddle of water on the floor adjacent to electrical equipment.water leaking from pipe runni
Jan 25, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35644549z failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1,27-381.at time of inspection observed emergency lights not opera
Jan 25, 2023 · Penalty $1,562
Active - Class - 2
Exit door not self closing.at time of inspection observed exterior exit doors not self closing at:exit 1 scrapes on the bottom,exit 8 doesn't close fully,main entry middle & left doors do not close properly.rem
Jan 25, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35542637l failure to maintain bldg in code compliant manner. noted: at time of my inspection,i observed at bulkhead level of staircase g & h several step vertical & horizonal cracks on the walls of the
Mar 7, 2022 · Penalty $625
Resolve - Class - 2
Reissued#35467976z failure to maintain bldg in code compliant manner. illumination for exits,exit discharges & public corridor per bc 1006.1.27-381. noted: at time of my inspection,i observed at time of testing
Mar 7, 2022 · Penalty $625
Active - Class - 2
Reissue#35475674n failure to maintain bldg in code-compliant manner bulkhead level staircase g&h cracks in wall.repair &/or replace.
Jan 27, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination for exits ,exit discharges and public corridors per bc 1006.1;27-381.note:observed during inspection that the mergency lighting for yard c #1 t
Feb 27, 2020 · Penalty $625
Active - Class - 2
Exit door not self-closing.note:observed during inspection that @ 5th fir/st.g,4th fir/st.e,3rd fir-st.c,2nd fir-st.f & st.e,1st fir-st.a(exit#1),ground fir-lunchroom(exit#2),ground fir between yard#c & main lo
Feb 27, 2020 · Penalty $625
Resolve - Class - 2
Re-issue#35384077l.failure to maintain bldg in code-compliant manner.note:observed at bulkhead level of staircase g & h several step(vertical & horizontal)cracks on the walls of the staircase.remedy:repair and/
Feb 27, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue # 35316757k. failure to maintain bldg in code compliant mannernoted:@ time of insp i observed several cracks @ bulkhead staircase(h)also different cracks on wall, horizontal & step cracks observed @ bul
Feb 5, 2019
Resolve - Class - 2
Reissue # 35316755r. failure to maintain bldg in code compliant mannernoted @ time of insp i observed missing mortar between exterior brick wall throughout was observed condition safeguard by a sidewalk shed @
Feb 5, 2019
Resolve - Class - 2
Reissue # 35316764p. failure to maintain bldg in code compliant manner.noted: @ time of insp i observed damage in class room #402 from waterr penetration through ceiling was observed also ceiling an walls in th
Feb 5, 2019
Resolve - Class - 2
Re-issue# 352348142. failure to maintain bldg in code-complaint manner. noted: water penetration through ceiling was observed in classroom# 402, also @ ceiling & walls in the staircase (c) bulkhead,area, & @ 1s
Jan 29, 2018
Resolve - Class - 2
Exit door not self-closing. noted: @ 2nd flr east corridors 1st flr exit: 1st flr staircase h, exit 7, doors not self closing was observed. rem: repair/replace door.
Jan 29, 2018
Resolve - Class - 2
Re-issue# 35234816m. failure to maintain bldg in code-compliant manner: lack of emergency lighting for exits, exit discharges & public corridors per bc 1006.1; 27-542. noted: @ 1st flr/staircase (f), @ right ex
Jan 29, 2018
Resolve - Class - 2
Failure to maintain bulding in code compliant manner. noted: several cracks obseved at bulkhad, saircase h, also different cracks on walls,horizontal and step cracks observed at bulkhead,stairca
Jan 29, 2018
Resolve - Class - 2
Re-issue# 35234813r. failure to maintain bldg in code-compliant manner. noted: missing mortar between exterior brick wall thoughout was observed, condition safe guard by a sidewalk shed @ school perimeter. rem:
Jan 29, 2018
Resolve - Class - 2
Exit door not self closing. noted: @ 2nd story east corridor, 1st flr exit 8, 1st flr staircase (f) exit 5, 1st flr staircase (h), exit 7, doors not self closing were observed. rem: repair/replace door.
Feb 28, 2017
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtenances. noted: water penetration through the roof was observed @ (1) bulkhead area staircase 'd' & @ classroom 402. rem: maintain exterior bldg wall.
Feb 28, 2017
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtenances. noted: missing mortar between exterior bricks wall throughout was observed, condition safeguard by a sidewalk shed @ school perimeter. rem: maintain exterior b
Feb 28, 2017
Resolve - Class - 2
Bldg or open lot occupied w/out a valid c of o. noted: bldg has been occupied w/out a valid c of o as a school. rem: obtain valid c of o or discontinue illegal occupancy.
Feb 28, 2017
Resolve - Class - 2
Failure to comply w/ the commissioner's order contained in summons/violation# 35085700y issued on 3/5/14 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. for: erecting shelving over 6" & above doorway, w
Feb 28, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits, exit discharges & public corridors per bc 1006.1; 27-542. noted: defective emergency lighting was observed @ 1st flr exit
Feb 28, 2017
Resolve - Class - 2
Reissue #35085700y. work without at room 316 erected sheiving above entry door 6ft to 10ft high for compiters 1 exterior fiber optics wiringno permit on file teacher room. remedy: comply with notice of violatio
Mar 29, 2016
Resolve - Class - 2
Sec. 3307.6.5 sidewalk shed erected under job#201194796 along exp#1 has 3 inoperable bulbs rendering the affected area visibly dark & shadowy creating a potential risk to public safety. remedy: comply w/notice
Jan 7, 2016 · Penalty $830
Resolve - Class - 2
Re-issue#35085701k excessive combustible sign hanging fl light fixture,pipes,(conduits) & on walls protruding from walls.rem:remove all items do not exceed 20% of wall space.
Feb 25, 2015
Resolve - Class - 2
Re-issue#35085782h excessive wiring.(back)wires not secure & excessivebunching roofs,front,& corners of bldg.rem:secure all wiring or remove.
Feb 25, 2015
Resolve - Class - 2
Re-issue#35085699x emergency lighting defective all exit discharges for public corridors & throughout defective.rem:maintain emergency lighting replace all.
Feb 25, 2015
Resolve - Class - 2
Re-issue#35085700y work w/out a permit @rm 316 erected shelving over 6' above enter door for computers & exterior & fiber added.rem:got proper permit or restore to prior legal condition.
Feb 25, 2015
Resolve - Class - 2
Re-issue#35016847j defective doors @2nd fl stair a & b 1st fl stairs e@exit 13 doors noy closing properly.rem:replace doors.
Feb 25, 2015
Resolve - Class - 2
Illumination for exits, exit discharge public corridors including gyms,cafeteria throughout the bldg. remedy:maintain emergency lighting as per code.
Mar 5, 2014
Resolve - Class - 2
Room 316 erected shelving over 6'-0" & above doorway. remedy:install shelving and/or brackets as per code.
Mar 5, 2014
Resolve - Class - 2
Reissue-35016847j defective doors: 3rd fl exit 1 2nd fl stairs a,b,g ground flr exterior exit 1 stwy a-b, exit 5/f cafeteria exit 4 racked not self closing. remedy: maintain.
Mar 5, 2014
Resolve - Class - 2
Black wires not secured & excessive bunching @ 1)roofs. 2) front & corner of bldg. remedy: secure all wiring and/or remove.
Mar 5, 2014
Resolve - Class - 2
Hang signs 4th fl signs hanging from light fixtures cafeteria signs hanging from pipes/conduits. remedy:maintain bldg as per code.
Mar 5, 2014
Resolve
Complaints
- Heat/hot water
Entire building
Jan 9, 2023 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1916
- Floors
- 5
- Residential units
- —
- Building area
- 123,000 ft²
- Lot area
- 73,590 ft²
- Zoning
- R7-1
- Community board
- 203
- Council district
- 16
- Block / lot
- 2902 / 1
- Assessed value
- $8,986,500
- Landmark / historic district
- No
Questions about 450 St Pauls Place
Who owns 450 St Pauls Place?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 450 St Pauls Place have violations?
NYC HPD has no housing violations on record for this property.
Is 450 St Pauls Place rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 450 St Pauls Place built?
City records list 1916 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.