1600 Webster Avenue

Bronx, NY 10457BBL 2-02897-0005Map

Owner of record: NYC Department Of Education

1600 Webster Avenue is a school building built in 1974 in Bronx, 10457. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
64
ECB violations
101
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 64

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 22, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 7, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
Show 40 more ↓
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 9, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    Nyc department of education

    Mar 14, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 13, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 18, 2012

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 8, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 5, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 19, 2008

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 27, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 15, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 24, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 26, 2004

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Elevator elevatorrequired

    2p4839

    Feb 20, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Elevator elevatorrequired

    2p4839

    Feb 15, 2001

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed

ECB violations · 101

  • Class - 2

    Reissue#35693288k exit door not self-closing.noted:exterior exits 4,5 and 7 do not self-close properly when tested at the time of inspectiondoor frames for those exits are also in disrepair.rem:repair/replace d

    Jul 10, 2026 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35693287z failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:emg lights on 3rd flr gym 3 were not opertional at

    Jul 10, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:interior fpsc doors do not self-close properly at 2nd flr-library door.1st flr-gymnasium door a.classroom doors do not self-close properly at 4th flr

    Jul 10, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35677116y date of issue: 08-22-2024. exit door not self-closing properly. at the time of inspection observed and noted at 4th fl. stairway "g" one exit door, at 4th floor near rm-424 1 corridor exit do

    Aug 20, 2025 · Penalty $625

    Active
  • Class - 2

    Reissue: 35677119j date of issue: 08-22-2024. failure to maintain building in code-compliant manner. illumination for exits, exit dischargesand public corridors per bc 1006.1; 27-381. at the time of inspection

    Aug 20, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35672147y date of issue:01.24.2023 failure to maintain building in code-compliant manner.at the time of inspection observed fireproof self closing doors not closing properly at auditorium entrance door

    Aug 22, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35672144z date of issue:01.24.23 failure to maintain building in code compliant manner.at the time of inspection observed that auditorium ciling above stage is spalling and missing cement has fallen exp

    Aug 22, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at thetime of inspection observed that at 2 place emergency exit light is no

    Aug 22, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35672148x date of issue:1.24.2023 exit door not self-closing properly at the time of inspection exit 2a panic bar,exit 4 & exit 5 at4th fl exit-7,one door,4th fl exit-3 2 doors,1st fl auditorium 3 exit

    Aug 22, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.at time of inspection observed fireproof self closing doors not closing properly.at auditorium entry door and right stage door both are racked.at 2nd floor

    Jan 24, 2023 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Reissue#35644545l failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at time of inspection observed existing emergency lights

    Jan 24, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35644544j failure to maintain building in code-compliant manner:no firestopping per bc 712.3;27-345.at time of inspection observed at basement level gas meter room,openings in concrete ceiling no firest

    Jan 24, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35644546n failure to maintain building in code-compliant manner.at time of inspection observed at auditorium ceiling above stage is spalling and missing cement that has fallen exposing wire lath.missing

    Jan 24, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self-closing.at time of inspection observed exterior exit doors not self closing.exit 2a panic bar defective and rubs can saddle.exit 4 does not close fully and exit 5 gets stuck on saddle.rem:rep

    Jan 24, 2023 · Penalty $625

    Active
  • Class - 2

    Reissue #35548321m failure to maintain building in code compliant manner.no fire stopping per bc 712.3;27 345.noted:at time of inspection observed at basement level at gas meter room openings in concrete ceili

    Mar 7, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue #35548320k failure to maintain building in code compliant manner:illumination for exits exit discharges and public corridors per bc 1006.1; 27-381.noted:at time of inspection observed existing emergency

    Mar 7, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissued #35548319n failure to maintain building in code compliant manner.noted:at time of inspection observed at auditorium spalling and missing cement has fallen exposing wire late missing acoustical ceiling

    Mar 7, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35548318l failure to maintain bldg in code compliant manner. noted: at time of my inspection,i observed fire proof self closing doorat 4th fl exit 4,3 fl exit 2,4,7 stair. are racked & dont fully selfcl

    Mar 7, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:noted:observed@auditorium,spalling&missing cement that has fallen exposing wire lathe,missing acoustical ceiling tiles due to water penetration.repair &/or repl

    Feb 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:observedexisting emergency lights w/battery backup power #ed 302,109,104,102,b

    Feb 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s) or appurtenances:noted:observed@exp1(west elevation) corrugated metal roofing sheet above exith in disrepair,missing sec&loose near edges.maintain exterior bldg wall.

    Feb 9, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:noted:observed fireproof selfclosing doors@4flexit4,3flexit7,1flexit2,4,7&stairb are racked&don't fully selfclose due to doors knocking on doorframe.repair &/or

    Feb 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:no fire stopping perbc712.3,27-345.noted:observed@bsmt's gasmeterrm,openings in concrete ceiling slab w/pipe penetrations&@electricalrm,condiuits penetrating in

    Feb 9, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Re-issue#35229037r.failure to maintain bldg incode-compliant manner.noted:at main entrance and walkeays uneven concrete pavement from street to bldg entrance door also cracked throughout.rem:repair and/or repla

    Jan 29, 2018

    Resolve
  • Class - 2

    Bc28-301.1:unlawful placement of furnishings,decorations or other object at exits that obstruct access to egress from or visibility there of per fdny 2008 code;fc 1027.4.noted:at library discharge a horizontal

    Jan 29, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.no fire stopping perbc 712.3;27-345.noted:missing fire stopping was observed at boiler rm,gas meter rm and at electric meter rm throughout ceiling and walls.rem

    Jan 29, 2018

    Resolve
  • Class - 2

    Re-issue#35235076k:failure to maintain bldg in code-compliant manner.noted:at exp#3(rear side of bldg)a broken window glass was observed at 1st fl.rem:repair and/or replace.

    Jan 29, 2018

    Resolve
  • Class - 2

    Exit door not self-closing.noted:at 4th fl exit 7 on stairway(g)door was not self-closing due to broken hinges.rem:reparir/replace door.

    Jan 29, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-complian manner.noted:step cracks obsrved at north wall in the hallway leading to east corridor from left exit at auditorium's stage.rem:repair and/or replace

    Jan 29, 2018

    Resolve
  • Class - 2

    Re-issue#35229049y.miscellaneous violation.unlawful display of artwork in corridors greater than 20% per fdny 2008 code fc803.3.3.2.noted:an excessive amt of art work and walls.decorations was observed on wall

    Jan 29, 2018

    Resolve
  • Class - 2

    Occupancy contrary to that allowed by the certificate of occupancy or bldg dept records. noted: bldg is being used as a school, contrary to cofo #68850 that indicates accessory wholesale and retail sales,access

    Feb 23, 2017

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. noted: at exp3 (rear side of bldg) a broken window glass was observed at 1st floor level. rmdy: maintain exterior building wall.

    Feb 23, 2017

    Resolve
  • Class - 2

    Exit door not self closing. noted: not self closing door observed at 4th floor staircase (g),3rd floor,staircase(g),2nd floor main entrance 1st floor, exit 7. rmdy: repair/replace door.

    Feb 23, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. lack of emergency lighting for exis,exit discharges and public corridors per bc1006.127-542. noted: at 1st flr exit #6 and #7 and at gymnasium, emergency

    Feb 23, 2017

    Resolve
  • Class - 2

    28.301.1 unlawful display of artwork in corridors greater than 20% per fdny 2008 code; fc 803.3.3.2 noted: an excessive amount of art work and walls decorations was observed on walls,public corridors thro

    Feb 23, 2017

    Resolve
  • Class - 2

    Reissued #35120300x. for failure to maintain building in code compliant manner. noted: at main entrance and walkways uneven concrete pave ment from street to entrance also cracked.rmdy:maintain exterior bldg

    Feb 23, 2017

    Resolve
  • Class - 2

    Uneven concrete pavement. at main entrance and walkays uneven concretepavement from street to entrance also cracked. rmdy: replace concrete and remove tripping hazard and dangerous conditions.

    Feb 24, 2015

    Resolve
  • Class - 2

    Reissue #34923316n standpipe panel missing. standpipe missing cabinet and panel locks,gate valve handles and pipe thread caps throughout entire school. rmdy: replace cabinets and hardware.

    Feb 24, 2015

    Resolve
  • Class - 2

    Excessive combustibles. at all floors and corridors combustible art,decorations papers and pictures (also classrooms hanging from pipes.rmdyremove all items (corridors and hanging on classrooms ceiling do not

    Feb 24, 2015

    Resolve
  • Class - 2

    Paint room- no vent. remedy: maintain paint room as per code.

    Mar 3, 2014

    Resolve
  • Class - 2

    Re-issue # 35022775k,34982076n,34923316n. various locations. standpipe handles, missing panel doors, pipe thread caps. remedy: maintain staandpipe cabinets as per code.

    Mar 3, 2014

    Resolve
  • Class - 2

    Illumination for exits, exit discharge & public corridor missing at: 1- 4 floor. 2- 2nd floor exits a,b,c,d. 3- 3rd floor exits a,b,c,d. 4- cafeteria (1 out) & gym (1 out).

    Mar 3, 2014

    Resolve
  • Class - 3

    Re-issue # 35018374h,34982080x. main entry handicap entrance missing bottom rail. remedy: install railing as per code.

    Feb 28, 2014

    Resolve
  • Class - 3

    Re-issue # 34982075l,34923318r. ceramic tile missing from wall of kitchen storage room- kitchen sinks. remedy: install &/or replace kitchen tile.

    Feb 28, 2014

    Resolve
  • Class - 2

    Spaces not fully enclosed with cmu/concrete cellar. 1- elecric meter room, at pipe chase. 2- electric panel chase at c-13 open to corridor. 3- c-11 fan exhaust into cellar corridor. 4- paint room, no vent thru

    Feb 28, 2014

    Resolve
  • Class - 2

    Reissue 34923316n,34982076n standpipe valve handles missing & pipe thread caps. rmdy: replace valve/caps.

    Jun 4, 2013

    Resolve
  • Class - 3

    Reissue 34982080x partial handrail missing at handicap entrance. rmdy: replace railing.

    Jun 4, 2013

    Resolve
  • Class - 2

    Reissue: 34923312x auditorium entrance steps missing 4 total handrails. remedy: replace handrails.

    Jun 27, 2012

    Resolve
  • Class - 3

    Reissue: 34923310m water penetration at bulkheads of stwy 'b' & 'c' causing damage below. remedy: water proof bulkheads.

    Jun 27, 2012

    Resolve
  • Class - 3

    Reissue: 34923311y floors,walls & ceilings at stairway 'b' & 'c' bulk heads are water damaged. remedy: repair defects.

    Jun 27, 2012

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1974
Floors
3
Residential units
—
Building area
132,000 ft²
Lot area
127,363 ft²
Zoning
R7-1
Community board
203
Council district
15
Block / lot
2897 / 5
Assessed value
$16,839,000
Landmark / historic district
No

Questions about 1600 Webster Avenue

Who owns 1600 Webster Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 1600 Webster Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 1600 Webster Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1600 Webster Avenue built?

City records list 1974 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.