718 Bryant Avenue
Bronx, NY 10474BBL 2-02763-0279Map
Owner of record: NYC Department Of Education
718 Bryant Avenue is a school building built in 1974 in Bronx, 10474. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 44
- ECB violations
- 93
- HPD complaints
- 3
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 44
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Retaining wall none
Failed to file cycle 1 technical report by 12/31/2018 per rcny 103-09
May 1, 2024
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 5, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 5, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 13, 2018
Dob violation - resolved
Show 34 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Apr 13, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 2, 2017
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2014 inspection/test
Jun 10, 2015
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 6, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 12, 2013
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2011 inspection/test
Oct 1, 2012
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2010 cat 1 insp/tst
Aug 15, 2012
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 3, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 19, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 18, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 26, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 13, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 13, 2004
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 21, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 18, 2003
Dob violation - resolved - Elevator elevatorrequired
2p4718
Feb 20, 2002
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed
ECB violations · 93
- Class - 2
Reissue on ecb #35725187p. failure maintain building in code-compliantmanner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: installation of illegal kick stop hardware on fire rated d
Jul 24, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb #35725185l. failure to maintain building in code-compliant manner. noted: fire rated classroom and smoke doors not self-closing due to binding, missing and/or faulty hardware on classrooms 437, 4
Jul 24, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb #35725184j. failure to maintain building in code-compliant manner. illumination for exit, exit discharges and public corridors per bc 1006.1' 27-381. noted: emergency illuminated discharge exit a
Jul 24, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: wire mesh glass vision panel on fire rated smoke door missing in corridor 3rd floor by rm 337 observed upon inspection. remedy: repair and/or replac
Jul 24, 2026 · Penalty $1,250
Active - Class - 2
Reissue on ecb #35725183h. failure to maintain building in code-compliant manner. noted: ansul fire suppression system missing on a three burner commercial stove in school cafeteria kitchen observed upon inspec
Jul 24, 2026 · Penalty $3,125
Active - Class - 2
Reissue ecb #35725188r. failure to maintain building in code-compliantmanner. noted: at gas meter room at basement/cellar level used for storage with misc. materials consisting of desks, garbage bins chairs com
Jul 24, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35692575z failure to maintain building in code-compliant manner.noted:at cafeteria kitchen stand alone three burner gas stove in place without an ansul system present.rem:comply with code.
Sep 2, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35692574r failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:approx.30% of emergency lights throughout the schoo
Sep 2, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:self-closing interior classroom doors do not close 4th flr-481,485,483,453,459,471,473.3rd flr-339,337,307,365,361,351.2nd flr-245,233,219,207,201.1st
Sep 2, 2025 · Penalty $1,250
Active - Class - 2
28-301.1 unlawful display of artwork in corridors greater than 20% perfdny 2008 code;fc 803.3.2.noted:during inspection observed banners on ceiling hanging down on the 3rd flr,2nd flr.rem:comply with notice of
Sep 2, 2025 · Penalty $1,250
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.noted:during inspection observed firestopping missing in several areas.in electrical room.rem:provide/maintain firestopp
Sep 2, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:observed material in gas meter room during inspection.desk,bones,minis(garbage bins)chair,books.rem:remove all material.
Sep 2, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:during inspection observed kick stops on classroom doors,4th flr 449,445,2nd flr-247
Sep 2, 2025 · Penalty $1,250
Active - Class - 2
Reissue #35674804y. failure to maintain building in code-compliant manner. noted at cafeteria kitchen, stand alone three burner gas stove inplace without an ansul system present. remedy: comply with code.
Nov 6, 2024 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted approx. 30% of emergency lights throughout the school various lev
Nov 6, 2024 · Penalty $625
Active - Class - 2
In responds to complaint on existing 4 story school building under alteration, i observed installed supported pipe scaffold in all places of exterior exposures. during inspection i noted at exposure-3 on longfe
Sep 26, 2023 · Penalty $6,250
Active - Class - 2
Failure to maintain building in code complaint manner. noted: observed during inspection of hallway over rm 329 ceiling has become porous allowing water penetrating into building. remedy: repair and/or replace
Jun 8, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted: observed during inspection of cafeteria kictehn, stand alone three burner top stove present without ansul system presnet. remedy: comply with code
Jun 8, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner. noted: observed during inspection of gas meter room, no light fixture present a drop light on a extension cord being used.remedy: repair or replace
Jun 8, 2023 · Penalty $625
Resolve - Class - 2
Exit door not selfclosing properly atoi.i observed that atoi¬ed 4flcorridor exit door near rm444,4fl near stairwayd 2exit doors,4fl near rm439.1corridor exit door@3fl near stairwayf 1exit door not selfclosin
Jul 8, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381 atoi i observedthat near rm355 3emer exit sign&3emer exit light@4fl near rm465&455 ea
Jul 8, 2022 · Penalty $625
Resolve - Class - 2
Exit door not self closing. note: at 3rd fl by exit #7 & at 1st fl exit #3 doors not self closing when tested. remedy: repair/replace door.
Aug 26, 2019 · Penalty $5,000
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: illumination for exits;exit discharges & public corridor per bc1006.1;27-381. note: at 4th fl by room 449,by rm 456,across 465,by 492,over stair'e'by rm 439.
Aug 26, 2019 · Penalty $625
Resolve - Class - 2
35m07,39x10,02x10,64m07,69b11,42m07. 35m-provide electric box cover; 39x-repair light; 02x-repair in car phone; 64m-provide in car; 69b-provide up to code data tag; 42m-provide bypass switches.
May 15, 2019
Resolve - Class - 1
Cu05l10,cu48b10,46m07,70z09. 2 cease use items (a) 05l-repair restrictor; b-48b-add oil to tank oil very low and contact nycdob of restore to srvice inspection ; 46m-provide ventilation in motor room; 70z-remo
May 15, 2019
Resolve - Class - 2
28-301.1 failure to provide ventilation to gas meter rm per p.115.6 (1988 code) fgc appendix e(e4) (2019 code) in 2nd fl gas (meter) room noventilation observed @the time of insp.rem:comply w/notice of vio,
Jul 30, 2018
Resolve - Class - 2
Exit door not self closing @4th fl stair way "d" one door 4th fl near rm no 443 one (corridor) exit door.@3rd fl near exit door "7" one (corridor) exit door @2nd fl near exit "b" one door in 1st fl near exit 3
Jul 30, 2018
Resolve - Class - 2
Reissue#35216614p failure to maintain bldg in code compliant manner. noted on 1st fl room#104 is being occupied as classroom/office w/o no adequate ventilation or natural light. remedy: repair/or replace.
Jun 16, 2017
Resolve - Class - 2
Sec. 28-301.1 reissue vio#35127832z failure to provide ventilation(natural or mechanical)to occupied spaces per mc401.2: noted room#104&128 occupied as services room not have ventilation. remedy: comply w/notic
Jun 16, 2017
Resolve - Class - 2
Failure to maintain building in code-compliant manner. observed: missing ceiling in room 263 near exit "a" approx. 1'x1'(ft). also, next to room #171 in hallway removed radiator leaving hole in wall approx 2'x3
Jun 16, 2017
Resolve - Class - 2
Reissue#35216615r failure to maintain bldg in code compliant manner(interior)noted water penetration from roof resulting in spalling plaster on 3rd fl auditorioum ceiling & ceiling near security area.
Jun 16, 2017
Resolve - Class - 2
Failure to maintain building in code compliant manner: lack of emergency lighting for exits. exit discharges and public corridors per bc 1006.1; 27-542; note light unit. 1,2,4,6,8,9,10,12,13,14,15,17,22,26,34,2
Jun 16, 2017
Resolve - Class - 2
Failure to maintain building in code compliant manner: observed room 263 2nd flr, near of exit a 12'x12'area apprx missing ceiling, at 1st fl near of room 171 blank space from radiator elimination.rmdy:repair
Jun 16, 2017
Resolve - Class - 2
Reissue #35127831r failure to maintain bldg walls or appurtenances.(exterior). noted: on the bryant ave side bottom of the hill. the retaining wall is out of plumb & leaning inward. remedy: maintain exterior
Nov 9, 2016
Resolve - Class - 2
Reissue #35127832z failure to maintain bldg in code compliant manner. noted: on 1st fl room 104 is being occupied as classroom/office w/no adequate ventilation or natural light. remedy: repair &/or replace.
Nov 9, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.(interior)noted: observed water penetration from roof resulting in spalling plaster on 3rd fl auditirium ceiling & ceiling near security desk area.
Nov 9, 2016
Resolve - Class - 2
Reissue #35093506k failure to maintain bld in code compliant manner.ceiling tiles missing & defective @rm 207 corridor near rm 238.rem:comply w/notice of vio.
Aug 21, 2015
Resolve - Class - 2
Re-issue#35023427z failure to maintain bldg walls or appurtenances retaining wall leaning & out of plumb on bryant ave side toward bottom of hill.rem:comply w/notice of vio.
Aug 21, 2015
Resolve - Class - 2
Re-issue #35023426r failure to maintain in code compliant manner.no ventilation for required space rms 104 & 128 rms occupied as service rms.rem:comply w/notice of vio.
Aug 21, 2015
Resolve - Class - 2
Floor defective in the following rooms &/or areas: stwy f 1st fl landing,room 346,exit 6/f on 3rd fl,stwy d/i landing,near room 218 hallway,6/f 2nd fl & landing between 2nd & 1st fl,5e 1st fl landing & between
Mar 19, 2014
Resolve - Class - 2
Main water shut-off room. sprinkler shut-off valve cmu wall partially collapsed -room not full enclosed. remedy: maintain bldg as per code. remove bike from area.
Mar 19, 2014
Resolve - Class - 2
Fuel tank room - access panel anchors not embedded in concrete & cmu wall - (at pipe chase). remedy: install access panel as per code.
Mar 19, 2014
Resolve - Class - 2
Partial obstruction. exit 1/a on the 4th floor. floor plants partially obstruction of egress. remedy: maintain bldg as per code.
Mar 19, 2014
Resolve - Class - 2
Auditorium stage right- handicap lift not operational. remedy: maintain handicap lift as per code.
Mar 19, 2014
Resolve - Class - 2
27-765. re-issue # 35023426r. no ventilation of occupied spaces as req at room designated 104 & 128. remedy: provide code compliant ventilation.
Mar 19, 2014
Resolve - Class - 2
Ceiling tiles missing &/or defective. room 207, corridor near room 238 missing tiles at corridors. remedy: maintain ceiling tiles as per code.
Mar 19, 2014
Resolve - Class - 3
Re-issue # 35023427z. bryant ave side. exterior concrete retaining wall is leaning & out of plumb approx 6" out of plumb, leaning towards children playground. remedy: maintain concrete retaining wall as per cod
Mar 19, 2014
Resolve - Class - 2
Work w/o permit.note:reissue nov #34937486n. work w/o permit (plumbing:gas line) in school lunch kitchen w/o automatic gas shugoff valve. rem:obtain permits/authorization.
Jun 13, 2013
Resolve - Class - 3
Reissue nov #34980658y:retaining wall out of plumb. 5' tall retaining wall @bryant ave exposure leaning/out of plumb. rem:repair defect noted.
Jun 13, 2013
Resolve - Class - 2
*doors not closing* @1st story exit discharge door exit 1. @3rd story cross corridor doors adjoining rooms 331 and 329. rem:repair and/or replace doors noted.
Jun 13, 2013
Resolve
Complaints
- General
Cooking gas
Oct 21, 2020 · Apt 5E
Close - Electric
Wiring
Jun 24, 2020 · Apt 8C
Close - Door/window
Door
Aug 29, 2014 · Apt 2R
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1974
- Floors
- 4
- Residential units
- —
- Building area
- 187,100 ft²
- Lot area
- 117,500 ft²
- Zoning
- R6
- Community board
- 202
- Council district
- 17
- Block / lot
- 2763 / 279
- Assessed value
- $18,776,700
- Landmark / historic district
- No
Questions about 718 Bryant Avenue
Who owns 718 Bryant Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 718 Bryant Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 718 Bryant Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 718 Bryant Avenue built?
City records list 1974 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.