roofy

1170 Rev James Polite Ave

Bronx, NY 10459BBL 2-02692-0014Map

Owner of record: NYC Department Of Education

1170 Rev James Polite Ave is a school building built in 1940 in Bronx, 10459. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
40
ECB violations
63
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 40

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 2, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 2, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 9, 2018

    Dob violation - resolved
Show 30 more ↓
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2016 inspection/test

    Sep 15, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 18, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 12, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 14, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 4, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 14, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2008

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 2, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 7, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 20, 2003

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Elevator elevatorrequired

    2p5264

    Aug 12, 1999

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 28, 1993

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed

ECB violations · 63

  • Class - 2

    Reissue on ecb #35672045n. altered/changed building occupied without avalid certificate of occupancy as per 28-118.3.1-28-118.3.2. noted: dob records show co number 200953110t026 expired 9/4/2018. observed at t

    Jul 21, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue on ecb #35672043j. failure to maintain building in code-compliant manner. noted: fire rated classrooms and smoke doors not self-closing due to binding, missing and/or faulty hardware on classrooms 317,

    Jul 21, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue on ecb #35672042h. failure to maintain building in code-compliant manner. noted: at exposure #4 in front of flagpole is missing a section of wrought iron fence from post to post, observed at the time of

    Jul 21, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue on ecb #35672041x. failure to maintain building in code-compliant manner. noted: wire mesh vision glass panels in stairwells missingat stair e from 3rd to 2nd fl and stair d from roof level to 3rd fl ob

    Jul 21, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: storage in electrical switching gear panel closets and main switch gear rm at basement/cellar level with misc items including janitorial products, c

    Jul 21, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: illegal kick stops installation on fire rated doors at classrooms c-22, 301, 239a

    Jul 21, 2026 · Penalty $1,250

    Active
  • Class - 2

    Altered/changed building occupied without a valid certificate of occupancy as per 28-118.3.1. noted: observed at time of inspection dob records show co number 200953110t026 expired 9/4/2018. remedy: obtain a va

    Sep 17, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted: observed exit door at exit 4 rubbing onto(saddle) bottom compromising the doors ability to open easily. remedy: repair and/or replace door.

    Sep 17, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observedat time of inspection fire proof self-closing door at stair c(1) left door not self-closing into jam. remedy: repair and/or replace.

    Sep 17, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observedat exposure #4 front of flag pole fence missing entire section from post to post. remedy: repair and/or replace.

    Sep 17, 2025 · Penalty $1,250

    Active
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observedin stair e(2) vision panel missing/replaced with inproper material. remedy: repair and/or replace.

    Sep 17, 2025 · Penalty $1,250

    Active
  • Class - 2

    Found weil mclain oil fired boiler model# h2594 with discharge pipe at low water cut off not long enough as required by code, cleaveland draft control on rear of boiler missing and wires were left exposed.

    Aug 27, 2025 · Penalty $1,250

    Active
  • Class - 2

    Found weil mclain oil fired boiler model # h2594 with defective smoke alarm on rear flue pipe of boiler and disabled (jumped out)

    Aug 27, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35663567x failure to maintain building in code-compliant manner windows not operating wear and tear do not stay open and broken.rem:repair and/or replace.

    Nov 12, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35665393y failure to maintain building wall(s) or appurtenances. noted: at boiler room, foundation wall has become porous allowed the rain water in the cellar. water puddle observed. remedy: make necce

    Jul 11, 2023 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue #35665394x failure to maintain building in code-compliant manner. noted: windows to not operate properly due to wear/tear over the long period of time throughout the building. remedy: repair/replace win

    Jul 11, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35665396j failure to maintain building in code-compliant manner. noted: at roof level, air pockets observed throughout the roof. remedy: make necessary repairs.

    Jul 11, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35591656h doi8.30.21 failure to maintain bldg wall(s) or appurtenances.atoi i observed&noted@cellar level foundation walls become porous&water penetrating thru walls&fls standing puddles of water.comply

    Jul 11, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue35591659n doi8.30.21 failure to maintain bldg in codecompliant manner illumination for exits,exit discharges&public corridors per bc1006.1;27-381.atoi observed noted@bsmt level near stairwayc 1emergency

    Jul 11, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not selfclosing property atoi.atoi i observed that@2fl near stairwayd 2exit doors,@2fl near staire 2exit doors@1fl exit2 outside 1exit door not selfclosing properly atoi when tested.repair or replace

    Jul 11, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue35591654y date8.30.21 failure to maintain bldg in codecompliantmanner.atoi i observed&noted on all exps of bldg exterior flood lightslocated on roof to shine for sidewalk&private walk arent in op.repair

    Jul 11, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35591655x doi8.30.21 failure to maintain bldg in codecompliant manner.atoi i observed that&noted upon@various locations thruout entire bldg windows not op properly due to several yars.repair or replace w

    Jul 11, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35591657j doi9.30.21 failure to maintain bldg in codecompliant manner.atoi i observed&noted@3fl rms319&322 ceiling water damage due to water penetrating on roof.repair or replace.comply w/code,repair or

    Jul 11, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35591653m doi8.30.21 failure to maintain bldg in codecompliant manner.atoi i observed that&noted@roof level numerous areas thruout uneven deterioration&discoloration of roofing material,many areas of roo

    Jul 11, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #35498395m.failure to maintain building in code compliant manner.noted:upon inspection observed on all exposures of building exterior flood lights located on roof to shine for sidewalk and private walk

    Aug 30, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #35498393z.failure to maintain building in code-compliant manner.noted:upon inspection observed at cellar level foundation walls become porous and water is penetrating through walls & floor creating p

    Aug 30, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Re-issue #35498392r.failure to maintain building in code-compliant manner.noted:upon inspection observed at 3rd floor rooms #319 & #322 ceiling water damage due to water penetrating roof.remedy:repair and/or re

    Aug 30, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #35498394k.failure to maintain building in code-compliant manner.noted:upon inspection observed at various locations throughout entire building windows not operating properly due to several years wear

    Aug 30, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issued #35498396y.failure to maintain building in code-compliant manner.noted:upon inspection observed at roof level numerous areas throughout uneven deterioration & discoloration of roofing material creatin

    Aug 30, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #35498391p.failure to maintain building in code-compliant manner.noted:upon inspection observed at electrical meter room excessive amount of cardboard boxes,school furniture & supplies along side combu

    Aug 30, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #3549839on.failure to maintain building in code-compliant manner:illumination for exits,exit discharge & public corridor per bc 1006.1.noted:upon inspection observed gymnasium & cafeteria,emergency lig

    Aug 30, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35443019k failure to maintain building in code compliant manner note at electrical room ilelgal storage of boxes school supplies and other combutable materials comply with notice of violation and do no

    Jun 5, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35443017r failure to maintain building in code compliant manner note at cellar level the foundation walls have become pourous and water penetrates through the walls and floors standing puddles of water

    Jun 5, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35443020h failure to maintain building in code compliant manner illumination for exits exit discharges and public corridors per cb 1006.1 noted at gymnassium and cafeteria the emergency exit lighting di

    Jun 5, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35443018z. failure to maintain building in code-compliant manner. note: water damage at ceiling in room 319 & 322 due to water penetration at the roof. remedy: repair and replace

    Jun 5, 2020 · Penalty $1,562

    Resolve
  • Class - 1

    Unsafe storage of combustable materials and equipment note observed inelectric room gas operated show blowers and town mowers stored illegally the school needs an outdoor container that can securely and safety

    Jun 5, 2020 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner note at roof level observed many areas of standing puddles of water an dsicoloration and dterioration of the roofing . repair and or replace roof and allow

    Jun 5, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35443016p failure to maintain building in code compliant manner noted windows do not operate properly throughout the building due to wear and tear repair and or replace windows where needed

    Jun 5, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain buidling in code compliant manner note the exterior flood lights around the perimater of the roof are not working properly repair and or replace exterior flood lights

    Jun 5, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:@electrical meter room,illegal storage of boxes,school supplies,etc.rem:comply with notice of violation.

    Aug 9, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.illumination for exits,exit discharges & public corridors per bc1006.1.notedl@gym & cafeteria,exit emergency lighting inoperative.rem:repair&(replace lighting).

    Aug 9, 2019

    Resolve
  • Class - 2

    Reissue #35347416y.failure to maintain bldg wall(s)or appurtenances.atcellar level,foundation wall has become porous at(north side)allowing the rain water into the boiler room.rem:maintain exterior wall

    Aug 9, 2019

    Resolve
  • Class - 2

    Reissue 35387444h.failure to maintain bldg in code compliant manner.noted:windows do not operate properly thru-out the bldg due to wear/tearalso @ roof top @elevator machine room,door do not close properly due

    Aug 9, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:@3rd fl @elevator btw room 319 & 322 roof leak.also @gym roof leak due to defective roof.rem:make necessary repairs.

    Aug 9, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. no fire stopping per bc 712.3, 27-345. noted at electric meter room, penetrations at wall(s) rmdy: comply with code.

    Jul 18, 2018

    Resolve
  • Class - 2

    Failure to maintain building wall(s) and appurtenances. noted: at gym window(s) slam down when opened some stick when opened. rmdy: comply w/commissioner's order and/or file a certificate of corre

    Jul 18, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner, lack of illumination for exits, exit discharges and public corridors per bc 1006.1, 27-381. noted: at auditorium, em light/sign hard wired to stage light

    Jul 18, 2018

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. noted: at boiler room, water damaged walls along north side. rmdy: comply with code.

    Jul 18, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.@gym ceiling near exit d has water penetration visible masonry spalling & peeling paint.rem:comply w/notice of vio.

    Aug 19, 2015

    Resolve
  • Class - 2

    Re-issue #35003015y failure to maintain bldg in code compliant manner @electrical rm fire stopping missing,pipe penetration thru masonry wall.rem:comply w/notice of vio.

    Aug 19, 2015

    Resolve

Complaints

  • Heating

    Heat related

    Dec 12, 2006 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1940
Floors
3
Residential units
—
Building area
77,400 ft²
Lot area
67,425 ft²
Zoning
R7-1
Community board
202
Council district
17
Block / lot
2692 / 14
Assessed value
$6,173,100
Landmark / historic district
No

Questions about 1170 Rev James Polite Ave

Who owns 1170 Rev James Polite Ave?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 1170 Rev James Polite Ave have violations?

NYC HPD has no housing violations on record for this property.

Is 1170 Rev James Polite Ave rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1170 Rev James Polite Ave built?

City records list 1940 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.