164 Willow Avenue
Bronx, NY 10454BBL 2-02587-0001Map
Owner of record: NYC Department Of Homeless Services
164 Willow Avenue is a care facility built in 1931 in Bronx, 10454. The owner of record is NYC Department Of Homeless Services. HPD has recorded 2 housing violations here, most recently on December 11, 2016.
- HPD violations
- 2
- DOB violations
- 28
- ECB violations
- 38
- HPD complaints
- 10
What to know
No open immediately-hazardous violations among recent records.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 2
- CImmediately hazardous
M/d law abate the nuisance consisting of scalding hot water at community bathroom, 4th story
Dec 11, 2016
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures at community bathroom, 1st story
Aug 8, 2016
Closed — Violation closed
DOB building violations · 28
- Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 4, 2020
Dob violation - active - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 27, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 4, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 29, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 25, 2014
Dob violation - resolved
Show 18 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Jan 31, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 31, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 28, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 15, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 14, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 14, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 23, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 8, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 27, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 24, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 14, 2004
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 21, 2003
Dob violation - resolved - Elevator elevatorrequired
2p3014
Feb 12, 2001
Dob violation - resolved - Elevator elevatorrequired
2p3014
Nov 20, 1999
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 28, 1993
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed
ECB violations · 38
- Class - 2
Class 2. car door gibs were found worn or missing, compromising proper door guidance and retention. accumulated dirt was observed in the door sill, on the car top, and in the pit, requiring cleaning, as per asm
Sep 24, 2026 · Penalty $625
Active - Class - 2
Class 2: firefighter's service phase i switch mulfunctioning - cylinder rotates 360, not always activating phase i operation mode, repair. toe guard loose, secure. provide updated maintenance log (last records
Mar 20, 2026 · Penalty $625
Active - Class - 1
Observed throughout the building no trap wrap insulation under sinks in bathrooms. on 4th floor in bathroom sprinkler head not installed properly. thid floor bathroom vent is back pitched. on second floor bathr
Mar 20, 2026 · Penalty $2,500
Active - Class - 1
In basement using pvc piping on waste line under slope sink. in cafeteria room open waste line. door by the water meter strikes waste line pipe. in basement jim caps are used on waste lines. also pipe penetrati
Mar 20, 2026 · Penalty $2,500
Active - Class - 1
Electrical closet not dedicated to electrical distribution equipment only. observed on the 1st fl electrical closet was not dedicated to electrical found computer servers and camera recording equipment in the s
Mar 20, 2026 · Penalty $1,200
Active - Class - 1
Electrical work without a permit. observed in exp #2 in the alley that the installation of a/c split unit compressor, and one new electrical panel in cafeteria to power unit. found no permit on file in biz/ dob
Mar 20, 2026 · Penalty $2,500
Active - Class - 2
Class 2: fire tabs on hoistway doors hanging rollers are not set to the upright position, re-adjust. toe guard loose, secure. both hoistway and car doors are not settting to fully open position, adjust. car doo
Aug 15, 2025 · Penalty $625
Active - Class - 1
Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed hole penetrations throughout building. potential fire hazard., provide/m
Feb 7, 2025 · Penalty $2,500
Resolve - Class - 1
Door zone restrictor inoperative. this is a safety feature which ensures passenger safety. remedy: to restore service, call the d.o.b. elevator division at (212) 393-2144 for a reinspection. class 2 items:brake
Sep 3, 2024 · Penalty $1,250
Active - Class - 1
Only elevator in the building out of service.
Apr 12, 2024 · Penalty $1,250
Resolve
Show 28 more ↓
- Class - 1
Door zone restrictor not working tampered with disabled(cu). brake maintenance tag expired and missing the date brake test was performed.
Apr 5, 2024 · Penalty $1,250
Resolve - Class - 1
97-x-17=entire device is inoperative upon inspection arrival. this is the only elevator premises. creating a hazardous condition as per 1rcny 11-02. remedy: repair the elevator back to service and contact nycdo
Oct 25, 2023 · Penalty $1,250
Resolve - Class - 2
Found boiler not operable, corroded and leaking return line, body fdrain missing on safety relief valve, coil relief valve missing, coil plate corroded
Aug 21, 2023 · Penalty $625
Resolve - Class - 2
Found dirty glass gauge, corroded hartford loop, coil relief valve missing.
Aug 21, 2023 · Penalty $625
Resolve - Class - 1
Out of service, restore to service
Aug 21, 2023
Resolve - Class - 2
Jim caps installed on cast iron fittings on first floor. as per plumbing code 708.1.6., repair and/or replace
Mar 22, 2023 · Penalty $625
Resolve - Class - 2
Found both oil pump sets running constant, should run when burner runs, latches and bolts missing on boiler doors, glass gauge guards missing, body drain on relief valve missing.
Sep 30, 2021 · Penalty $625
Resolve - Class - 1
Unlawful acts. failure to comply with an order of the commissioner. in 10/12/17 and 09/05/18. two violations was issued to the respondent. the respondent failed to comply with (nyc) code 250.4, 28-201.11, (ecb'
Oct 16, 2018
Resolve - Class - 1
An unlawful act failur to comply with an order to the commissioner.failure to correct and certify summons #35294527k(35294527k)for failure to ground the electrical installation that violation was issued on 10/1
Sep 5, 2018 · Penalty $6,250
Resolve - Class - 1
Cu05l10; 29l11. 05l10-upon inspection of device it was found that thecar door zone restrictor is defective repair and contact nycdob for return to service; 29l11-rmdy repair or replace. door closed.
Aug 14, 2018
Resolve - Class - 1
An unlawful act.failure to comply w/an order of the commissioner.failure to correct & certify summons #35313174p & 35294327k.rem:comply w/eccode/obtain permit.
Jul 13, 2018
Resolve - Class - 2
Exposed energized wiring. observed at electric meter bank. two meter switches not properly mounted to meter can enclosures. leaving energized parts exposed. note: violating condition previously cited under summ
May 15, 2018
Resolve - Class - 2
Buildings occupied without a valid certificate of occupancy.noted:observed a 4 story building occupied by d.h.s.as a shelter without a validcertificate of occupancy
May 8, 2018
Resolve - Class - 1
Unlawful acts. failure to comply with an order of the commissioner. in october 12, 2017, january 02,2018. two electrical violations was issued to the respondent. the respondent failed to comply with nyc e
Apr 24, 2018
Resolve - Class - 2
59b07,68m07,68m07,99bb05,42d06,40d06,50d06,39q03,16t07,21u07,39b07,100x10,70o02,34u07,80m07,67x10,61t07. 59-perform brake maint; 68-providemcp; 68-provide maint log; 99-perform sy test; 42-provide covers; 40-
Mar 19, 2018
Resolve - Class - 1
Unlawful acts.failure to comlply with an order of the commissioner. in october 12, 2017 a electrical violation was issued to the respondent .the respondent failed to comply with (nyc)electrical code #250.4(e
Jan 2, 2018
Resolve - Class - 1
Failure to ground electrical systems. observed at water main located in the basement: main grounding conductor electrode missing; has not been provided. to provide ground for buildings electrical distribution s
Oct 12, 2017
Resolve - Class - 2
Failure to maintain building in code compliant manner.observed on top floor no pressure gauge installed at the inspectors test station and on all floors no pressure bauges intalled at the floor control valves
Oct 12, 2017
Resolve - Class - 2
Unapproved, unsafe, unsuitable electrical equipment, aparatus, devices, materials, appliances or wiring in use. observed at electric meter bank room: two meter cans improperly mounted to enclosure; energized pa
Oct 12, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. observed on all floors above the cellar no pressure gauges installed at the floor controlvalves for the fire sprinkler system as required by the nppa13.
Jun 5, 2017
Resolve - Class - 2
Failure to maintain bldg code compliant. noted: at cellar, exposed, loose electric wiring left and right of elevator call station.2 separate electric meter panels have loose and hanging wires to wall mounted
Jul 21, 2016
Resolve - Class - 2
Occupancy contrary to building dept records. noted: building occupied as homeless shelter with 179 males. lno #5705 letter dated 01/14/16 states temporary 90 day letter of no objection.lno #5705 expired 04/14
Jul 21, 2016
Resolve - Class - 2
Failure to maintain building code compliant: lack of emergency lighting per bc1006.1; 27-542. noted: at 2a,4a and adjacent to 4th flr bed #23 and bed #/below, inoperative emergency lighting with battery backup.
Jul 21, 2016
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner. noted: 1) there are exposed (open) roof wood structure at top (4th) floor; 2) nyc bc-1968 classifies the shelter as occupancy group - j; 3) the lowest constru
Sep 19, 2014
Resolve - Class - 2
Sidewalk shed does not meet code specifications sidewalk shed erected under permit #210046118 has inoperable/not lit light fixtures at underside of shed. remedy: conform shed to code specifications.
Jan 31, 2009
Resolve - Non-hazardous
7l11-15l11-16l12-20l11-28h11-44l11-55x11 7l11=light ray 15l11=not self closing 3rd floor 16h12=1st fl 20l11=lights 44l11=arking
Apr 27, 2001
Resolve - Non-hazardous
7l11-15l11-16h12-20l11-28h11-44l11-55x11 7l11=light ray 15l11=not self closing 3rd fl 16h12=1st fl. 20l11-lights 44l11-arking
Apr 27, 2001 · Penalty $180
Resolve - Non-hazardous
57o,74x,28h,74d,40u,35z, 79-fix ems phone 35-water locks in motor room over main machine 40-2 year test 74-secure smoke hole in motor room.
Jan 23, 1998 · Penalty $180
Resolve
Complaints
- Plumbing
Water-leaks
Jul 22, 2013 · Apt 421
Close - Plumbing
Water-leaks
Jul 22, 2013 · Apt 421
Close - Heating
Heat related
May 23, 2013 · Apt 12
Close - Heating
Heat related
Nov 13, 2010 · Apt BLDG
Close - Heating
Heat related
Aug 28, 2009 · Apt A12
Close - Nonconst
Vermin
Jul 5, 2006 · Apt BUILD
Close - Heating
Heat related
Oct 24, 2004 · Apt BLDG
Close - Heating
Heat related
Jan 3, 2004 · Apt .
Close - Heating
Heat related
Jan 3, 2004 · Apt BLD
Close - Heating
Heat related
Jan 1, 2004 · Apt 4FL
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Care facility (N2)
- Year built
- 1931
- Floors
- 4
- Residential units
- —
- Building area
- 36,000 ft²
- Lot area
- 25,000 ft²
- Zoning
- M1-2
- Community board
- 201
- Council district
- 8
- Block / lot
- 2587 / 1
- Assessed value
- $779,850
- Landmark / historic district
- No
Questions about 164 Willow Avenue
Who owns 164 Willow Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Homeless Services.
Does 164 Willow Avenue have violations?
Yes. NYC HPD has recorded 2 housing violations at this property.
Is 164 Willow Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 164 Willow Avenue built?
City records list 1931 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.