250 East 156 Street

Bronx, NY 10451BBL 2-02443-0190Map

Owner of record: NYC Department Of Education

250 East 156 Street is a school building built in 1970 in Bronx, 10451. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
6
ECB violations
62
HPD complaints
3

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 6

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 12, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 24, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    Nyc department of education

    Mar 27, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 26, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 3, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 11, 1987

    Dob violation - resolved

ECB violations · 62

  • Class - 2

    28-301.1. unlawful display of artwork in corridors greater than 20% per fdny 2008 code; fc 803.3.2. noted: in corridor near rm #446 there are flags hanging from the ceiling throughout the whole hallway. remedy:

    Mar 26, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: classroom doors do not self-close proper;y at, 4th flr-410, 423, 434. 3rd-303.interior smoke doors do not close properly at, 1st flr-gym exit backdo

    Mar 26, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted: on the 1st flr exterior doors-"exit12", "exit 7 both doors" and exit 10 do not self-close properly when tested. remedy: repair/replace door.

    Mar 26, 2026 · Penalty $625

    Active
  • Class - 2

    Re-issue #35717267p. failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-271(j). noted: at 4th flr corridor by staircase "b" smoke door has turn kno

    Mar 26, 2026 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. noted: in electric meter room, there is stopping missing around pipes that run thru cmu block walls. remedy: provide

    Mar 26, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: use of prohibited door/and on hardware per bc 1008.1.8; 27-371(j). 4th floor corridorby stair #b has turn knobs instead of the door swinging by being pushe

    May 19, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35654910j failure to maintain building in code compliant manner:use of prohibited door and/or hardware per bc1008.1.8;27-371(j)note observed on 4th fl classrooms 473a,473b,450a,449a,449b,448,442,446a,44

    Mar 27, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    35654909m failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc1006.1;27-381.note observed on 2nd floor near stair f(#44)emergency light near r

    Mar 27, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35654908k exit door not self-closing.note observed on 1st floor stair h/exit 12 door frame is in state of disrepair due to rust/corroded door frame and door that is not allowing to operate properly.reme

    Mar 27, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Stair and/or floor identification signs missing and/or defective.note:observed at all stairways throughout the 4 story school building,the location id signs for each floor landing are not provided identifying t

    Mar 27, 2023 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code compliant manner.note observed atstair c ceiling between 1st and 2nd floor also between 2nd and 3rd floor.at stair h ceiling between 2nd and 3rd ceiling is in state of disre

    Mar 27, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:observed illegal hardware/kick stops installed on fireproof self-closing doors locate

    May 25, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35553625h exit door not selfp-closing noted:observed at 1st flr-stwyh/exit#12,door frame is rusted & door is not operating properly rem:repair/replace door.

    May 25, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:illumination forexits,exit discharges & public corridors per bc 1006.1;27-381.noted:observed existing emergency lights not operational when tested at the fo

    May 25, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue3547-exit door not self closing:exit door@staircase h,exit door12,frame rusted&not closing properly.comply w/code.

    Feb 4, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self clsoing noted at ground floor exit door at exit 12 staircase "h" door frame rusted and exit door not self closing repair /replace door

    Apr 28, 2020 · Penalty $625

    Resolve
  • Class - 1

    Unlawful acts. failure to comply with an order of the commissioner. injune 11, 2019. administrative code violation was issued to the respondent the respondent failed to comply with (nyc) administrative code 28-

    Jul 26, 2019

    Resolve
  • Class - 1

    97x17; (97-x-17)provide a working device & notify nyc dob of service restoration.

    Jul 9, 2019

    Resolve
  • Class - 2

    77b10,81b10;(77-b)repair spring buffer plates on the car(81-b)repair pistonplate under the car ,repair.

    Jul 9, 2019

    Resolve
  • Class - 1

    An unlawful act failure to comply with an order of the commissioner failure to correct and certify summons#35359876n, 35359874j and 35359875l issued on 4-23-2019 comply with ec code /ontain permit

    Jun 11, 2019 · Penalty $2,500

    Resolve
  • Class - 1

    Doors for equpment 1200a or danger shall open in the direction of egress and be equipped with panic b(). basement electrical room: no panic box provided. rmdy :comply with ec code.

    Apr 23, 2019

    Resolve
  • Class - 1

    Unapproved, unsafe,unsuitable electrical equipment, apparatus, materials, devices, appliances or wiring in use. basement electrical room; open defective temporary wiring are in use, open defective wiring are

    Apr 23, 2019

    Resolve
  • Class - 1

    No ground provided for separate derived system. basement electrical room: two 75kd transformers are not grounded. rmdy: comply with ec code

    Apr 23, 2019

    Resolve
  • Class - 2

    Reissue #350944017. failure to maintain building in code compliant manner. at 3rd floor girls bathroom next to room 352 automatic door opener not operational. rmdy: comply w/notice of violation.

    Apr 29, 2016

    Resolve
  • Class - 2

    3rd floor, girl's bathroom next to room 352 -automatic door opener not operational. remedy: maintain bldg as per code.

    Apr 30, 2014

    Resolve
  • Class - 2

    Fire stopping missing. 2nd floor fan room 209x -wall to ceiling joints. 1st floor room 176 wall to wall -ceiling. basement electric equipment -wall to ceiling joints. remedy: maintain bldg as per code.

    Apr 30, 2014

    Resolve
  • Class - 2

    Water penetration. location: roof, above exit 9e. remedy: maintain as per code.

    Apr 5, 2013

    Resolve
  • Class - 2

    Flag pole displaced. at front yard metal flag pole was knocked off of base (lying secured behind temp fencing). remedy: repair/replace flag pole.

    Jun 19, 2012

    Resolve
  • Class - 2

    Ceramic block wall bulging w/dislodged block mortar joints at exit 9e exit foyer 1st sty. remedy: repair defect noted.

    Jun 19, 2012

    Resolve
  • Class - 2

    Steel door jambs/doors rusted thru/deteriorated at various exit discharge doors throughout (approx 16 doors). remedy: repair/replace defectsnoted.

    Jun 19, 2012

    Resolve
  • Class - 2

    Water penetrating, 1st sty alcove roof at exit 9e. remedy: maintain water proof integrity of roof.

    Jun 19, 2012

    Resolve
  • Class - 2

    - doors not closing - 1) kick stops preventing doors from closing: at 4th sty cross corridor doors near rm 442, at 3rd sty cross corridor doors near 346, @ 2nd sty cross corridor door near stair d. 2) defective

    Jun 19, 2012

    Resolve
  • Class - 2

    Reissue: 34862764k the concrete block wall has 2 vertical crack located on the auditorium stage on the 1st floor level. remedy: repair and or replace cracks.

    Aug 24, 2011

    Resolve
  • Class - 2

    Interior exit doors has door knobs instead of panic push bars located on the 4th fl level at exit h. remedy: provide legal hardware.

    Jul 13, 2010

    Resolve
  • Class - 2

    The corridor width of the hallway is partially obstructed by musical instruments chairs & tables by room 414f & 406 on the 4th fl level. remedy: remove obstruction.

    Jul 13, 2010

    Resolve
  • Class - 2

    Reissue: 34760963x interior concrete block wall has 2 vertical cracks located on the auditorium stage 1st fl level & staircase leading to the cellar level with an 1/4" inch gap. remedy: repair and/or replace

    Jul 13, 2010

    Resolve
  • Class - 3

    Failure to maintain bldg walls or appurt. note: separation cracks w/mortor missing in brick facade. at bulkhead stair #8 north wall at playground 1st flr,& exit 'b' to street,above door. remedy: maintain exit

    Jan 27, 2009

    Resolve
  • Class - 2

    Sec. bc1017 failure to maintain bldg in code-complaint manner provide required corridor width per bc 1016.2,27-369 (advised principal) note: large table approx 5'x6' being stored in public corridor opposite rm

    Jan 27, 2009

    Resolve
  • Class - 2

    Failure to maintain bldg in code-complaint manner. note: separation cracks in concrete block walls & concrete beam locations auditorium rear stage wall & ceiling over stage & at cellar,at stair #11,block wall.

    Jan 27, 2009

    Resolve
  • Class - 2

    Reissue #34645804p failure to maintain bldg in code-complaint manner. note: separation cracks above exit 5 door (at 1st flr to street) cracks at joint of(lazed) block wall over door. remedy: repair defective wa

    Jan 27, 2009

    Resolve
  • Hazardous

    Reissue: 34592825h the ceiling plaster is spalling located adjacent to the electric room on cellar level. remedy: repair plaster on ceiling.

    May 30, 2008

    Resolve
  • Hazardous

    Reissue: 34592824x gymnasium movable walls are off the tracks on the 1st flr level. remedy: repair movable walls.

    May 20, 2008

    Resolve
  • Hazardous

    Reissue: 34592823y water penetration above the corridor adjacent the electrical room on cellar level. remedy: water proof above electrical room.

    May 20, 2008

    Resolve
  • Hazardous

    Glazed concrete block wall is shifting located at exit 5 on the 1st flr level. remedy: repair glazed block wall.

    May 20, 2008

    Resolve
  • Hazardous

    Stair case landing to cellar level is missing approx 15' feet of hand rail. remedy: replace missing hand rail.

    May 20, 2008

    Resolve
  • Hazardous

    Reissue # 34508762p failure to maintain exterior basement level near electrical equipment room corridor has water penetration from above school yard.remedy:make all necessary repairs.

    Aug 22, 2007

    Resolve
  • Hazardous

    Failure to maintain interior reissue # 34508764z 1st fl gym at slidingdoors are off track(seperating doors) remedy:make repairs/replace doors

    Aug 22, 2007

    Resolve
  • Hazardous

    Failure to maintain interior basement electric equipment room corridorplaster is spalling & cracking due to water penetration from school y ard above.remedy:repair plaster.

    Aug 22, 2007

    Resolve
  • Non-hazardous

    31h11/47y10. 31- guide roller worn. 47- oil leak around pump motor.

    Mar 31, 2006

    Resolve
  • Hazardous

    Note: at playground asphalt pavement has a lot of cracks and holes. remedy: repair/ rplace pavement.

    Mar 22, 2006

    Resolve

Complaints

  • Plumbing

    Basin/sink

    Dec 10, 2024 · Apt 5D

    Close
  • General

    Cabinet

    Dec 10, 2024 · Apt 5D

    Close
  • Plumbing

    Toilet

    Dec 10, 2024 · Apt 5D

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1970
Floors
4
Residential units
—
Building area
153,600 ft²
Lot area
112,814 ft²
Zoning
R8
Community board
204
Council district
16
Block / lot
2443 / 190
Assessed value
$15,159,600
Landmark / historic district
No

Questions about 250 East 156 Street

Who owns 250 East 156 Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 250 East 156 Street have violations?

NYC HPD has no housing violations on record for this property.