2712 3 Avenue
Bronx, NY 10454BBL 2-02306-0054Map
Owner of record: NYC Department Of Parks And Recreation
2712 3 Avenue is a school building built in 1958 in Bronx, 10454. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 22
- ECB violations
- 39
- HPD complaints
- 2
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 22
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 9, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 7, 2016
Dob violation - resolved - Plumbing none
Access to premises to inspect work under application #201191682 was denied. stop all work
Jul 6, 2016
Dob violation - dismissed - Elevator elevatorrequired
2s723
Feb 13, 2002
Dob violation - resolved
Show 12 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed - Elevator elevatoroptional
1
Oct 12, 1989
Dob violation - dismissed - Elevator elevatorrequired
51)restore elev to service for purporse of inspection by this dep dept 52)replace car floor
Feb 3, 1989
Dob violation - resolved
ECB violations · 39
- Class - 2
At time of inspection, sidewalk shed lighting remained installed and in use at exposure 1 and 2. electrical permit #x00149139-i1-el expired on 11/06/2021. lighting equipment is being operated without a valid el
Oct 1, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:interior fpsc doors do not self-close properly at 3rd flr-staircase d.2nd flr-library 1 door,staircase a.1st flr-auditorium.classroom doors do not sel
Jun 15, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing.noted:exterior exit doors do not self-closeproperly at auditorium exterior exit near stage right side and exit 6 1 door on first floor.rem:repair/replace door.
Jun 15, 2026 · Penalty $625
Active - Class - 2
28-301.1 unlawful display of artwork in corridors greater than 20% perfdny 2008 code;fc 80332.noted:on the 2nd flr rm#225b there were flags hanging off the ceiling throughout the room.rem:comply with notice of
Jun 15, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:in the gymnasium eight lights,in the cafeteria two lights,on the first
Sep 30, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:observed on the third floor exit 2 the door on the left is hitting on the door frame.rem:repair and/or replace.
Sep 30, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner;illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted:observed existing emergency lights w/battery back-up power were not operati
Apr 30, 2021 · Penalty $625
Resolve - Class - 3
Reissue#35414627l failrue to maintain bldg in code compliant manner. noted: at time of inspection i observed at gymnasium area floor in disrepair wood floor rotted section have been cut out soft spot & termite
Apr 13, 2020 · Penalty $500
Resolve - Class - 3
Reissue #35325684n.failure to maintain bldg in code compliant manner.noted:at time of inspection i observed at gymnasium area floor in disrepair wood floor rotted section have been cut out soft spot and termite
Apr 17, 2019 · Penalty $250
Resolve - Class - 3
Failure to maintain building in code compliant manner. noted: at gymnasium area floor in disrepair, some sections have been replaced by plywood but soft spots observed. rem: repair and/or replace.
Mar 14, 2018
Resolve
Show 29 more ↓
- Class - 2
Failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. noted: defective emergency lighting observed at 2nd floor
Mar 14, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner gym @main flr in disrepair wood flrs have wood rott sections have been cut out,soft spots and termite damage throughout.rem:replace.
Apr 19, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: lack emergency lighting for exits, exit discharges & public corridors as per bc 1006.1; 27-542. noted: @ 1st level, above security desk emergency light out# 28
Sep 14, 2016
Resolve - Class - 2
Reissue #35085574m defective exit signs. at gym and cafeteria exit signs not operational 4 at gym 1 at cafeteria. rmdy: repair or replace.
Jan 28, 2015
Resolve - Class - 2
Reissue #34982099v concrete cracked. at electrical room crack running along ceiling toward street side wall joint crack over steel bulkhead stwy concrete ().
Jan 28, 2015
Resolve - Class - 2
Reissue-35017039x doors not self closing - 1st stwy exit 4 vestibule, 2nd floor corridor doors rm 206 2nd flr stair a. rem maintain all doors as per code.
Feb 20, 2014
Resolve - Class - 2
Boiler room- louvers are not operational elec motor not connected. rem install louvers for motorized louvers.
Feb 20, 2014
Resolve - Class - 2
Sprinkler rm, water, gas meter room used as storage.(4)full height metal lockers, metal chair,ladder,ridgid.rem maintain mechanical rooms as per code.
Feb 20, 2014
Resolve - Class - 2
Defective exit signs &/or illumination not operational.gym-(4) exit lights out. auditorium-(2) exit lights out. cafeteria (1) exit light out - no emergency lighting. kitchen-(1) exit light out. rem maintain exi
Feb 20, 2014
Resolve - Class - 2
Reissue-35017040n,34982099y. 1- elec room - crack at ceiling/wall joint crack over steel column. 2- 3rd stwy bulkhead landing - stwy c concrete cracked delamination. rem maintain building as per code.
Feb 20, 2014
Resolve - Class - 2
Re-issue #34987900p. doors not closing. at: 1st sty exit 4 vestibule. at: 2nd sty corridor doors near rm 206 and 220. at: 3rd sty stair "c" (door kick stop). remedy: repair/replace doors noted.
Apr 29, 2013
Resolve - Class - 2
Reissue vio #34982099x. cracked ceiling and concrete coating over steel column at cellar electrical room. remedy: repair defects noted.
Apr 29, 2013
Resolve - Class - 2
Water penetrating bldg envelope at 3rd sty stair c/roof bulkhead landing. remedy: repair defect noted maintain weatherproof integrity of bldg envelope.
Apr 29, 2013
Resolve - Class - 2
3rd floor stwy 'c' door has kick stop to keep it open,2nd floor smoke doors near room 220 & 206 are racked. stwy 'b' door not closing. remedy: repair/replace doors,remove hold backs.
Jul 19, 2012
Resolve - Class - 2
Cellar level electrical room is being used for storage of fans,tables ,chairs,glass panels. remedy: remove storage items.
Jul 19, 2012
Resolve - Class - 2
Reissue: 34910587m at cellar level in electrical room concrete ceilingis spalling. remedy: repair/replace concrete ceiling.
Jul 19, 2012
Resolve - Class - 2
Concrete ceiling is cracked-located in the electrical room @ the cellar level.remedy:repair &/or replace concrete ceiling.
Apr 29, 2011
Resolve - Class - 2
The plaster on the wall is spalling located in the kitchen supply room @ the bsmnt level by the window.rem:repair &/or replace plaster on wall.
Apr 29, 2011
Resolve - Class - 2
Exterior metal grading is rusted & loose-located by the gymnasium exit leading into the courtyard @ the 1st flr level.(noted:heavy plywood covering the loose & rusted grading).rem:repair &/or replace metal grad
Apr 29, 2011
Resolve - Class - 2
All roof access cage doors pad locked with chains & pad locks. remedy:remove illegal hardware.
Mar 5, 2010
Resolve - Class - 2
2nd fl stwy "a" door broken & door check broken & door rocked. stwy "a" doors locked. remedy: repair/replace doors.
Mar 5, 2010
Resolve - Class - 2
Gas meter room & electrical rooms are being used to store cabinets,chairs,floor buffing machines snow blower, etc. remedy: remove storage items from rooms.
Mar 5, 2010
Resolve - Class - 2
Holes in steel & above doors of electrical room at cellar level. remedy: provide/maintain fire stopping.
Mar 5, 2010
Resolve - Hazardous
Roof has become porous & allowing rain water to enter the bldg above staircase exit no #3 on the 3 level. remedy: water-proof roof.
May 17, 2007
Resolve - Non-hazardous
Interior concrete is cracked along the column located in the boiler room on basement level. remedy: repair crack.
Apr 25, 2006
Resolve - Non-hazardous
Smoke stop doors were removed from the corridor at 2nd & 3rd fls. near rooms: 200,226,305 & 316. remedy: install doors as per ldg. code.
Jan 6, 2005
Resolve - Non-hazardous
Failure to maintain panic hardware where required by law locations:rear exits gymmnasium occ 620 from exit stage doors occ 500 remedy:provide panic hardware.
Feb 10, 2004
Resolve - Non-hazardous
Use of illegal hardware location rear exit door gymnasium & cafeteria key lock w/door knob in open position remedy:remove illegal hardware.
Feb 10, 2004
Resolve - Non-hazardous
Failure to use panic hardware where required by law : noted ; no panic hardware cafeteria doors & hallway doors cellar to 3rd floor all exits & auditorium at stage. remedy : provide panic hardware
Jan 7, 2002
Resolve
Complaints
- Heat/hot water
Entire building
Jul 9, 2026 · Apt BLDG
Close - Flooring/stairs
Stairs
Nov 19, 2024 · Apt 4C
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1958
- Floors
- 3
- Residential units
- —
- Building area
- 276,120 ft²
- Lot area
- 91,876 ft²
- Zoning
- R6
- Community board
- 201
- Council district
- 8
- Block / lot
- 2306 / 54
- Assessed value
- $18,543,600
- Landmark / historic district
- No
Questions about 2712 3 Avenue
Who owns 2712 3 Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.
Does 2712 3 Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 2712 3 Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 2712 3 Avenue built?
City records list 1958 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.