452 East 142 Street
Bronx, NY 10454BBL 2-02286-0036Map
Owner of record: NYC Department Of Education
452 East 142 Street is a school building built in 1957 in Bronx, 10454. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 16
- ECB violations
- 55
- HPD complaints
- 5
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 16
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Construction other optional
C-construction other optional
Feb 15, 2011
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed
Show 6 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed
ECB violations · 55
- Class - 2
Reissue#35721327j failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency lights on 1st flr-gym above exit g and au
Jun 12, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:interior fpsc doors do not self-close when tested at 3rd flr-staircase c.1st flrstaircase d auditorium door classroom doors do not self-close properly
Jun 12, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb #35684892m. exit door not self-closing. noted: at(3r fl) smoke door near rm 318(1st fl) auditorium, stairs a and d doors are in disrepair/not closing when tested. remedy: repair/replace door.
Aug 1, 2025 · Penalty $625
Resolve - Class - 2
Reissue ecb #35684891k. failure to maintain building in code-compliantmanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at(1st fl) gym and auditorium emergency l
Aug 1, 2025 · Penalty $1,250
Resolve - Class - 2
Exit door not self-closing.noted:observed on the third floor hallway next to room 31.on the first floor exit 2 two doors,exit k two doors,all three doors were not closing properly.rem:repair/replace door.
Sep 30, 2024 · Penalty $625
Resolve - Class - 2
Reissue#35672957x failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed on the first floor next exit d,two lights,
Sep 30, 2024 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code-compliant manner. illuminantion for exits, exit discharges and public corridors per bc1006.1; 27-381 atthe time of inspection at first floor auditorium 4 emergency exit ligh
May 16, 2023 · Penalty $625
Resolve - Class - 2
Re-issued#35473394j failure to maintain building in code compliant manner noted:observed at 1st floor gymnasium benches are missing seatingsbenches are in disrepair and non-retractable.rem:repair and/or replace
Apr 14, 2021 · Penalty $1,562
Resolve - Class - 2
Reissued35473395l failure to maintain bldg in codecompliant manner:useof prohibited door &/or hardware per bc1008.1.8;27-371j noted:observedillegal kickstops on following doors:410,409,411a,412,411b,418,420,434
Apr 14, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue35473396n/failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:observed existing emergency lights@gym@cafeteria above doorse&
Apr 14, 2021 · Penalty $1,562
Resolve
Show 40 more ↓
- Class - 2
Exit door not selfclosing.noted:observed exterior exit door@exitl in disrepair,door frame has been eaten away by corrosion&doesnt close fully,exitc&d dont selfclose&doors are extremely difficult to open.repair/
Apr 14, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code complian manner note at 1st floor gym seats missing and or broken repair and or replace
Apr 17, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner use ofprohibited door and or hardware per bc 1008.1.8;27-381 (j) the follwoing doors haveillegal kick stops installed 4h floor 430,434,441,boys& girls bathr
Apr 17, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain buildingin code compliant manner illumination for exits ,exit discharges and public corridors per bc 1006.1;27-381.note at 1st floor gyn energency light above exit a light not wokring repair
Apr 17, 2020 · Penalty $625
Resolve - Class - 2
Exit door not self-closing. noted: at bulkhead area staircase (f)(e), at 1st floor stairs (d),(e),(f),(g) and at 1st floor main entrance not self-closing doors observed. rem: repair/replace door.
Mar 14, 2018
Resolve - Class - 2
Operation of a place of assembly without a current certificate of operation. noted at 1st floor a music room with 82 seats was observed without a certificate of operation. rem: obtain a place of assembly certif
Mar 14, 2018
Active - Class - 2
Failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. noted: defective emergency lighting observed at 1st floor
Mar 14, 2018
Resolve - Class - 1
Removed order faced a written posted vacate order sticker.noted:@time of insp vacate sticker was observed to have been removed.as per complaint #2155835 on 02/16/2011 by badge #2331.for defective wall @northwes
Jan 9, 2018 · Penalty $5,000
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits, exit discharges & publuc corridors per bc 1006.1; 27-542. noted: no emergency lighting @ all staircase. @ 4th flr, exit s
Sep 13, 2016
Resolve - Class - 2
Exit door not self closing. noted: @ 3rd level, @ staircase b (near room 309) door does not self close, warped. @ staircase f on door does not self-close (away from window). @ exit d, doors do not self-close, @
Sep 13, 2016
Resolve - Class - 2
Reissue #35085354k remove hanging objects from ceilings and doors. all floors flags and ceiling decorations 3rd and 2nd flrs. rmdy: maintain bldg as per code.
Jan 22, 2015
Resolve - Class - 2
Front entrance water damage. at front entrance main above left stair case water damage visible due to leak. rmdy: maintain exterior repair or replace.
Jan 22, 2015
Resolve - Class - 2
Reissue #35085351p failure to maintain boiler room steam traps for boiler is defective leaking steam continually. rmdy: repair or replace.
Jan 22, 2015
Resolve - Class - 2
Reissue #35085353z, 35015866k exit door not self closing. 2nd story corridors doors adjoining room 332 door f stwy 1-3rd floor no door closer. rmdy: replace door closer maintian doors as per code.
Jan 22, 2015
Resolve - Class - 2
Boiler room. vacuum pump for boiler is defective leaking steam. remedy: repair &/or replace.
Feb 24, 2014
Resolve - Class - 2
Roof bulkhead doors (3) no panic bar installed. remedy: install panic hardware as per code. remove night latch from exterior side of door.
Feb 24, 2014
Resolve - Class - 2
Re-issue # 35015866k. 2nd sty corridors adjoining rm 218. 3rd sty corridors doors adjoining rm 332. stwy door stair f. stwy a- 3 floor no door closer. remedy: maintain doors as per code.
Feb 24, 2014
Resolve - Class - 2
Remove hanging objects from ceiling & walls. 1) 3rd floor corridor between rooms 317-320 flags & ceiling decorations. 2) cafeteria- ceiling & wall mounted food signs. remedy: maintain bldg as per code.
Feb 24, 2014
Resolve - Class - 2
South exit, missing bricks wall approx 4 x 13. remedy: maintain exterior as per code.
Feb 24, 2014
Resolve - Class - 2
- doors not closing - at: 2nd sty corridor doors adjoining rm 218. at:3rd sty corridor doors adjoining rm 332 and stwy doors stair "f". at 4th sty corridor doors adjoining rm 417. remedy: repair/replace doors.
Apr 22, 2013
Resolve - Class - 2
4th floor smoke doors near room 417 is racked. 3rd floor smoke doors near room 332 are racked. stwy 'f' door is racked. remedy: repair/replace doors.
Jun 28, 2012
Resolve - Class - 2
Sec. 27-371(b) plexi vision panels installed at 4th floor stwy 'a,b' &'e,f' doors. 2nd floor stwy 'e,f' & room 231 also have plexi vision panels installed. remedy: provide code complaint vision panels.
Jun 28, 2012
Resolve - Class - 2
Ash hoist metal doors are rotted. remedy: replace doors to ash hoist.
Jun 28, 2012
Resolve - Class - 2
Metal bar molding between the floor tiles & wood flooring is rising causing a tripping hazard located in the 1st flr gymnasium by the water fountain.rem:repair &/or replace metal bar molding.
Apr 28, 2011
Resolve - Class - 2
Fresh air vent in gas meter rm at cellar level is covered.remedy provide fresh air for gas metr room.
Feb 11, 2010
Resolve - Class - 2
Gas meter rm & electrical rm at cellar level are being used for storage of boxes sheet rock boxes of lamps e.c.tremedy-remove storage item from gas meter rm & electrical.
Feb 11, 2010
Resolve - Class - 2
Stairway i.d sign missing from all stairways on all floors at the staircase remedy provide stwy i.d. signs.
Feb 11, 2010
Resolve - Class - 2
4th floor smoke doors near rm 418 racked stwy d doors racked 3rd flr smoke doors near rm 332 & 317 drs are racked stwy c door racked 2 flr stwy a/c/d drs racked some drs near rm 217 racked &drs near 232 not clo
Feb 11, 2010
Resolve - Hazardous
Failure to maintain interior wall in hallway of auditorium wall building approx 1/2 inch at 6' up from flr across from gym. (glazed block approx 3'x 16' wide light blue) remedy: repair defected wall at above
Feb 21, 2008
Resolve - Non-hazardous
50a,50c,50b,b4b,b4b fitzgibbon ftfb boiler lp steam oil fired 1960e 50a asbestos hazard on boiler external insulation.perform(abatement)and re-insulate boiler shell.50b(obsolete)and defective safety valves
Aug 31, 2007
Resolve - Non-hazardous
50a,50c,50b,b4b,b4b fitzgibbon ftfb boiler lp stm oil fired 1960e 50a asbestos hazard on boiler exterior insulation perform(abatement)and re-insulate boiler shell.50b three plugged firetubes found in the boiler
Aug 31, 2007
Resolve - Non-hazardous
50a,50c50b,b4b,b4b fitzgibbon ftfb blr,lps,oil fired,1960e 50a asbestos hazard on boiler external insulation perform abatement and re-insulate boiler shell.50b obsolete and defective safety valves.replace with
Aug 31, 2007
Resolve - Hazardous
Floor tiles are cracked & missing located at exit 3 & 4 on the 3 fl. remedy: replace missing & cracked floor tiles.
May 17, 2007
Resolve - Hazardous
Wall is cracked above entrance located in the gymnasium above entrancedoor leading into the weight rm on the 1 fl. remedy: replace/ repair wall.
May 17, 2007
Resolve - Non-hazardous
Failure to maintain building. noted: fourth floor classroom 437 window has broken sash/coming apart. remedy: maintain building. repair or replace window.
Jan 6, 2005
Resolve - Non-hazardous
Failure to maintain building. noted: first floor cafeteria rear wood exit door is broken. door is split at upper & lower hinges. remedy: maintain building. replace door.
Jan 6, 2005
Resolve - Non-hazardous
Exit passageway or corridor required width decreased by obstructions. noted:basement corridors being used for storate of old desks, chairs, file cabinets, containers, blackboards, etc. large volume of debris/fu
Jan 6, 2005
Resolve - Non-hazardous
Reissue: failure to provide panic hardware where required by law at cafeteria gymnasium 7 exits at hallways. remedy: provide panic hardware.
Feb 10, 2003
Resolve - Non-hazardous
Failure to maintain - re - issue noted : at rear yard metal grating bent broken & falling apart. projecting upward at various areas causing a trip hazard remedy : repair grating immeditely
Jan 7, 2002
Resolve - Non-hazardous
Failure to provide panic hardware - re - issue where required by law. noted ; location cafeteria exits # 5 & 6 & exit at all hallways. remedy : provide panic hardware
Jan 7, 2002
Resolve
Complaints
- Plumbing
Water supply
Mar 23, 2025 · Apt BUILDI
Close - Heat/hot water
Entire building
Mar 8, 2025 · Apt BLDG
Close - Unsanitary condition
Mold
Mar 28, 2024 · Apt 2E
Close - Unsanitary condition
Garbage/recycling storage
Jul 26, 2022 · Apt BLDG
Close - Unsanitary condition
Pests
Mar 29, 2018 · Apt 4A
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1957
- Floors
- 4
- Residential units
- —
- Building area
- 146,320 ft²
- Lot area
- 116,775 ft²
- Zoning
- R6
- Community board
- 201
- Council district
- 8
- Block / lot
- 2286 / 36
- Assessed value
- $9,420,750
- Landmark / historic district
- No
Questions about 452 East 142 Street
Who owns 452 East 142 Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 452 East 142 Street have violations?
NYC HPD has no housing violations on record for this property.
Is 452 East 142 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 452 East 142 Street built?
City records list 1957 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.